05-23-2012, 10:47 PM
Thread: Network 8000 software
by Cal1- Replies
- 227
- Views
- 27,365
Hi ControlTec, Thank you for the reply I am...
Hi ControlTec,
Thank you for the reply I am really looking for a PEM1 programers manual and a GCM programers manual.I appreciate the feedback and yes I am using the infocon driver.I can see all the... -
05-23-2012, 05:30 PM
Thread: Network 8000 software
by Cal1- Replies
- 227
- Views
- 27,365
System 8000
Can anyone help me out here?
-
05-22-2012, 08:38 PM
Thread: Network 8000 software
by Cal1- Replies
- 227
- Views
- 27,365
Hi everyone, I too have a Network 8000 system...
Hi everyone,
I too have a Network 8000 system and need to make changes as the GCM is being replaced with a Jace.I have discovered the PEM's and the MZ11 checked the logic blocks in the GCM with... -
12-14-2011, 07:14 PM
Thread: Roof Top Unit/VMA control nightmare
by Cal1- Replies
- 15
- Views
- 2,794
RE:VMA
Sit down with a cup of joe and read up on your states and other things like saturation timers etc and then do as proxyking says disable prac and check your propbands.
GB -
09-21-2011, 09:12 AM
Thread: Looking around for a good JCI contractor
by Cal1- Replies
- 8
- Views
- 519
RE:JCI
Like i said contact me via my Email my office is located in Metro Boston Area.
GB -
09-20-2011, 02:15 PM
Thread: Looking around for a good JCI contractor
by Cal1- Replies
- 8
- Views
- 519
JCI
Very experienced wth PMI NCM GPL JCBASIC contact info in my profile
-
09-20-2011, 07:56 AM
Thread: Honeywell XBS
by Cal1- Replies
- 3
- Views
- 621
Honeywell XBS
After a recent power failure we cant log on with any of the user ID's. Is there a default password for XBS 1.4.3? My email addy is in my profile if you can help us that would be great.
-
02-23-2011, 07:09 PM
Thread: JCI MD20 with VMA1420s
by Cal1- Replies
- 10
- Views
- 839
You could send the N30 out to be repaired or...
You could send the N30 out to be repaired or install a Tridium style supervisory FX20 would work just fine for you.
-
12-21-2010, 09:33 PM
Thread: Trane Intellipak
by Cal1- Replies
- 10
- Views
- 1,069
Re: Trane Intellipak
Thank You everyone that did the trick although the DWU was set below the Occupied Heating setpoint they may have been set to closely together.
In addition patience is the key it took a long time for... -
12-15-2010, 08:02 AM
Thread: FX Server Questions
by Cal1- Replies
- 5
- Views
- 498
RE: FX SERVER
I appreciate the help and yes I have been to the FX Supervisory Control training class couple years ago but they did not cover the server setup in great detail. I have looked into the AX...
-
RE:GPL
Hi,
What rev PMI and GPL are you running and on what kinda computer is that XP machine there spanky?
Shutdown PMI and launch GPL from the FMS/BIN directory. I dont think GPL was ever tested on XP... -
12-14-2010, 11:06 PM
Thread: NCM Battery
by Cal1- Replies
- 8
- Views
- 1,126
The last one i ordered from JCI this past Summer...
The last one i ordered from JCI this past Summer had a lead time of 8 weeks. Try Ebay buy an old NCM 350 and use the power supply.
GB -
12-14-2010, 10:54 PM
Thread: Trane Intellipak
by Cal1- Replies
- 10
- Views
- 1,069
RE:Intellipak
I thank you all for your help I will be on site later this week and will try the setpoint and review the sequence of operation.Its getting cold up here in the NE :) good for business.
GB -
12-14-2010, 06:57 PM
Thread: FX Server Questions
by Cal1- Replies
- 5
- Views
- 498
FX Server Questions
I have a question on the alarm portal.My Niagara Network is all setup three FX's all see each other and the server.I setup a station recipient for each FX pointing to the server but my alarms are not...
-
12-14-2010, 05:26 PM
Thread: Trane Intellipak
by Cal1- Replies
- 10
- Views
- 1,069
Hi Mark, Yes I tried that yesterday and the gas...
Hi Mark,
Yes I tried that yesterday and the gas heat stages on normally in test mode.The only recent issue with the unit has been the static pressure has been reading hi I am waiting on a altivar... -
12-14-2010, 10:12 AM
Thread: Trane Intellipak
by Cal1- Replies
- 10
- Views
- 1,069
Trane Intellipak
Hi,
I have a problem with a Trane Intellipak.The unit wont stage the gas burner on the heat mode enables but the heat does not stage on.All the temperature sensors are reading ok.I put the unit in... -
12-09-2010, 07:25 PM
- Replies
- 7
- Views
- 591
Trending
Setup M-Trend for the points you need to trend when you want to archive your trend data simply look for the Trenddb.mdb file in the Mdata or active database subdirectory and copy a blank Trenddb.mdb...
-
10-01-2010, 08:16 AM
Thread: NCM/DCM to Extended Architecture
by Cal1- Replies
- 10
- Views
- 709
Re:DCM
Go the Niagara route AX of FX especially if your GPL for the DCM's is complex.The programing capability on the AX/FX is vastly superior to the Extended Architecture product line.
GB -
05-17-2010, 08:33 PM
Thread: JCI - M3i password
by Cal1- Replies
- 8
- Views
- 810
M3 Password
Wow that Sam I must ask thread has legs anyways onto your question try this...
To reset and set up M-Password:
1) Select Start > Programs > JCI > M-Password > Config. Leave User Name blank... -
04-27-2010, 06:23 PM
Thread: FX40 schedule for a AHU102 controler
by Cal1- Replies
- 15
- Views
- 841
RE:Return Fan
Do you have a occupied BD point? Just curious why you are scheduling the fan command itself and not the occupied command.You could also schedule the shutdown command BD 197 if need be. Any chance...
-
04-27-2010, 03:03 PM
Thread: FX40 schedule for a AHU102 controler
by Cal1- Replies
- 15
- Views
- 841
RE:Schedule
What point are you scheduling?
-
02-25-2010, 10:48 PM
Thread: Questions on NCM's
by Cal1- Replies
- 24
- Views
- 983
Re: NCM
I will assume you have a NCM 350.Did you check your Novram in the NCM kinda curious as to what port the modem is assigned to.What type code general with OT or NT use NT when you have a modem assigned...
-
02-17-2010, 09:59 PM
Thread: N-30 Resets
by Cal1- Replies
- 7
- Views
- 378
Re:N30
That sounds like a normal power up sequence for the N30. Leave it alone is my advice we have had several fail downloads and go into boot code conditions or worse for no reason at all. Time to upgrade...
-
02-17-2010, 09:43 PM
Thread: N-30 Resets
by Cal1- Replies
- 7
- Views
- 378
Re:N30
Is the DS2 red led on steady or flashing? Does the controller reset continuously?
GB -
02-03-2010, 08:08 PM
Thread: How do I adjust DX to change outside Temp
by Cal1- Replies
- 15
- Views
- 1,056
RE:Sensor
If you rule out the sensor and connections it sounds as though the only thing left is the wire. I will assume the sensor has worked correctly in the past.Is the sensor mounted in a short penetration...
Results 1 to 25 of 64