  1. Thread: Goodman Problem

    by topdog
    Replies
    23
    Views
    2,422

    Yes the furnace will shut down if condensate...

    Yes the furnace will shut down if condensate water does not flow.
    You should see water in the open trap(gray box), if not , prime the trap with water and see if it is draining.
  2. Thread: Goodman Problem

    by topdog
    Replies
    23
    Views
    2,422

    High eff. furnace means it is a condensing...

    High eff. furnace means it is a condensing furnace? Induced draft? Sealed burner? System shuts off after one hour run and temperature not reached?

    Suggest check amps on blower motor or induced...
  3. Thread: Goodman Problem

    by topdog
    Replies
    23
    Views
    2,422

    Where is the furnace located? Is it a 80% or...

    Where is the furnace located? Is it a 80% or 90%? Has there been any new work doneto the house?
  4. Replies
    5
    Views
    608

    On the east coast, temperature went from below...

    On the east coast, temperature went from below normal to above normal[feast or famine as we say], company that I work with took on warranty companies -too many- boss wants cash flow, end of story. ...
  5. Replies
    10
    Views
    9,543

    I believe he meant themidistat,which not only...

    I believe he meant themidistat,which not only controls humidity into a dry house but also removes humidity when the house is damp. True most contractors won't install a humidifier in an attic or any...
  6. Replies
    89
    Views
    7,619

    I am an Amerasian and never used my minority...

    I am an Amerasian and never used my minority status for job placement or benefits. I am an American U.S. citizen and want to earn my wages and respect as such. The most important person on any job...
  7. Replies
    10
    Views
    9,543

    Sorry to here about the bad luck with the 14 year...

    Sorry to here about the bad luck with the 14 year old system. I work the DC and Baltimore area and based in Annapolis, MD. Heatpump systems in our area with annual maintenance, usually last 16-20...
  8. Replies
    17
    Views
    1,871

    If designed properly electro-mechanical zoning...

    If designed properly electro-mechanical zoning systems are excellent and can even reduce the tonnage and electricity needed to perform adequate heating and cooling. It is not cheap to install...
  9. Replies
    12
    Views
    4,303

    Need to know tonnage of eqiuipment and duct sizes...

    Need to know tonnage of eqiuipment and duct sizes to make proper adjustments. 8" Flex = 150cfm at .10 static. If it is a return....... less cfm
  10. Replies
    10
    Views
    1,045

    Been using Carrier Comfort Zone system for over...

    Been using Carrier Comfort Zone system for over 10 years, commercial and residential and works great. Hope you said variable speed outdoor system and not indoor unit. Don't believe you can zone with...
  11. Replies
    10
    Views
    9,543

    What happen to the old system?...

    What happen to the old system? Age,burn-out,improper sizing....etc? With the new 13 seer systems make sure duct sizing and load calculations are within specifications, thus you don't repeat...
  12. Thread: Lennox HP

    by topdog
    Replies
    3
    Views
    853

    Lennox heatpump model # HP19-461-6P what is the...

    Lennox heatpump model # HP19-461-6P what is the tonnage?

    TIA, TD
  13. Replies
    14
    Views
    1,154

    No your not asking too much from a distributor....

    No your not asking too much from a distributor. You gave them plenty of time to get your order together and get what parts were necessary. At least to call you back to say if something was not...
  14. Replies
    4
    Views
    660

    If you're putting in variable speed system would...

    If you're putting in variable speed system would not suggest putting dampers in lines to balance air flow or may have motor failure.
  15. Thread: duct work

    by topdog
    Replies
    15
    Views
    1,781

    chillbilly this on the return side, I would...

    chillbilly this on the return side, I would suggest going to .08 to check cfm capabilities.
  16. Thread: duct work

    by topdog
    Replies
    15
    Views
    1,781

    I agree with trane. Flex duct is not the same cfm...

    I agree with trane. Flex duct is not the same cfm as round hard pipe and the pleated filter does restrict airflow even more. You're vs motor doesn't know whether to #@%& or get off the pot.
  17. Thread: Hey Norm...

    by topdog
    Replies
    1
    Views
    635

    OOPS thought I was in General Discussion for a...

    OOPS thought I was in General Discussion for a "Cheers" revival.
  18. Thread: wasted trips

    by topdog
    Replies
    25
    Views
    2,547

    Yeah,but your light stayed on and the batteries...

    Yeah,but your light stayed on and the batteries are dead.
  19. Replies
    18
    Views
    1,883

    bullshoot, you're new to trade stick around and...

    bullshoot, you're new to trade stick around and you'll develop the tough skin you're going to need to continue in this trade. Judging from the replies, I don't think some of these guys knew that...
  20. Replies
    18
    Views
    1,883

    Trying to check in heating at that ambient is...

