  1. Replies
    3
    Views
    214

    Use the CAF file. I did the same thing using the...

    Use the CAF file. I did the same thing using the PRN file the first time. I was able to get the import to work with the PRN by editing the controller type in the file, but I learned later the CAF is...
  2. I agree with "throrope". These inlets really are...

    I agree with "throrope". These inlets really are not the same as linear flow through a round duct with 10 diameters up stream and 5 diameters downstream. With the proper values from the fan...
  3. A=pi*r^2 So do not use 24" for r because there...

    A=pi*r^2

    So do not use 24" for r because there are 2 circles. Actually easier if you convert 12" to 1'. Then the area is about 3.14 SqFt. So 2 sides would be 6.28 SqFt. If you used r=2 then the...
  4. BACnet® Controller Integration with NAE/NCE...

    BACnet® Controller Integration with NAE/NCE Technical
    Bulletin on JCI quick lit

    and

    MS/TP Communications Bus Technical Bulletin also on Quicklit

    Google LIP-ME201 for info on the router and...
  5. Replies
    18
    Views
    889

    I know we are talking about simulation in the...

    I know we are talking about simulation in the shop, but in the field it pays to remember you likely have a 1.5 volt and 9 volt very clean power supply handy. I bet you carry backup batteries for you...
  6. Replies
    9
    Views
    548

    We install the battery in the 60 and also install...

    We install the battery in the 60 and also install a small UPS on the 120 volt power line to the unit.
  7. What is the Busy time, Average Poll and the Cycle...

    What is the Busy time, Average Poll and the Cycle Times for each rate? I assume you made a separate tuning policy for the LRS you need fast? If you just kicked the default policy to Fast the bus will...
  8. Replies
    2
    Views
    371

    JCI AS-UNT??? If so just add a numeric...

    JCI AS-UNT???

    If so just add a numeric writable mapped to the Zone Temp Analog Input. Then you can write the value. The default import imports Analog Inputs as Numeric Points (not writable)
  9. Replies
    16
    Views
    2,389

    How about GOOGLE? ...

    How about GOOGLE?

    https://www.google.com/search?q=Niagara+Workbench+Guide&ie=utf-8&oe=utf-8
  10. Replies
    11
    Views
    428

    Just make a folder and put control elements in...

    Just make a folder and put control elements in the folder. Then drop a trigger from kitControl/ControlPalette/Trigger to control when the routine runs. Also checkout the kitControl-LeadLagRuntime....
  11. Replies
    9
    Views
    343

    The serial number will be useful. The sealed...

    The serial number will be useful. The sealed factory package really does not mean much with the tridium software license. The software can be installed with any copy of the software. The license is...
  12. Heater may have overheated due (in part) to a NC...

    Heater may have overheated due (in part) to a NC PE and bad main air. Check heater high limit. And Heat coil itself.

    If it were my job I would switch the PE to NO if possible and move the tube to...
  13. Replies
    11
    Views
    428

    OK. In the AX make the lead pump selection a...

    OK. In the AX make the lead pump selection a separate sheet from the OA and alarm control of the pumps. Make the Lead selection only trigger and change the Lead Pump Enum point on, say, tuesday...
  14. Replies
    11
    Views
    428

    Hardware? Software? Answer depends on the tools...

    Hardware?
    Software?
    Answer depends on the tools you are using! Maybe the runtime based selection routine should only run every 604800 sec? Or use a schedule trigger?
  15. Replies
    9
    Views
    343

    I think JCI keeps records of who bought what in...

    I think JCI keeps records of who bought what in terms of the FX licenses.

    Best route whold be to look for the order info for the Server disk in the records of the purchaser. Also get JACE Ids...
  16. Google jci quicklit. Jci posts it all there. ...

    Google jci quicklit. Jci posts it all there.

    Sent from my SM-G900V using Tapatalk
  17. It looks to me like the parts are all original....

    It looks to me like the parts are all original. The hand drawn piping looks goofy. Yes the Volume controller and Reversing relay outputs look to be connected. I do not remember what effect that will...
  18. Is the bus a separate loop for these 3 devices?...

