Search:

Type: Posts; User: MaxBurn

Page 1 of 20 1 2 3 4

Search: Search took 0.03 seconds.

  1. Replies
    6
    Views
    245

    Is this for WebCTRL? ALC does tend to lag in...

    Is this for WebCTRL? ALC does tend to lag in getting a patch out after finding some new java update breaks something for 5.5 and lower.

    Your dealers service dept should be able to send you the...
  2. Replies
    6
    Views
    245

    Constant annoyance, I'm so glad we don't need...

    Constant annoyance, I'm so glad we don't need java anymore with the latest version.
  3. Replies
    30
    Views
    1,309

    I have a couple of these, one for the laptop and...

    I have a couple of these, one for the laptop and one for me. They fit in my backpack. About $9.

    http://www.dickssportinggoods.com/graphics/product_images/pDSP1-10886923p275w.jpg

    I must admit...
  4. Replies
    3
    Views
    248

    That driver suggests that you are looking at an...

    That driver suggests that you are looking at an integration already, to a Dataguard system. You will likely find something between 200 and 1000 points of integration under that LGR. The points in the...
  5. Sounds like you need a local account added to...

    Sounds like you need a local account added to that computer so you can login to it with no network access. If it's normal for it to not have network access than that's not really optional.
  6. Replies
    3
    Views
    206

    Depending on what version of software the LGE was...

    Depending on what version of software the LGE was used under there are two different ways to put the IP in.

    If it is "legacy" exec 6 it needs to be programmed with supervision or webctrl as a...
  7. Replies
    9
    Views
    1,062

    It might already depending on how it was...

    It might already depending on how it was programmed.

    Turn it off and move the ARCnet/9600/38400 jumper to the 9600/38400 side and turn dip switch 1 on for 38,400 or off for 9600. Wire your MS/TP...
  8. Replies
    8
    Views
    570

    Thanks for sharing! Wonder how many hours of...

    Thanks for sharing!

    Wonder how many hours of programming went into that thing? Each one had to be a one off production I bet.
  9. Replies
    4
    Views
    288

    Yes just some basic due diligence before you call...

    Yes just some basic due diligence before you call them back but it does seem to be that device that's the issue.
  10. Replies
    4
    Views
    288

    Does your module work right next to the device...

    Does your module work right next to the device you are reading?

    Do the other usual wire checks, ohming to each other and each to ground etc.

    Can you get modscan and a communication adapter to...
  11. If you are concerned with the wall contaminating...

    If you are concerned with the wall contaminating the temp reading of the stat I don't think you need a new stat, just add some insulation behind the stat. Should be a foam wall plate backing...
  12. Replies
    21
    Views
    1,239

    I'm now carrying a fluke 376 with integrated amp...

    I'm now carrying a fluke 376 with integrated amp clamp and back light, I've taken a real liking to it. For ages I've carried the various versions of the fluke 77 and I still have one but that's...
  13. Replies
    8
    Views
    240

    Seconded, I ran into this as well. The new ZN...

    Seconded, I ran into this as well. The new ZN modules are shipping with updated hardware which requires a 6.xx.xxx module driver.

    Basically the stance of ALC is always use the latest module...
  14. Replies
    10
    Views
    433

    What got me ahead or on track etc was taking the...

    What got me ahead or on track etc was taking the equipment and software home and taking the time to understand what's going on and nailing how to do certain tasks. Ask to take some things home (on...
  15. Replies
    4
    Views
    431

    Yes, on the ALC side there are several updates...

    Yes, on the ALC side there are several updates you need to view trends with the most recent java version. For us the patches are posted on ALC support site, do you have such a thing?
  16. Replies
    5
    Views
    326

    Hey ControlsFreak, where do I get seeds for one...

    Hey ControlsFreak, where do I get seeds for one of those?
  17. Replies
    1
    Views
    156

    As I understand it that isn't a comm port, it's...

    As I understand it that isn't a comm port, it's for bias and termination.

    http://www.ccontrols.com/pdf/TD0712000I1.pdf
  18. Replies
    9
    Views
    379

    If you want to run anything in the LGR yes, it...

    If you want to run anything in the LGR yes, it has to be an execB equipment file.

    From the cut sheet: The Hybrid LGR is supported in WebCTRL v4 SP1b or later systems.
  19. Replies
    9
    Views
    379

    The hybrid LGR is a way to go, you can run legacy...

    The hybrid LGR is a way to go, you can run legacy CMnet off of port S1 and new ARCnet modules off of that port. The only drawback I can think of is you can't run a legacy FB in it.
  20. Replies
    2
    Views
    305

    As I understand it they are using HTML5 somehow....

    As I understand it they are using HTML5 somehow. I don't really know at that level but you don't need java or flash for most of WebCTRL now.
  21. Yes, before I made the switch I had OSX running...

    Yes, before I made the switch I had OSX running in a VM too.
  22. Thread: Control Jobs

    by MaxBurn
    Replies
    3
    Views
    429

    I'm not sure, maybe you want to bring that up to...

    I'm not sure, maybe you want to bring that up to the committee?
  23. Replies
    14
    Views
    1,277

    Do you have a make and model number to share with...

    Do you have a make and model number to share with us? Does it have the Google play store on it?
  24. Thread: Control Jobs

    by MaxBurn
    Replies
    3
    Views
    429

    I believe it's limited to professional members...

    I believe it's limited to professional members but, yep.
  25. Osiyo; unfair or not I DO lump the ecosystem that...

    Osiyo; unfair or not I DO lump the ecosystem that surrounds a company, it is within their power to clean things up and make it better, of course that likely would disrupt things. It's a trade off but...
Results 1 to 25 of 500
Page 1 of 20 1 2 3 4
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine
Comfortech365 Virtual Event