Search:

Type: Posts; User: Jogalloway

Search: Search took 0.00 seconds.

  1. Replies
    17
    Views
    1,435

    Where is the inside unit located? Can you get to...

    Where is the inside unit located? Can you get to and see if evaporator is freezing?
  2. Thread: Stumped!

    by Jogalloway
    Replies
    34
    Views
    2,216

    Evacuated system, checked orifice and it was full...

    Evacuated system, checked orifice and it was full of dirt, cleaned orifice, installed new filter dryers and system works like a charm now! thanks to everybody's opinion i have learned a couple of...
  3. Thread: Stumped!

    by Jogalloway
    Replies
    34
    Views
    2,216

    It has an orifice, yes evap coil has been cleaned...

    It has an orifice, yes evap coil has been cleaned and fins on fan do not have any dust or buildup of any kind on them.
  4. Thread: Stumped!

    by Jogalloway
    Replies
    34
    Views
    2,216

    From everything i have gathered, I do not think...

    From everything i have gathered, I do not think it is a airflow problem. I am going to recover, open and check orifice, install a new filter drier and sight glass which it does not have now, weigh in...
  5. Thread: Stumped!

    by Jogalloway
    Replies
    34
    Views
    2,216

    Ive got a couple of classes coming up this fall,...

    Ive got a couple of classes coming up this fall, intro to ref. and comfort cooling at local tech school. We have most tools vacuum pump, gauges, micron gauges, recovery machine, recovery cylinders,...
  6. Thread: Stumped!

    by Jogalloway
    Replies
    34
    Views
    2,216

    Appreciate it skw, will get my post count up and...

    Appreciate it skw, will get my post count up and apply for pro cause i have alot of questions ha ha, my supervisor is just a manager so he really only cares about how much it will cost to repair, and...
  7. Thread: Stumped!

    by Jogalloway
    Replies
    34
    Views
    2,216

    Thanks guys, compressor was changed in april 08,...

    Thanks guys, compressor was changed in april 08, no problems until last week, lady called office and said she had ice all over filter, another tech checked the first time and said filter was dirty...
  8. Thread: Stumped!

    by Jogalloway
    Replies
    34
    Views
    2,216

    O.K. thanks for the heads up. I am not a pro....

    O.K. thanks for the heads up. I am not a pro. just a maintenance tech at a n apartment complex, only been in the hvac/maintenace field about a year so this is really the first unit i have had that...
  9. Thread: Stumped!

    by Jogalloway
    Replies
    34
    Views
    2,216

    How do you test staic pressure?

    How do you test staic pressure?
  10. Thread: Stumped!

    by Jogalloway
    Replies
    34
    Views
    2,216

    Yeah, indoor fan comes on every time.

    Yeah, indoor fan comes on every time.
  11. Thread: Stumped!

    by Jogalloway
    Replies
    34
    Views
    2,216

    Stumped!

    Help!! 2.5 Ton Goodman Heat Pump, when unit first turns on in cool, the suction psi is between 35-45psi, head pressure is between 125-150psi. These pressures hold steady at those psi's for 15-25 mins...
Results 1 to 11 of 11
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine
Comfortech365 Virtual Event