  1. Thread: Siemens

    by Arpoc926
    Replies
    4
    Views
    786

    it simulates HMI user inputs. For example and...

    it simulates HMI user inputs. For example and OIP for that ran the following:

    00010 OIP ("point.log","s/h/f/a/x/x/x/x/x")

    on an apogee panel would add a Field Panel to the panel database that...
  2. Replies
    3
    Views
    645

    You should add points to a UC from the system...

    You should add points to a UC from the system profile. Double click on the UC, then select the "edit points" radio button -> select "New Points" and go to town. The points you create will be...
  3. Replies
    15
    Views
    1,968

    There are indeed no conflicts specific to Insight...

    There are indeed no conflicts specific to Insight 3.11. If you have taken WillyTech's advice, and restored your DB, then it is indeed time to call your branch. Any further troubleshooting would...
  4. Replies
    15
    Views
    1,968

    If there are no errors in APbacklog.txt then it...

    If there are no errors in APbacklog.txt then it may be an issue with revising from 3.6 to 3.7, which I am pretty confident there is a Field Support News article about. I also recall problems with...
  5. Replies
    15
    Views
    1,968

    sorry it took so long to get back to you. ...

    sorry it took so long to get back to you.
    Check APbacklog.txt (a file in Insight/Database) in an application like Notepad++, for any occurrences of the word "error". At the end of each...
  6. Replies
    1
    Views
    418

    If your trend successfully collected on a time...

    If your trend successfully collected on a time basis, but your problem is the value of the change, then have your tech check the Point definitions for Dyamic COV values or the SLOPE value. If a...
  7. Replies
    14
    Views
    1,651

    I have heard of some building managers putting...

    I have heard of some building managers putting T-stat boxes in each office, with setpoint dials that don't do anything at all. I would never do that, nor do I approve of it. But it is pretty cheap,...
  8. Probably the only alternative, as terrible as it...

    Probably the only alternative, as terrible as it may be (assuming you absolutely won't buy more equipment or have siemens bang out a new app), is to write PPCL that commands those subpoints to be...
  9. Yeah...proprietary

    Sorry. Those tools are proprietary, and I they keep a pretty tight grip on distribution.
  10. Thread: First Bacnet

    by Arpoc926
    Replies
    47
    Views
    3,467

    Obviously, BACnet, I defer to your expertise. I...

    Obviously, BACnet, I defer to your expertise. I was concerned that the network architecture might be other than what is represented in the diagram you supplied. If, in fact, the OP had an alternate...
  11. Replies
    15
    Views
    1,968

    WillyTech is absolutely correct. It might be...

    WillyTech is absolutely correct. It might be inconvenient, but it is the only way to guarantee a complete upgrade.

    Removed Link. You need to be a Pro Member in order add a link to your company....
  12. You have to utilitize the Siemens Application...

    You have to utilitize the Siemens Application Builder software in order to change the custom application on the PXCC on P1. This is true for both changes in point definition or changes in...
  13. Thread: First Bacnet

    by Arpoc926
    Replies
    47
    Views
    3,467

    This might be a silly question, but are you...

    This might be a silly question, but are you trying to "WhoIs" across your router with the BBMD turned off? If they are on different subnets, this will not work.
  14. Replies
    2
    Views
    690

    It should be possible to route through a field...

    It should be possible to route through a field panel's MMI connection, by going to "Device"-> Connection settings-> Route, and selecting the desired TEC name. From that point, WCIS will act as...