    the valve checked good the heat added and then...

    the valve checked good the heat added and then dip into and ice bath, responsive to both
  2. Replies
    28
    Views
    8,634

    tXV

    The TXV was changed from the factory Danfoss to a Sporland, The equalize line was check for flow. All checked good. Air flow was double checked by checking pressure drop a crossed the coil. .58”wc
  3. Replies
    28
    Views
    8,634

    Fixed

    Sorry for the delaying in posting, While I was on vacation, another tech replaced the indoor coil. After replacement the system ran at spec's 12 deg s/c 9 deg of s/h. althought the coil would frost...
  4. Replies
    28
    Views
    8,634

    As did I with three different instruments A...

    As did I with three different instruments A cooper digital. Field Piece digital. And my old standby yellow jacket and fluke temperature probes. Nothing makes sense. How can a evap show flooded and...
  5. Replies
    28
    Views
    8,634

    The Refrigerant charge was recovred and weight...

    The Refrigerant charge was recovred and weight back in @ factory specs added 5 lbs more. and removed 10lbs. still little change is s/c
  6. Thread: infinity system

    by MIDCAM
    Replies
    7
    Views
    874

    Infinity Issue

    Did the screen read critical malfunction or system malfunction? Critical malfunction are when the infinity control cannot commutate with the blower. Or there is a blower motor fault. This is a hard...
  7. Replies
    28
    Views
    8,634

    Compressor @ 60% of fla air flow @ 700cfm

    Compressor @ 60% of fla air flow @ 700cfm
  8. Replies
    28
    Views
    8,634

    25HNB624 with an FE4ANF003 Air Handler. 90 deg...

    25HNB624 with an FE4ANF003 Air Handler.
    90 deg ODBD Pressures 298/138# liquid line@ service valve 93deg vapor @ service valve 52 deg.
    air flow @ 700 CFM +/- 20 cfm
    RA 76 deg db 67 Deg wb
    SA ...
  9. Replies
    28
    Views
    8,634

    Low Subcooling Low Superheat?

    I am working on a two stage heat pump with a varable speed air handler.
    The system runs about 1.5 deg S/C and about 2 deg S/H The delta T is 22 deg. A capacity check shows systems is operation at...