Search:

Type: Posts; User: myssjeep

Search: Search took 0.01 seconds.

  1. Replies
    0
    Views
    317

    Shortridge water meter HDM150

    I'm selling a used short ridge HDM 150. It is in perfect working order comes with the case, panel, hoses, and manual. Pics on request.

    Asking $1800 OBO
  2. Light commercial units don't generally bother me...

    Light commercial units don't generally bother me to much, its when I have a 1200 cfm exhaust fan with 24 outlets all calling for 50 cfm each when I brake out the tums.

    As far as number of...
  3. I don't think there are that many of us T&B guys...

    I don't think there are that many of us T&B guys out here.
  4. Replies
    4
    Views
    638

    Forgot to mention most work with just white out,...

    Forgot to mention most work with just white out, I'm always out of reflective tape.
  5. Replies
    4
    Views
    638

    I don;t have any experience with the fieldpiece...

    I don;t have any experience with the fieldpiece tach but I use a extech non-contact and I like it. I'm sure you'd be happy with it I've been happy with all my fieldpiece insturments.
  6. Replies
    7
    Views
    2,172

    This was not an air curtain but someone installed...

    This was not an air curtain but someone installed it didn't know how to read prints. The air distribution was to be installed in the drop ceiling not above. There is no defending hat was done here.
  7. Replies
    7
    Views
    2,172

    Kitchen is to hot

    We all know a kitchen is always hot but my friend went to check it out anyway, this is what he found.
  8. Thread: goodman...?

    by myssjeep
    Replies
    115
    Views
    8,197

    I have no problem working on them its just...

    I have no problem working on them its just explaining to a homeowner why you have hundreds of dollars in repairs on a unit that is only 18months old. The evap coils seem to get leaks all the time. ...
  9. Replies
    7
    Views
    1,030

    Welcome, I have a friend from way up there.

    Welcome, I have a friend from way up there.
  10. Replies
    6
    Views
    1,707

    I have never seen a return air installed in a...

    I have never seen a return air installed in a bathroom for that very reason. I have seen systems that smell pickup has become an issue(outside air intake to close to exhaust outlet).

    In my...
  11. Replies
    9
    Views
    1,154

    I'd check your building pressurization, I had a...

    I'd check your building pressurization, I had a customer with he same problem here in FL, someone figured they'ed save some money by closing the O/A didn't think about all the unconditioned air that...
  12. Replies
    8
    Views
    1,023

    Thanks Just ordered.

    Thanks Just ordered.
  13. Replies
    8
    Views
    1,023

    I'd like to pick up one of your micron gauges, do...

    I'd like to pick up one of your micron gauges, do you sell them direct? or where can I get one locally I'm in the Tampa area.
  14. Replies
    8
    Views
    2,462

    The filters used are the only ones that wouldn't...

    The filters used are the only ones that wouldn't restrict the fan to below design, well when they were clean anyway. When no filter was installed(the way it was engineered) the fans used actually...
  15. Replies
    8
    Views
    2,462

    That was another problem originally these fans...

    That was another problem originally these fans had been designed with no filteration and when it rained the fans would pull the water off the roof and put it into the units (not to mention how dirty...
  16. Replies
    8
    Views
    2,462

    Nope, construction was completed 10 months prior....

    Nope, construction was completed 10 months prior. Can we say VE, we noted that the filters loaded quickly during turnover, the EOR made the comment they just need to change the filters everyday.
  17. Replies
    8
    Views
    2,462

    Not enough Outside Air

    I got a call after I balanced this pressure critical building saying it was extremely negative and we didn't setup the fans correctly.
  18. Replies
    18
    Views
    3,717

    Sounds like Trane was the best choice to start...

    Sounds like Trane was the best choice to start with. Your installer knows how their relationship with their supplier. Relationships are everything.
  19. Replies
    6
    Views
    2,838

    I prefer Greenheck but I'm not the one paying for...

    I prefer Greenheck but I'm not the one paying for it. Most ME's I work with use Greenheck for basis of design, but the mechanicals try to use similar cook to save a few bucks.
  20. Replies
    49
    Views
    7,428

    I've been looking for one more for my own...

    I've been looking for one more for my own enjoyment, just can't justify it yet. The wow focator from homeowners is a plus, not many people have them in these parts, I guess for good reason though.
  21. Agreed a rotating blade is a last resort. These...

    Agreed a rotating blade is a last resort. These devices are very subject to user error and without performing a traverse and creating a factor, it only provides a guestimate.
  22. Replies
    0
    Views
    505

    NCI Certification

    I have been looking into taking the NCI air balancing course, just wanted some feed back on how many other people have done this and if its worth it.

    I'm looking at leaving my current balancing...
  23. Thread: Tools/Parts

    by myssjeep
    Replies
    13
    Views
    1,178

    I try, but its a lot of work to buy American, I...

    I try, but its a lot of work to buy American, I still try though.

    I did get my wife to start checking her pureses now she won't buy Coach anymore, Thank God.
  24. I worked for a beer can cold company and thought...

    I worked for a beer can cold company and thought they were a doing everything right. That was until I wanted to go out on my own and started studying for my license. Its amazing the more you learn...
  25. Replies
    9
    Views
    1,053

    Hood is a good place to start. I'd also check...

    Hood is a good place to start.

    I'd also check the Outside Air, people close it off all the time to save a dime and then pay someone to find out why they have problems. O/A not being adjusted...
  26. Replies
    20
    Views
    7,229

    You can make a career out of it no problem. ...

    You can make a career out of it no problem. Nobody likes the balancer, last ones in and as mentioned they always need it done yesterday. The fact the mechanical contractor forgot to add dampers to...
  27. Replies
    23
    Views
    8,651

    Thanks for the warning I was looking a picking up...

    Thanks for the warning I was looking a picking up a used one. Not now.

    I agree with the post about replacing flex duct, but I won't tell my customers no when they want it cleaned. I try to...
  28. Replies
    6
    Views
    3,686

    0.05"wg would be difficult to maintain. I would...

    0.05"wg would be difficult to maintain. I would almost definetly leave the room slighlty over pressureized to allow for filter loading, belt wear or any other building change.

    Calculations are...
  29. Thread: Need Help

    by myssjeep
    Replies
    6
    Views
    431

    Cheaper doesn't = right

    Cheaper doesn't = right
Results 1 to 29 of 48