Search:

Type: Posts; User: jczekai

Page 1 of 2 1 2

Search: Search took 0.00 seconds.

  1. Replies
    7
    Views
    3,376

    If you could contact someone for me that would be...

    If you could contact someone for me that would be great. My email is in my profile.... I talked w/ a Mike .?. from Mechanicsberg, PA this morning and he told me that he doesn't think Carrier is...
  2. Replies
    7
    Views
    3,376

    I already seen those and took a look at them. The...

    I already seen those and took a look at them. The job I'm looking at has over 400 controllers throughout the buildings. I looked at the LON conversion module, but really would prefer to use a CCN...
  3. Replies
    7
    Views
    3,376

    Carrier CCN to Tridium AX

    I was wondering if anyone has successfully integrated to the Carrier Comfort Network either through RS485 or Ethernet. I would like to use a AX JACE to do the integration if possible. I know Carrier...
  4. Thread: N30 Interlock

    by jczekai
    Replies
    3
    Views
    543

    I always setup the interlocks like that, I use...

    I always setup the interlocks like that, I use the interlocks a lot w/ the VMA controllers and global commands like Morning Warmup, etc...

    I have never had a problem w/ it. Do you have the project...
  5. Replies
    9
    Views
    839

    We use all kinds of different controllers, mostly...

    We use all kinds of different controllers, mostly we choose by what fits application and has lon or bacnet comm on it. I didn't mean that in a bad way, the only time we have been using JCI is when we...
  6. Replies
    10
    Views
    1,487

    So all of the programmed N2 points would then be...

    So all of the programmed N2 points would then be available via BACnet just like a N30 controller?

    Thankx
    Jamie
  7. Replies
    9
    Views
    839

    To be honest, I have found so my reasons not to...

    To be honest, I have found so my reasons not to use the FX line of field controllers. I feel that JCI developed the controlers about 50% then released them to the contractors to deal w/ and BETA test...
  8. Replies
    20
    Views
    1,703

    From my experiene w/ PLC controllers, you usually...

    From my experiene w/ PLC controllers, you usually have to know quite a bit about the programming. This is b/c in the "RUNGS" you usually have to create coils and holding registers to view the values...
  9. Replies
    20
    Views
    1,703

    FYI, Here is a license from a FX40...

    FYI, Here is a license from a FX40...
  10. Thread: N30 Interlock

    by jczekai
    Replies
    3
    Views
    543

    In the interlock "Action Tables" select Override...

    In the interlock "Action Tables" select Override instead of the value from the "Command" drop down. Then select the "List Elements" box button, then select the value you want. Do it this way will...
  11. Replies
    9
    Views
    839

    I have done a few FX15 controllers in R2, it suxs...

    I have done a few FX15 controllers in R2, it suxs b/c you can't learn the NCIs into R2. What I had to do was create NVIs in FX Builder to adjust. It works fine doing this, you just have to make sure...
  12. Replies
    10
    Views
    1,487

    Is this something that JCI has to do w/ there...

    Is this something that JCI has to do w/ there configuration software or is it something that I can do through there web browser? I have all the passwords for the NAE but just haven't connected to it...
  13. Replies
    20
    Views
    1,703

    I would say not to use a JCI Integrator or FX40!...

    I would say not to use a JCI Integrator or FX40! Since the job is already N30s it most likely already has a M3 or M5 Workstation. I have used Integrators before, I basically ended up throwing it out...
  14. Replies
    10
    Views
    1,487

    ..:: NAE to Tridium AX via BACnet ::..

    Does anyone know if there is a way to expose the points in a NAE as BACnet/IP or another protocol that we could then intergrate the points into a Tridium AX system?

    Johnson came in on this...
  15. Replies
    9
    Views
    839

    Just send it to Tridium and they will make it...

    Just send it to Tridium and they will make it into a shadow odject for you! There is no way to make it yourself easily in R2. You could also just use a "DynamicDevice" in R2 and "Upload" the config...
  16. Replies
    5
    Views
    789

    The way we have done it in the past is purchase a...

    The way we have done it in the past is purchase a BCU, then expose the points as BACnet/IP. The BCU is a little high in price but it is cheaper than ripping out all the controls!
  17. Thread: FX40 and M3

    by jczekai
    Replies
    8
    Views
    1,715

    If you open the FX-40 controller, then open up...