    Is the bus a separate loop for these 3 devices? Or is it the same wire with some apogee devices? Can you tell anything from where this bus connects to the siemens controller.

    Are you removing a...
  19. Replies
    8
    Views
    679

    N2 is pretty forgiving. You have not included...

    N2 is pretty forgiving. You have not included much info about your site. Wire, topology, controller model.

    Try Google " jci quicklit" then search "N2 guide".

    Sent from my SM-G900V using...
  20. Replies
    16
    Views
    2,389

    I have seen my kids doing block programming at...

    I have seen my kids doing block programming at school, building Lego Mindstorm Robots. Also when they created levels on the PS3 little big planet. Then they were pulling apart and rewriting XML on...
  21. Replies
    12
    Views
    1,036

    Part of what my customers expect is an ability...

    Part of what my customers expect is an ability for my company to be able to reach in and command elements of their system. Most of them do not have the HVAC or IT skills to do what we do. That is why...
  22. Replies
    5
    Views
    884

    "I can also connect to the Jene JACE in workbench...

    "I can also connect to the Jene JACE in workbench and surf through the factory programming.. But I was just wondering if the I can do this through the main JACE for the building.. The Jene Jace is...
  23. Replies
    12
    Views
    1,036

    Just found my answer at :...

    Just found my answer at :
    http://www.ccontrols.com/pdf/ds/DS-BASCLD00B.pdf
    This is exactly what I was thinking when I asked the question.
  24. Replies
    7
    Views
    505

    I am glad I am not the only one. I can't tell...

    I am glad I am not the only one.
    I can't tell you the number of times I have struggled with something like this. Then leave it... when you come back it is just a few clicks, easy.
  25. Replies
    12
    Views
    1,036

    I guess that is my real question. Does someone...

    I guess that is my real question. Does someone offer this solution? A box, kind of like a typical home router, that would reach out to a server on the internet. A user on the internet would then...
  26. Replies
    6
    Views
    594

    My first check would be to make sure the current...

    My first check would be to make sure the current loop is a series loop. If it somehow changed from series to parallel when you rewired you would have problems. (Maybe each gets half the current but...
  27. Replies
    12
    Views
    1,036

    firewall pass through for Jace

    I sometimes use Logmein to access a computer inside a firewall. I also know there are hosts that reach out to specific places on the internet in a similar way for other equipment (usually requires a...
  28. Replies
    7
    Views
    2,285

    I use it when troubleshooting a N2 comm problem....

    I use it when troubleshooting a N2 comm problem. Much more portable than the laptop. It tells me which controllers are on each trunk when dividing the network into segments. Yes the laptop can do the...
  29. Replies
    10
    Views
    726

    Re-reading your original post it sounds like you...

    Re-reading your original post it sounds like you got the PMI to work. "PMI works fine". This should get you some time as Cagey57 said. If you could share your location someone in your region might...
  30. Replies
    10
    Views
    726

    JCI may sell the NIE at an affordable price, but...

    JCI may sell the NIE at an affordable price, but as you get more committed the NAE/ADS prices to really upgrade the system will rise. I like the Tridium from a good contractor. I am sure the S4...
  31. Replies
    40
    Views
    4,217

    Most of the Modbus on supplied equipment has a...

    Most of the Modbus on supplied equipment has a Protonode optional gateway to BACnet from the Equipment supplier. If the control contractor can get that piece of hardware supplied by the equipment...
  32. Replies
    10
    Views
    726

    If you really want to keep the M5 I suggest you...

    If you really want to keep the M5 I suggest you contact Iconics. They made the M workstation and still support it. Their first solution will be upgrade to a newer version that supports the new OS....
  33. Replies
    2
    Views
    312

    Siemens TEC on an AX

    I use a lot of JCI controllers. I have a project where I will be using the Maxline driver to connect a bunch of Siemens TEC to the Jace with a FLN bus. In the future what tools do I need to service...
  34. Replies
    66
    Views
    3,157

    Well I like to use a selector relay from the...

    Well I like to use a selector relay from the TP970 thermostat branch air line. Use that to reset your RP908 submaster controller.

