  1. Replies
    1
    Views
    569

    I seem to be having a problem on the 134-a...

    I seem to be having a problem on the 134-a chillers smashing the impeller into the wall does anyone out there this problem
  2. Replies
    10
    Views
    1,810

    think about your approaches 2 on cond 6 cooler...

    think about your approaches 2 on cond 6 cooler you sound like you could be low on charge I had from fact low on charge and as your load changes oil return could be a problem also raise water to 44or...
  3. Replies
    9
    Views
    1,415

    I just rebuilt 2 of those 1st make sure your cond...

    I just rebuilt 2 of those 1st make sure your cond water is not to cold then check approach on cooler also on the 23xl I have had to remove alot of the r-22 from some of these best way to charge is...
  4. Replies
    13
    Views
    5,974

    I would like to know if anyone out there has had...

    I would like to know if anyone out there has had any problems with the high pressure 134-a chillers smashing the impeller into the wall on say a minor surge I have 3 that have done this all is clean...
  5. Replies
    12
    Views
    1,043

    Check your flow rates and the design delta t most...

    Check your flow rates and the design delta t most water cooled chillers are 85 ewt 95 lwt now most of the newer high pressure machines would like a 75 gegree ewt