Search:

Type: Posts; User: gentian

Search: Search took 0.00 seconds.

  1. bad float ?

    bad float ?
  2. Thank you .

    Thank you .
  3. Thank you. Dở you know If the TPI leak detectors...

    Thank you.
    Dở you know If the TPI leak detectors are made by Sensit, and what do you think of those leak detectors?
    Alsở I heard you were an engineer at Tif, did you have any input on the ZX 1,...
  4. Replies
    16
    Views
    1,318

    remove the battery after each use

    it says so on the manual I think. otherwise it will discharge.
  5. Replies
    10
    Views
    610

    make sure the injection solenoid valve is the...

    make sure the injection solenoid valve is the right one for that type of compressor. Copeland supplies different ones for different compressors. Are all the compressors running when this one goes...
  6. who makes yellow jacket accuprobe leak detector?

    is it Accutools that also makes their micron gauge? Thanks.
  7. in 10 years of refrigeration I have not run into...

    in 10 years of refrigeration I have not run into anyone that uses stay brite, and I have not seen any new equipment with staybrite. so if the manufacturer does not use it why would you?
  8. staybrite cracks. Not right away but 1 year or so...

    staybrite cracks. Not right away but 1 year or so down the road you will be back to fix a leak.
  9. Replies
    61
    Views
    6,712

    2 sides to a story. I have this tendency to...

    2 sides to a story.
    I have this tendency to trust the word of a hardworking supermarket tech over that of a "Know It ALL " store manager.
    All we have heard is the store manager saying how these...
  10. Replies
    61
    Views
    6,712

    I'm fine with the managers caring for their...

    I'm fine with the managers caring for their equipment. All I'm saying is that u give the techs room to work , don't be breathing down their neck, like showing them where to hook up the gauges, etc.
    ...
  11. Replies
    61
    Views
    6,712

    is this a diy forum ?!

    lets invite every store manager in this site, so next time we service their stores they can show us where to hook up the gauges and check the superheat, or even better, give them a tool bag so they...
  12. Replies
    23
    Views
    2,168

    siemens/furnas doesn't make contactors any more,...

    siemens/furnas doesn't make contactors any more, united refrigeration started carrying cutler hammer
  13. Replies
    24
    Views
    1,597

    is sight glass before or after drier? Have had...

    is sight glass before or after drier? Have had driers with 20 pressure drop across them with no frosting or temp difference at all. for me low suction pressure with a high superheat and with a clear...
  14. Replies
    21
    Views
    1,784

    "Just a little bit outside"

    "Just a little bit outside"
  15. Replies
    41
    Views
    12,780

    That could be 1 of the problems with the...

    That could be 1 of the problems with the fielpiece IR, or simply, it is just not as good as the Manufacturer says it is.
    But from what I hear is pretty good at detecting termites.:grin2:
  16. Replies
    41
    Views
    12,780

    Turned on both tekmate and the Ir outside....

    Turned on both tekmate and the Ir outside. tekmate picked up the evaporator leak as soon as I walked in the box. Once i took apart the evaporator and got close to Ubends the fieldpiece picked it up....
  17. Replies
    41
    Views
    12,780

    Brand new

    Brand new
  18. Replies
    41
    Views
    12,780

    r22, but had same experience with 404a.

    r22, but had same experience with 404a.
  19. Replies
    41
    Views
    12,780

    It was R22, but same thing has happened with...

    It was R22, but same thing has happened with 404a. The srl2 will not pick up a leak unless you are right on top of the leak, that's just unacceptable in supermarket work where i have to leak check a...
  20. Thread: Leak Detector

    by gentian
    Replies
    49
    Views
    7,409

    fieldpiece infrared sucks, especially in...

    fieldpiece infrared sucks, especially in supermarkets. try it on you car Ac, that's all is good for.
  21. Replies
    41
    Views
    12,780

    the fieldpiece infrared just sucks. Worked in a...

    the fieldpiece infrared just sucks. Worked in a walkin cooler with half of the evaporator u bends with pinholes. tekmate starts going nuts as soon as I opened the door. the fieldpiece nothing, just...
  22. Replies
    1
    Views
    796

    SMAN2 & 3 on Fieldpiece website

    anyone has 1 yet ?
  23. Replies
    28
    Views
    4,480

    not pumping but cutting out on LPC?

    how can that happen?
  24. Replies
    0
    Views
    422

    switching case from low to medium temp

    customer wants a multideck frozen meat case 402A turned into a deli medium temp case. Do I need to install an epr valve to try to raise the suction pressure from 15psi to 58-60psi ? right now the...
  25. Replies
    4
    Views
    756

    seen that alot

    at the Shoppers stores here in maryland/virginia, mostly meat preps and meat walkins it keeps evaps from getting dirty
  26. Replies
    7
    Views
    1,451

    Hussman Gel reach in

    I have hussman low temp GEL reach in cases that are icin up on the bootom of case and evaporators are icing up.
    Most of the case are icecream case set -17 degrees, some of them are set at -12...
  27. Replies
    176
    Views
    24,006

    I have had the digicool 1250 for 2 months now ,...

    I have had the digicool 1250 for 2 months now , good quality but the dual temp probes suck, wires too thin and they get tangled too easily, don't think those things going to last very long, every...
  28. Replies
    26
    Views
    2,090

    that looks a lot like UEI Phoenix series

    that looks a lot like UEI Phoenix series
  29. Replies
    26
    Views
    1,701

    anyone here drinks 5hour energy

    it works for me, had 6 the other night I was on call after a 16 hour shift, felt great, just my team Leader couldn't understand a word I was saying, weird!
  30. Thread: testo 410-2

    by gentian
    Replies
    5
    Views
    1,363

    testo 410-2

    anyone has used this 2 in1 psychrometer with vane anemometer?
    Just ordered it for $190.
    I started doing supermarket refrigeration, got it just to give me an idea of the conditions of the store...
Results 1 to 30 of 30
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine
Comfortech365 Virtual Event