Search:

Type: Posts; User: dlhvac

Search: Search took 0.00 seconds.

  1. did you set the bacnet instance id to a different...

    did you set the bacnet instance id to a different one before you put them on the network all spyders come with the same instance id got me the first time
    this is different than the mstp address
  2. Replies
    5
    Views
    873

    infocon makes a cbus driver that works very well...

    infocon makes a cbus driver that works very well you flash the easyio 30p and it sends the data to a jace
  3. Replies
    29
    Views
    5,884

    It is digital tone modified frequency or modem...

    It is digital tone modified frequency or modem audio
  4. Replies
    29
    Views
    5,884

    Yes it could be a big deal as long as it is comm3...

    Yes it could be a big deal as long as it is comm3 isolate ie not polarity sensitive already have driver for the comm3 non isolated ie polArity sensitive
  5. Replies
    29
    Views
    5,884

    The interface is a torroid transformer the...

    The interface is a torroid transformer the protocol is audio just as modem audio that is the data highway
  6. Replies
    28
    Views
    3,628

    i tried to email you the answer but your email...

    i tried to email you the answer but your email bounced email me at dlhvac@ptd.net
  7. Replies
    28
    Views
    3,628

    i use an infocon easyio 30p or a spyder micro

    i use an infocon easyio 30p or a spyder micro
  8. Replies
    28
    Views
    3,628

    the sensor has the output rating right on it i...

    the sensor has the output rating right on it i cannot recall offhand but the bypass damper cannot be controlled by the jace you must replace this controller with another the ccp panel previously...
  9. Replies
    28
    Views
    3,628

    yes but usually the supply house you purchase the...

    yes but usually the supply house you purchase the driver from is the first contact i use broudy supply in philadelphia, also cochrane supply in mich has the driver
  10. Replies
    28
    Views
    3,628

    worked well have done a bunch since then 12 or 13

    worked well have done a bunch since then 12 or 13
  11. Replies
    28
    Views
    3,628

    9600 8 none 1

    9600 8 none 1
  12. Replies
    3
    Views
    1,400

    broudy supply in phila has the drivers

    broudy supply in phila has the drivers
  13. Replies
    3
    Views
    1,400

    yes it is available thru maxline drivers with...

    yes it is available thru maxline drivers with infocon support for 10 years
  14. Replies
    28
    Views
    3,628

    Does the install have trane purple wire if not...

    Does the install have trane purple wire if not your on your own
  15. Replies
    28
    Views
    3,628

    Approx 80 or more points per rtu all the...

    Approx 80 or more points per rtu all the diagnostic alarms and you can also reset diagnostic faults
  16. Replies
    28
    Views
    3,628

    You can see more of the voyager and reliatel...

    You can see more of the voyager and reliatel points than with tranes software
  17. Replies
    28
    Views
    3,628

    The zoning and rtu overides are done in the jace

    The zoning and rtu overides are done in the jace
  18. Replies
    28
    Views
    3,628

    I would use a six if you are putting graphics on...

    I would use a six if you are putting graphics on it if noy jace 2 should work watch your java heap and busy time on the jace comm four is a reource hog
  19. Replies
    28
    Views
    3,628

    Sorry but i dont give away stations that ive done...

    Sorry but i dont give away stations that ive done but it is doable to integrate all that you stated
  20. Replies
    28
    Views
    3,628

    Maxline drivers owms the comm4 driver infocon...

    Maxline drivers owms the comm4 driver infocon sold the driver division go them but has a contract for 10 years to provide support
  21. Replies
    28
    Views
    3,628

    worked very well have done 12 to date

    worked very well have done 12 to date
  22. Replies
    29
    Views
    5,884

    you have to put the unit in tracer control and...

    you have to put the unit in tracer control and command the input mode
  23. Replies
    119
    Views
    17,480

    the ashrae show sent you an email

    the ashrae show sent you an email
  24. Replies
    119
    Views
    17,480

    the ashrae show

    the ashrae show
  25. Replies
    119
    Views
    17,480

    THE CONTROLLERS WILL BE OUT AT THE SHOW IN DALLAS...

    THE CONTROLLERS WILL BE OUT AT THE SHOW IN DALLAS IM BETA TESTING A PROTOTYPE
  26. Replies
    119
    Views
    17,480

    Have over 50 installed at different sites all...

    Have over 50 installed at different sites all work flawlessly and yes they talk sedona modbus and bacnet all at the same time the new ones due out will have its own html5 graphics engine and it own...
  27. Replies
    29
    Views
    5,884

    Forgot using lon requires the firmware in chiller...

    Forgot using lon requires the firmware in chiller to be the latest Trane will have to upgrade recommend using comm4
  28. Replies
    29
    Views
    5,884

    There are some issues with the commissioning of...

