    Sorry for the delayed response. The security...

    Sorry for the delayed response.

    The security page is only for PCM Edit software. All 0's means you don't need to log into PCMEdit. The Display password is in the Display setup screen. It's the...
  2. Replies
    6
    Views
    285

    That password screen will show a "broken" key...

    That password screen will show a "broken" key when the keypad is locked. You enter in whatever sequence of + and - had been programmed as the the display password. Then analog and binary parameters...
  3. Replies
    6
    Views
    408

    The FLN driver works well for TEC controllers but...

    The FLN driver works well for TEC controllers but does not work at all for older 535-600 TCU controllers (these were on heat pumps at one job). It sort of works on UC controllers but you must...
  4. Replies
    7
    Views
    392

    I've never made a custom module before, I'll give...

    I've never made a custom module before, I'll give it a try. What could possibly go wrong :grin2:
  5. Replies
    7
    Views
    392

    They do have a cool one that makes it rotate...

    They do have a cool one that makes it rotate around but I'm just looking to make labels that have vertical text, it would seem like a basic thing to do but heck if I can figure it out. Yes you can...
  6. Replies
    7
    Views
    392

    Rotating Bound Labels

    Is there any way to rotate either a Label (text or image) or a bound label? Sometimes it would be nice to have vertical text.
  7. We use the Setra M230 series with the valve...

    We use the Setra M230 series with the valve manifold. High proof pressures (ratings they will withstand before the zero is affected) and pressure ratings of 350#. Available from kele.
  8. Replies
    8
    Views
    450

    If the variables you seek are in the UC600 but...

    If the variables you seek are in the UC600 but cannot see them from the SC, then the equipment template for the UC600 needs to be updated and edited.
  9. I used WACNet for the 1st time today (the latest...

    I used WACNet for the 1st time today (the latest 1.1.9), I was able to immediately find a MSTP device conflicting through a router with a BACNet/IP device. It solved my issue.

    Nice compact...
  10. For the AI's, go with 2 sensors, the efforts it...

    For the AI's, go with 2 sensors, the efforts it would take to split the signal would cost far more. For the AOPs, you could have a signal or rectifier diode (any type would work, the current is very...
  11. Replies
    9
    Views
    3,889

    A great old thread that took care of what I...

    A great old thread that took care of what I needed to do. Still works the same today with 3.8.41.

    Thanks
  12. Great, thanks!

    Great, thanks!
  13. Jace with ASD Bus driver MNET and MNFLO controllers

    I've used the ASD drivers successfully for integrations with MZIIs, MFLOs and PEMs. The driver lists MicroNet controllers but does anybody have experience with integrating these? I'm using the...
  14. Replies
    3
    Views
    359

    There are DIP switches to make the inputs either...

    There are DIP switches to make the inputs either voltage or Current input (located under the Display) make sure the one for input 53 is set to current.
  15. Read the programming guides that are included in...

    Read the programming guides that are included in Tracer Summit. Use the points for the other chillers as models. Do not delete any points. It's not a bad thing but the Bacnet point reference...
  16. Replies
    18
    Views
    855

    If you are sticking with the Trane SENSOR that is...

    If you are sticking with the Trane SENSOR that is connected 1 2 3 to 1 2 3, then you should be able to keep the comm board connected. Only if you want to use the T-Stat connections (ie R G Y1 Y2 W1...
  17. Replies
    18
    Views
    855

    Yes, take the internal comm off the Comm board. ...

    Yes, take the internal comm off the Comm board. If the comm board has 2 comm cables connected to it, then there is another board(s) downstream, such as the economizer. Trace the comm harnesses...
  18. Replies
    2
    Views
    355

    The 510 will not work with any other t-stat. It...

    The 510 will not work with any other t-stat. It will run fine stand-alone. I believe one of the inputs can be programmed as an occupancy input so you can have setbacks but the Rover programming...
  19. Replies
    9
    Views
    1,204

    The alarm classes need a recipient. Usually the...

    The alarm classes need a recipient. Usually the Console Recipient.

    In Config > Service > Alarm Services the alarm classes will be in there. Connect them to the ConsoleRecipient, that becomes...
  20. Replies
    8
    Views
    1,104

    Many cell phone companies have quietly stopped...

    Many cell phone companies have quietly stopped supporting text messaging via TAP protocol. Could it be the BCU is trying but the carrier just doesn't respond any longer?

    The pager has to be setup...
  21. Replies
    8
    Views
    1,104

    The workstations have to be defined in the Site...

    The workstations have to be defined in the Site Configuration. The device ID set in the Options Menu has to match the defined Workstation.

    Then the Workstations have to be setup as event...
  22. Replies
    8
    Views
    2,612

    That took care of it. Thanks!

    That took care of it. Thanks!
  23. Replies
    8
    Views
    2,612

    Bringing up an old discussion: Can the flow...

    Bringing up an old discussion:

    Can the flow reading be "zeroed" out. Most of the boxes still report flow when the AHU is off. I see settings for calibrating the K factor but nothing to offset...
  24. Replies
    2
    Views
    625

    For the anamometer, look for the ultrasonic type....

    For the anamometer, look for the ultrasonic type. No moving parts.
  25. Replies
    7
    Views
    932

    Hyperterminal 38400 Baud. If the BCU is...

    Hyperterminal 38400 Baud. If the BCU is configured as IP then you can use telnet to the IP address.
  26. Replies
    7
    Views
    932

    If there was a remote workstation programmed as...

    If there was a remote workstation programmed as an event receiver and then removed, it may still be flagged as not receiving the message. Also, there may be a current alarm that you are not aware of...
  27. Replies
    8
    Views
    2,375

    This an old thread, but No, the power exhaust...