    If you open the FX-40 controller, then open up the Bacnet "Jar" file on your palette....

    In the palette you should see a folder called "Point".........

    Expand the folder and you will see a...
  18. Replies
    21
    Views
    6,480

    Did you ever find a driver to communicate to the...

    Did you ever find a driver to communicate to the ASD bus? I have a campus that has hundreds of the Microzone controllers communicating to GCMs throughout the campus, then to a wonderware system that...
  19. Replies
    2
    Views
    686

    There is no demo with any flavor of workbench....

    There is no demo with any flavor of workbench. Its on a per computer license, and the license is digitally signed from Tridium (uneditable).
  20. Replies
    2
    Views
    663

    Go to the objects toolbar, then click outputs,...

    Go to the objects toolbar, then click outputs, add a Position Adjusting Time Output -- used for floating control

    Thankx
    Jamie
  21. Replies
    6
    Views
    1,290

    Y wouldn't you just buy the BACnet (IP or MSTP)...

    Y wouldn't you just buy the BACnet (IP or MSTP) or Lon Interface board from JCI/York. We have bought the both versions of the BACnet in the past. Its probably a lot cheaper and easier than...
  22. Replies
    8
    Views
    3,843

    Good luck, the trane software is very expensive...

    Good luck, the trane software is very expensive and is licensed on a per machine basis. NO SHARING AT ALL, and theres really no way around it besides sending lots of $$$$$$$$.
  23. Thread: York BAS

    by jczekai
    Replies
    16
    Views
    2,553

    Most of Yorks controls weren't porpritory b/c...

    Most of Yorks controls weren't porpritory b/c most they resold other manufacturers controls. Most of the York controls that I have seen are Delta Controllers repackage with the York name on it.
    ...
  24. Replies
    20
    Views
    1,662

    I never really created them, just heard of the...

    I never really created them, just heard of the ability to make them. They would have to be very generic graphics with no animations, pretty much just the data from a point. Then the canvas pane on...
  25. Replies
    20
    Views
    1,662

    Did you make different graphics? HX is used for a...

    Did you make different graphics? HX is used for a PDA, cell, etc. PX is used for IE, Firefox, etc.
  26. Thread: Trane VAV

    by jczekai
    Replies
    4
    Views
    779

    Fyi

    Fyi
  27. Thread: York BAS

    by jczekai
    Replies
    16
    Views
    2,553

    If it is a York underfloor system I would stay...

    If it is a York underfloor system I would stay far away from it. We subcontracted York to install underfloor systems in four different buildings and the systems still don't right. The underfloor...
  28. Thread: Trane VAV

    by jczekai
    Replies
    4
    Views
    779

    Sounds like low side switching, floating 24v...

    Sounds like low side switching, floating 24v acuator. The 24v common is most likely sourced through the BO triac and if either float open or float closed turns on the damper drives.

    To wire the...
  29. Replies
    9
    Views
    3,674

    I have demo controller and they can be configured...

    I have demo controller and they can be configured in either AX or WEBS. I really don't know of any programming documents out there, all ive seen is sales brochures. But if you know Tridium they are...
  30. Replies
    5
    Views
    1,188

    Take a look at this, there is PLC labeled...

    Take a look at this, there is PLC labeled SEC_PUMP. Basically the pumps switch automatically every 2 weeks (adj) if not in alarm.

    Rename file to .dxs

    Thankx
    Jamie
  31. Replies
    12
    Views
    995

    I just tried it in my office, I am running Win XP...

    I just tried it in my office, I am running Win XP Pro and Mtools 5.4.

    Here is what I did....
    1. Open up Site Book
    2. Add a Connection, Direct Serial
    3. New Phonebook Entry
    4. Name it "N30...
  32. Replies
    4
    Views
    542

    You could have up to 8 pages of PLC w/ 8 lines of...

    You could have up to 8 pages of PLC w/ 8 lines of code.
  33. Replies
    9
    Views
    799

    I would say more of a computer job. I have worked...

    I would say more of a computer job. I have worked for a large mechanical contractor, for the past five years. I actually went to college for Computer Information Technology and now have a degree in...
  34. Replies
    1
    Views
    549

    There could be a lot of reasons why the Alarms...

    There could be a lot of reasons why the Alarms are not showing up, most likely M-Alarm isn't connecting to the N30 notifaction class.


