Search:

Type: Posts; User: cperk

Page 1 of 20 1 2 3 4

Search: Search took 0.02 seconds.

  1. We need a realist in there, all this s@"t would...

    We need a realist in there, all this s@"t would be fixed!


    Sent from my iPhone using Tapatalk
  2. Replies
    23
    Views
    2,750

    Water will just complicate the problem. Tell them...

    Water will just complicate the problem. Tell them your gonna half to shut her down to assess the situation.
    How did the ice get there? Door closer not working? Door held open for inventory (love...
  3. You can let the bypass control the D.P. in the...

    You can let the bypass control the D.P. in the bldg. Seems kinda Rube Goldburg-ish to me though. Why not just have a three way valve at the air handler-s to bypass the water and do away with the...
  4. Looks like variable primary to me. First you need...

    Looks like variable primary to me. First you need to know the minimum flow requirements for the chiller. Second you must have something reading the flow through the chiller, a diff. press....
  5. Replies
    2
    Views
    841

    I would assume it is because the fins on the...

    I would assume it is because the fins on the outer coil do not line up with fins on the inner coil. Thus everything that is coming between the outer coil fins hits the inner fin dead center and...
  6. Replies
    21
    Views
    1,371

    With most newer drives you can enable a flying...

    With most newer drives you can enable a flying start parameter. This allows a motor to be spinning at any speed and when drive gets a run command it starts at 60hz then "hunts" the speed of the...
  7. Replies
    13
    Views
    5,463

    We have had to replace several coils on cgaf's....

    We have had to replace several coils on cgaf's. Some were still under warranty. Ask your local Trane office.
  8. Replies
    21
    Views
    3,495

    That's it! I'm never huffing again, especially if...

    That's it! I'm never huffing again, especially if it's going to give me heart disease or a vagina.:putergreet:
  9. Replies
    21
    Views
    3,495

    LOL! I'm dusting off my keyboard right now with a...

    LOL! I'm dusting off my keyboard right now with a refrigerant hose and a drum of:censored:.
  10. Thread: Manly help

    by cperk
    Replies
    8
    Views
    896

    Aren't you supposed to sweat when you...

    Aren't you supposed to sweat when you workout?:angel:
  11. I would check it again after it pulled the space...

    I would check it again after it pulled the space down.
  12. Replies
    2
    Views
    1,406

    If it has the ribbon cable, and I assume it does,...

    If it has the ribbon cable, and I assume it does, check the comm connections from the chiller module to your fan relay output board and to your 1A starter module.
  13. Replies
    4
    Views
    593

    Are you talking about when the pump shuts down?...

    Are you talking about when the pump shuts down? Then your tower sump starts overflowing? If so, it has nothing to do with the check valve, it is the stopping of the pump. When the pump stops, it...
  14. A hot gas by-pass would work.

    A hot gas by-pass would work.
  15. Replies
    8
    Views
    1,013

    Motors that come with plugs have a sealed...

    Motors that come with plugs have a sealed bearing. On a motor with a fitting the drain plug is on the opposite side of bearing from the grease fitting, so the grease pushes through the bearing before...
  16. Replies
    56
    Views
    12,515

    Lennox has a commercial line? HEY are you the guy...

    Lennox has a commercial line? HEY are you the guy with big mustache in the Lennox ads?
  17. I have to argue with all of you guys. I got a...

    I have to argue with all of you guys. I got a pretty good sample of oil the first oil temp. sensor I tried to change. I thought it had a well. I was wearing enough oil to fill at least 10 of those...
  18. Replies
    5
    Views
    957

    Check the oil cooler. TEV powerhead cap tube is a...

    Check the oil cooler. TEV powerhead cap tube is a good place to start.
  19. Replies
    18
    Views
    2,899

    Did you meg the comp. or ohm it. Chase1 has a...

    Did you meg the comp. or ohm it. Chase1 has a good point about the crankcase heaters. If comp. is filled with liquid refrigerant (or) too much oil, it could be grounding it enough to blow a fuse. I...
  20. Thread: Trane Techview

    by cperk
    Replies
    6
    Views
    1,654

    Biggest tip I can give is, when you get into...

    Biggest tip I can give is, when you get into binding view it puts the machine in local stop. Then you have to hit auto for the machine to start. I ran into this on two emergency chillers that were...
  21. Replies
    15
    Views
    2,886

    Ditto, and also low discharge temp. with a...

    Ditto, and also low discharge temp. with a pulsating oil seperator.
  22. We had one building that had three way valves all...

    We had one building that had three way valves all throughout, with a VSD. We went in and made blankoffs for the bypasses on all but the end of the piping air handler. We done this to keep hot or...
  23. Replies
    34
    Views
    2,638

    You sChould take a dictionary, so you don't...

    You sChould take a dictionary, so you don't incorrectly spell words on the invoice.
  24. Replies
    65
    Views
    13,940

    This is why you need your gauges AND your...

    This is why you need your gauges AND your thermometer, to check superheat and subcooling. This will tell you to look at other things like dirty coils, TXV's and airflow.
  25. Thread: Joy axial fans

    by cperk
    Replies
    15
    Views
    4,063

    Yeah we have a bunch of them. On alot of them we...

    Yeah we have a bunch of them. On alot of them we have done away with the actuators that pitch the fan. We built some brackets to pitch them all the way loaded and installed VFD's on the motors. The...