    This an old thread, but No, the power exhaust control is on that module, you'll need another solution for the exhaust.
  28. Replies
    11
    Views
    1,941

    Sorry, I was looking at the photo from August...

    Sorry, I was looking at the photo from August post.
  29. Replies
    11
    Views
    1,941

    That looks like a VAV UCM-1. If it is, that is...

    That looks like a VAV UCM-1. If it is, that is not a true Com-4 device. It is a Non-isolated com-3 device. On VAV systems they could coexist with new com-4 vavs but that is when used with a...
  30. Replies
    1
    Views
    493

    I've had that issue as well. I believe ver 17...

    I've had that issue as well. I believe ver 17 has issues with uploading from BMTSs with ethernet. What I had to finally do was install an arcnet card in the BCU, connect with that from my laptop...
  31. Thread: Vfd contactor

    by t-reck
    Replies
    21
    Views
    3,115

    Should not be a problem with any newer drive. ...

    Should not be a problem with any newer drive. This is no different then having a local disconnect at the unit (which you should have by code).

    Some older drives could be damaged if the load side...
  32. Replies
    5
    Views
    978

    If you have something in pdf form, that would be...

    If you have something in pdf form, that would be great but it's not worth the effort to pull out the manuals. These are operated as slave devices anyway, its an integration project as it is so we've...
  33. Replies
    5
    Views
    978

    I use Hyperterminal to talk to the BLN...

    I use Hyperterminal to talk to the BLN controller. I use a Siemens modem cable connected to my laptop via a null cable. This connects at the MMI port.

    When I try the same type of connection to...
  34. Replies
    5
    Views
    978

    Configuring Siemens UC 544-449

    I have a handful of these controllers on an integration job. I would like to check the configuration of the points since I'm having issues with the AOPs. I have a cable that works on the MMI port...
  35. I use the one made by IBMS. ...

    I use the one made by IBMS.

    http://www.hvacc.net/pdf/EasyIO/ibmsAsd_02Feb2012/docAsd.pdf

    I don't know there are others.
  36. Correction: 3.5 or above

    Correction: 3.5 or above
  37. I did not have a Loop Controller to deal with. ...

    I did not have a Loop Controller to deal with. If the MIG has 2 RS232 ports then you'll need to add another card to your Jace. The OPM driver requires 3.6 or above.

    The polling rate had to be...
  38. IGOTWORMS: It's been a while since I wrestled...

    IGOTWORMS: It's been a while since I wrestled with the MIG I had to deal with. I believe it was also a ver3 unit. I tried to load the VCT using a later version of the utility but it would not...
  39. I was never able to resurrect the MIG I had. The...

    I was never able to resurrect the MIG I had. The battery died so there was no backup stored. The HP database could have been reentered manually but the driver is also lost with the power failure. ...
  40. Some tips: -Units are probably defaulted to SI...

    Some tips:

    -Units are probably defaulted to SI
    -Baud Rate default will be 78K
    -If it is a VAV unit, work with the discharge setpoints, The Occupied space setpoints won't do anything
    -Some...
  41. Replies
    4
    Views
    1,424

    If the discharge low limit is the setpoint you...

    If the discharge low limit is the setpoint you are referring to, that is too high. The is intended to turn off stages of cooling when the discharge temp drops below that. 45-50 deg is a normal...
  42. Replies
    7
    Views
    891

    The comm board will also have to be removed for...

    The comm board will also have to be removed for the t-stat terminals to be functional. If the RTU has the COMM-4 board for a varitrac system then the rest of that Bypass VAV system will not operate...
  43. Replies
    317
    Views
    73,664

    Lots of great stuff in that zip including PSI...

    Lots of great stuff in that zip including PSI installer, thanks for the link.

    Does anyone have a download for utilities to backup a GCM without the use of Signal? NUDL or Python I think were the...
  44. Replies
    7
    Views
    1,132

    I'm trying to do the batch edit of proxy points...

    I'm trying to do the batch edit of proxy points to change all the point IDs for example HP_01_01 to HP_01_02 as I copy folders but The replace function is unavailable in the point manager. Am I...
  45. Replies
    11
    Views
    1,003

    The points should show up in discovery. The...

    The points should show up in discovery.

    The points you need:
    Air Flow Maximum AV-47
    Air Flow Maximum Heat AV-46
    Air Flow Minimum AV-42
    Air Flow Minimum...
  46. Replies
    1
    Views
    415

    Intellipak is a device type 44. It would be a...

    Intellipak is a device type 44. It would be a different link as the TIMs if you still have other units on that link so it would require a different cable.
  47. Replies
    21
    Views
    5,204

    Without being connected to a controller I can't...

    Without being connected to a controller I can't see the screens to direct you exactly where to go but look in the configuration menu. Depending on your screen resolution, the load and save buttons...
  48. Replies
    21
    Views
    5,204

    The cable probably needs the other handshaking...

    The cable probably needs the other handshaking pins connected. A full 9 to 9 pin may be necessary.
  49. Replies
    21
    Views
    5,204

    Read all documentation available. There should...

    Read all documentation available. There should be no licensing required for the software.

    Connect to the original controller first, it should find it and tell you what you are connected to, then...
  50. Replies
    21
    Views
    5,204

    You need Trane Techview software: ...

    You need Trane Techview software:

    http://www.trane.com/commercial/north-america/us/en/controls/HVAC-equipment-controls/trane-lontalk-controllers/TechView.html

    A laptop with a serial port and a...