  1. Replies
    2
    Views
    247

    I would change it at 3.

    I would change it at 3.
  2. Replies
    17
    Views
    6,299

    I had my holland do the same thing. It ended up...

    I had my holland do the same thing. It ended up being the tank was over filled. I bleed of some propane and wala.
  3. Replies
    12
    Views
    1,719

    I worked on one that had this problem before. It...

    I worked on one that had this problem before. It was a liquid line solonoid valve leaking by on shut down
  4. Replies
    11
    Views
    1,143

    I have fixed leaks before like that with 15% silv...

    I have fixed leaks before like that with 15% silv solder. I went to a install class last month on Daikin. Got to go to the service class in December. I'm not impressed with them. Kinda dread working...
  5. Replies
    4
    Views
    494

    Thanks for the info. I contacted leibert to find...

    Thanks for the info. I contacted leibert to find out what the universal monitor did when it got a alarm. It pages out to a pager. to get a message on a cell phone they have to call there provider and...
  6. Replies
    4
    Views
    494

    the unit has the icom on the front panel. The...

    the unit has the icom on the front panel. The panel I need to hook up is called Universal Monitor. Its a remote mounted panel that is capable of pageing a pager or sending a text message if an alarm...
  7. Thread: no oil

    by d_lee1
    Replies
    6
    Views
    513

    if you have good oil level watch your oil...

    if you have good oil level watch your oil pressure. see if flucates. I have had them tripping from the txv over feeding washing the oil from the pump causing the pressure to drop to low. Check your...
  8. Replies
    4
    Views
    494

    Liebert Universal Monitor

    I Put in a liebert M#VS070AMA0E1277A. After unit was in and running they came up with this universal monitor. I never put one in before. Looks like I need a space sensor which did not come with...
  9. Replies
    2
    Views
    529

    carrier service tool IV

    anyone using service tool IV for carrier controls? want to know your opinions. I currently use comfort view. If its better going to try to talk the boss in getting it.
  10. Thread: Rheem Furnace

    by d_lee1
    Replies
    30
    Views
    2,136

    good thing sarcasim is free twillie cause here id...

    good thing sarcasim is free twillie cause here id be broke.
  11. Thread: Rheem Furnace

    by d_lee1
    Replies
    30
    Views
    2,136

    thanks for your info there jp. but if i wanted...

    thanks for your info there jp. but if i wanted youre sarcasim i would have asked for it. oh and i don't believe i did.
  12. Thread: Rheem Furnace

    by d_lee1
    Replies
    30
    Views
    2,136

    not sure gas line size from outside. 1/2 black to...

    not sure gas line size from outside. 1/2 black to upstairs furnace. gotta go back as soon as customer. returns. gas wasn't low.didn't drop below 13 running. goes up to 16 with nothing running....
  13. Thread: Trane tracer

    by d_lee1
    Replies
    5
    Views
    637

    as far as time schedule?calibrate automatically...

    as far as time schedule?calibrate automatically by itseslf at a certain time. or a calibrate table! I have another building also that has summit. it has a pc onsite. easy to use has a calibrate...
  14. Thread: Rheem Furnace

    by d_lee1
    Replies
    30
    Views
    2,136

    Then man is out of town waiting for him to get...

    Then man is out of town waiting for him to get back. I'm going to check the regulator.when the down stairs furnace fired the inlet pressure drops 3".but it doesn't go below min required prs.could be...
  15. Thread: Trane tracer

    by d_lee1
    Replies
    5
    Views
    637

    Trane tracer

    I have to replace the motor and back-plate assy on a varitrane parallel box. there is a computer monitor on site.(dos based)yellow screen. I do not have rover. if i put the new damper in the same...
  16. Thread: Carrier VVT #3

    by d_lee1
    Replies
    5
    Views
    1,345

    i worked alittle with the gen controls, alot with...

    i worked alittle with the gen controls, alot with comort id. was told not to hook the ground on the sensors unless having a problem reading the sensor. as far as the buss itself you only hook the...
  17. Replies
    28
    Views
    12,130

    emoney its according on who makes the box. I work...

    emoney its according on who makes the box. I work on alot of reddi boxes that are phnematic that gets a air signal to operate..been converting alot of those over to ddc carrier comfert id. which you...
  18. Thread: Rheem Furnace

    by d_lee1
    Replies
    30
    Views
    2,136

    Thanks for all the advice..got every-thing but...

    Thanks for all the advice..got every-thing but the answer to my question.Im not a dumb service tech with just a few years experince. Been in the buisness for a while. just never seen that problem...
  19. Thread: Rheem Furnace

    by d_lee1
    Replies
    30
    Views
    2,136

    propane.

    propane.
  20. Thread: Rheem Furnace

    by d_lee1
    Replies
    30
    Views
    2,136

    the inlet gas pressure is rated max 14. 13 1/2...

    the inlet gas pressure is rated max 14. 13 1/2 running.manifold 10" rated 10". the flame does not change when fired, looking up in the exchanger from the burners no cracks seen. every one i found...
  21. Thread: Rheem Furnace

    by d_lee1
    Replies
    30
    Views
    2,136

    Rheem Furnace

    Hi, I recently looked at a furnace for a friend. rheem upflow gas furnace 3 burners. aprox 12-15 yr old. Fire was popping and burning back in the burners. seen this happen before so I new burners...
  22. Thread: D.O.A. O6E

    by d_lee1
    Replies
    21
    Views
    1,786

    O6E

    I HAVE STARTED EQUIPMENT NEW AND FOUND THAT PROBLEM. THE COMPRESSORS I HAD A PROBLEM WITH WERE 06D,S.THE OIL IN THE SIGHT GLASS DISSAPEARED AND NEVER CAME BACK CAUSEING ALL KINDS OF NOISIES. MY...
  23. Replies
    4
    Views
    1,835

    it has the exv with the sight-glass.what is the...

    it has the exv with the sight-glass.what is the fix for the exv when it cant respond quick enough with the building load? the system has fan coils with 3way walves.
  24. Replies
    12
    Views
    1,547

    I had the same problem and it was the tubing...

    I had the same problem and it was the tubing cutter. I use to run alot of pipe and I found that with me 1-1/8 up the cutter would leave a ridge.So I bought a rigid but have to keep a new blade in it...
  25. Replies
    4
    Views
    1,835

    T114+T115 Alarms

    I have checked T5 + T6 thermistors and compared them with my fluke digital thermometer and my fluke 189 with temp probe.verified voltage and resistance with the chart in the book. and verified with...