    Point is there are a lot of methods to accomplish the strategy....
  35. Replies
    3
    Views
    658

    Calibrate a valve? One needs to be careful...

    Calibrate a valve?

    One needs to be careful when calibrating an output to a pneumatic valve. Yes, the valve operates over a given spring range, but full closeoff pressure is obtained at a pressure...
  36. Replies
    71
    Views
    8,603

    I thought the trend is heading toward "Plugin...

    I thought the trend is heading toward "Plugin Free" browsing. Part of the reason for the HTML5 and Niagara 4.

    One big feature of a router only solution is security. Not building security but data...
  37. Replies
    71
    Views
    8,603

    I still don't understand how this "pure" Bacnet...

    I still don't understand how this "pure" Bacnet Ip system works.

    Hypothetical...
    5 MSTP controllers in a small building. Connect a BACnet router. Provide pathway to the router. With a computer...
  38. Replies
    71
    Views
    8,603

    I am curious, In a theoretical building with say...

    I am curious, In a theoretical building with say 5 "Bacnet" controllers all set up with schedule, trend and alarm extensions. Bacnet network accessible on the LAN in the building. What does a user...
  39. This might work, cheap and easy enough to try.

    This might work, cheap and easy enough to try.
  40. Replies
    11
    Views
    1,445

    Try unplugging the N2 cable from the local...

    Try unplugging the N2 cable from the local controller. Cycle power and see if the unit starts. Most older N2 controllers will run a unit in stand alone if the network is not present. You are taking a...
  41. Replies
    6
    Views
    516

    What is the definition of System Performance? ...

    What is the definition of System Performance?

    My $30 radiant electric heater from the drugstore is always 100% efficient (all the energy input becomes heat). I suppose I can use my Fluke to log...
  42. Replies
    1
    Views
    479

    Well go down to Home Depot and get a WiFi...

    Well go down to Home Depot and get a WiFi thermostat. Put it in the space the chiller serves. And there you go...

    Honestly, you have to provide some details yourself if you want a real suggestion!
  43. Replies
    9
    Views
    942

    I can just imagine the linkage required to pull...

    I can just imagine the linkage required to pull plates in and out as the wheel flips like a coin along its horizontal axis across the diameter. Reminds me of some inlet vane designs!
  44. Replies
    9
    Views
    942

    "I'm curious as to whether it matters which way...

    "I'm curious as to whether it matters which way an energy recovery wheel spins, and why."

    Well if spun at a 90° axis to how they typically are installed, they would likely need much more room in...
  45. Replies
    49
    Views
    4,471

    That is normally all you need to do.

    That is normally all you need to do.
  46. Replies
    12
    Views
    2,589

    The ADX itself can not talk bacnet to the jace. ...

    The ADX itself can not talk bacnet to the jace.

    The Nae can talk bacnet to the jace. Typical Jace proxy points are not bacnet points. You can create bacnet points in the jace. The Nae could then...
  47. Replies
    49
    Views
    4,471

    Yes sometimes the DMO import I mentioned will not...

    Yes sometimes the DMO import I mentioned will not get the points you are after. Then the table will allow you to manually add the point.

    Since the DX is programmable there is no shortcut to learn...
  48. Replies
    49
    Views
    4,471

    Since you have the DXS file, you can make the DMO...

    Since you have the DXS file, you can make the DMO file the FX60 will use to import the points. There are some options for making the dmo file in the file tab of GX9100. It is done the same way as the...
  49. Replies
    49
    Views
    4,471

    yes the reset could be in the DX or the NCM....

    yes the reset could be in the DX or the NCM. Decoding the names in a dx is a PIA if you don't have the config files on the ows. look for *.dxs or *.tag files.

    If no luck finding the files start...
  50. Replies
    49
    Views
    4,471

    The model.und will have the translation from the...

    The model.und will have the translation from the cs object AI_n, BI_n, AD_n, SP_n, AO_n, BO_n used in metasys to the N2 addressing. AIn, BIn, BDn, ADFn, AOn, BOn.

    As far as which points are...