    The workstation name in the Site Book will use the computer...
  35. Replies
    12
    Views
    995

    The Sitebook connection probably isn't setup...

    The Sitebook connection probably isn't setup correctly. You can do what is called a Port 3 Dump.


    To obtain an N30 port dump:

    1) Connect a PC with VT100 to Port 3 of an N30.
    2) Launch the...
  36. Replies
    4
    Views
    944

    The battery stores the realtime clock, counter...

    The battery stores the realtime clock, counter values, supervisory control mode, and all RAM items. Ram items are all R or R/W items shown without the (E) in the item list (Appendix B).
    ...
  37. The problem is probably with Windows and...

    The problem is probably with Windows and Licensing of PMI. Remote Desktop uses Terminal services and a lot of programs will not work when Terminal Services opens up. This is so that you have to buy...
  38. Replies
    12
    Views
    995

    I would try changing the name of the site, call...

    I would try changing the name of the site, call it whatever the facility is named or something like that. I think it has to be a different name than the N30 b/c it gets stored in the database file. ...
  39. Replies
    4
    Views
    542

    I have found in the past that comparators don't...

    I have found in the past that comparators don't update in the N30s for some reason. I would imagine that you added the points through hyperterminal b/c I dont think that Project Builder will import...
  40. Replies
    5
    Views
    1,450

    If you get the lonhoneywellAXWizards.jar file...

    If you get the lonhoneywellAXWizards.jar file from your local Honeywell verdor you will be able to add any point from the controller into the FX40. Since the XL15C is programmable through Tridium it...
  41. I use Tridium Workbench AX to program the FX40....

    I use Tridium Workbench AX to program the FX40. All I do is use the Software Manager on the Platform and copy the JCI modules to my computer. Then I delete the JCI appliance from the FX40 and install...
  42. Replies
    10
    Views
    2,410

    I agree w/ "pjk" I have set this up on a couple...

    I agree w/ "pjk" I have set this up on a couple of jobs where they don't have a web supervisor.

    It really shouldn't matter what kind of router your using, b/c I think just about every router...
  43. Replies
    6
    Views
    1,102

    If you guys don't know the FX40 is JCIs version...

    If you guys don't know the FX40 is JCIs version of the Tridium AX Jace, really the only difference is JCI (most likely Tridium) developed a N2 driver for it.
  44. Replies
    3
    Views
    1,314

    I have used the CS driver in R2 to interface with...

    I have used the CS driver in R2 to interface with some proprietary RS485 controls, and it worked great after figuring it out. Never really heard of Teletrol but the CS driver is not going away...
  45. Replies
    6
    Views
    1,102

    There appliance is really a joke anyway, There...

    There appliance is really a joke anyway, There are already 2 revs behind the Tridium niagara software. I already upgraded all of the FX40 we installed with .106 back in January.

    I agree with you...
  46. Replies
    10
    Views
    2,688

    I use Macromedia Fireworks for all of my...

    I use Macromedia Fireworks for all of my graphic/image editing. The best way I found to make CAD floor plans into image files is to....

    1. Open up AutoCAD and size the floor plan to the scale that...
  47. Replies
    88
    Views
    12,361

    The only problem with the NAE and NIE is that...

    The only problem with the NAE and NIE is that they are a JCI branch controller and are really not availible to ACBS contractors. JCI corp. are the only people that can install them.

    Off hand I...
  48. Thread: N30 and DST

    by jczekai
    Replies
    6
    Views
    722

    There shouldn't be any update b/c the programmer...

    There shouldn't be any update b/c the programmer specifies the UTC Offset, DST Latest Begin and DST Latest End.

    All I've done on the jobs we have N30s on, was adjust the Begin and End Dates to the...
  49. Thread: FX40 and M3

    by jczekai
    Replies
    8
    Views
    1,715

    It not even close to working with M-Graphics....

    It not even close to working with M-Graphics. When I first started in the automation field five years M3/M5 was the first SCADA system that was using. Then four years ago we adopted the Tridium line...
  50. Thread: FX40 and M3

    by jczekai
    Replies
    8
    Views
    1,715

    Why would you want to do that, the FX40 can be...

    Why would you want to do that, the FX40 can be access through any standard web browser from anywhere?
Results 1 to 50 of 55