    There are some issues with the commissioning of the lci-c chiller lon cards you have to set the response to the jace at no response to commission because some of the cards do not send this response
  29. Replies
    29
    Views
    5,884

    looked this up you should be able to get lon...

    looked this up you should be able to get lon cards for these lci-c
  30. Replies
    29
    Views
    5,884

    sorry should wear glasses when reading messages...

    sorry should wear glasses when reading messages you wrote chillers what comm card is in the chillers now i believe a comm 4 card is available
    for these chillers
  31. Replies
    29
    Views
    5,884

    The rooftops have a trane tci board if you rotate...

    The rooftops have a trane tci board if you rotate the daughter board 90 degrees it becomes comm4 instead of comm3 isolated this is integratable to a jace with an infocon comm4 driver
  32. Replies
    28
    Views
    3,628

    This is what the 20 ms intermessage delay...

    This is what the 20 ms intermessage delay fixes:cheers::cheers:
  33. Replies
    28
    Views
    3,628

    ps on the serial port setup in the intermessage...

    ps on the serial port setup in the intermessage delay set it to 20 milliseconds on all infocon drivers ( did the beta testing on the comm3 driver works great)
  34. Replies
    28
    Views
    3,628

    also if you cant read the temp sensors try ...

    also if you cant read the temp sensors try bringing the voyager in as a different voyager either 1, 2 or3 1 is for old style single board 2, and 3 are reliatel boards
  35. Replies
    28
    Views
    3,628

    when you bring the points into niagara before you...

    when you bring the points into niagara before you name it look at the facets it says which enum you must write for each voyager function use the ax communtiy jar found online
    because you need to...
  36. Replies
    7
    Views
    1,191

    Go to the spyder school but get tridium certified...

    Go to the spyder school but get tridium certified first its required
  37. Replies
    29
    Views
    5,884

    1 JACE 600 YOU DID NOT MENTION IF THE COMM3 IS...

    1 JACE 600 YOU DID NOT MENTION IF THE COMM3 IS ISOLATED OR NON ISOLATED THEIR IS AS OF YET NO ISOLATED COMM3 DRIVER I HAVE MY DEMO JACE SETUP AT A SITE WITH INFOCON DOING THE TESTING BUT COMM3 NON...
  38. Replies
    20
    Views
    4,788

    proprietary trane snvt sent you guys an email...

    proprietary trane snvt sent you guys an email with a couple of good items for trane eyes only (its easy to stop a trane h:angel::angel:ahaha)
  39. Replies
    20
    Views
    4,788

    Yes im aware of what the boards are for but i...

    Yes im aware of what the boards are for but i have 3 voyagers, 2 with the newer tci trangle boards and 1 with the older square all are in non isolated com3/4 but i can only see the older one the...
  40. Replies
    29
    Views
    5,884

    bcu with com three just remove bco go to rooftop...

    bcu with com three just remove bco go to rooftop tci boards change board from isolated com3 to non isolated com3/ com4 do it just like the other one
  41. Replies
    20
    Views
    4,788

    i have those proprietary points if you want them...

    i have those proprietary points if you want them email me but you did not hetem from me
    i have another problem so in hijacking the thread doing com4 driver in tridium
    cannot read 2 voyager with the...
  42. Replies
    9
    Views
    1,529

    just remove the ccp or tracker and do the vav...

    just remove the ccp or tracker and do the vav settings in the jace
  43. Thread: FX10

    by dlhvac
    Replies
    28
    Views
    2,087

    by the way it works well

    by the way it works well
  44. Thread: FX10

    by dlhvac
    Replies
    28
    Views
    2,087

    the fx stuff is now made by distech controls the...

    the fx stuff is now made by distech controls the older line was made by carel
  45. Replies
    28
    Views
    3,398

    bacnets idea w:gah:ill not work

    bacnets idea w:gah:ill not work
  46. Replies
    28
    Views
    3,398

    use a usb to serial adaptor with a null modem...

    use a usb to serial adaptor with a null modem serial cable to the webstat
    or you can use a program called filezilla ant ftp into the webstat and restart it
    :.02:
  47. Replies
    48
    Views
    2,858

    worked both union and non union union on average...

    worked both union and non union union on average has better skills than non due to pay
    but not a lot of controls jobs are union so opened my own company
  48. Replies
    3
    Views
    547

    you need to drive the alarm to a boolean and link...

    you need to drive the alarm to a boolean and link to a bo to do this
  49. Replies
    3
    Views
    1,200

    put in york in numbers like on you phone

    put in york in numbers like on you phone
Results 1 to 49 of 49