    Trying to check in heating at that ambient is going to be tough. If I remembered correctly Trane doesn't even have a chart for that. You're in a deadzone. But I could be mistaken,maybe someone has a...
  21. Thread: duct work

    by topdog
    Replies
    15
    Views
    1,781

    If it were hard pipe 10 would be around 350cfm...

    If it were hard pipe 10 would be around 350cfm and 12 600cfm. Flex duct is less. How much less, maybe someone else will reply. 10x20=550cfm 20x16=900cfm
  22. Replies
    9
    Views
    1,176

    Look at this thread ...

    Look at this thread http://hvac-talk.com/vbb/showthread.php?threadid=38790
  23. Thread: wasted trips

    by topdog
    Replies
    25
    Views
    2,547

    Flashlight

    Flashlight
  24. Replies
    9
    Views
    1,176

    A 13 seer unit made by one manufacturer or...

    A 13 seer unit made by one manufacturer or another is still only capable of doing 13 seer when matched properly. It's the install that makes the system last longer.

    I would check to see how many...
  25. Replies
    6
    Views
    1,278

    It's kinda like holding a universal CFC licence,...

    It's kinda like holding a universal CFC licence, huh doc?
  26. Replies
    47
    Views
    4,348

    I agree with shophound. Need to take indoor...

    I agree with shophound. Need to take indoor ambient,indoor wetbulb,delta across indoor coil, outdoor ambient,pressures, subcooling and superheat, and compressor amps. Also indoor and outdoor model...
  27. Replies
    5
    Views
    928

    Dan most of my customers will not go with higher...

    Dan most of my customers will not go with higher seer units. They are landlords of rental properties or transients. Here for a few years. Just letting them know about the minimum seer they have to...
  28. Replies
    9
    Views
    1,084

    That is correct between transformer and board.

    That is correct between transformer and board.
  29. Replies
    5
    Views
    928

    will104 here in Maryland it's about the same rate...

    will104 here in Maryland it's about the same rate for installers. Your boss is right about service techs. Soon the housing boom will be over with higher interest rates coming back. New 13 seer...
  30. Replies
    9
    Views
    1,084

    5 amp prong type with insulated spade connectors.

    5 amp prong type with insulated spade connectors.
  31. Replies
    9
    Views
    1,084

    Company I work with installs Goodman and Ruud...

    Company I work with installs Goodman and Ruud neither unit has low voltage fuse on AHUs. I tell install crew to install 5 amp off transformer before any startup.
  32. Replies
    16
    Views
    2,915

    Like I tell my installers, "just because you can,...

    Like I tell my installers, "just because you can, doesn't mean you should!"
  33. Replies
    9
    Views
    1,890

    Now I have a dumb question, "is this by any...

    Now I have a dumb question, "is this by any chance a heatpump?" If so, might be defrost board energizing reversing valve short or w going back to electric heat.
  34. Replies
    14
    Views
    1,401

    kcb203, have you tried Cropp/Metcalfe I believe...

    kcb203, have you tried Cropp/Metcalfe I believe they service your area. Please explain to the dispatcher age of system and what you are trying to upgrade to, if possible. This may insure you that you...
  35. Replies
    15
    Views
    1,495

    Definitely call the first contractor back and let...

    Definitely call the first contractor back and let them know repairs were made by another company. They may not know what their techs are doing to their customers and you may get your money back.
  36. Thread: system charging

    by topdog
    Replies
    28
    Views
    2,962

    hvactex we need more info. outdoor ambient indoor...

    hvactex we need more info. outdoor ambient indoor wet bulb and model/serial #s would be nice. Would like to help you out.
  37. Thread: system charging

    by topdog
    Replies
    28
    Views
    2,962

    I think Dice meant,"Wash 'er the indoor coil is...

    I think Dice meant,"Wash 'er the indoor coil is blocked!"
  38. Replies
    20
    Views
    2,464

    Yes you are probably low on refrigerant about 6...

    Yes you are probably low on refrigerant about 6 ozs.
  39. Thread: Old G.E. AHU

    by topdog
    Replies
    0
    Views
    570

    I have an old G.E. ahu 3 phase 460 volt model#...

    I have an old G.E. ahu 3 phase 460 volt model# BWE060C400EO and serial# 175662. It is being used to heat and cool a nursing home. Problem I am having is the blower motor is locking up,and don't know...
  40. Replies
    32
    Views
    2,244

    I use to be conceited. Found out it was a fault...

    I use to be conceited. Found out it was a fault and I don't have any.
  41. Replies
    3
    Views
    1,134

    Are you trying to cool the house or heat it? Is...

    Are you trying to cool the house or heat it? Is this a txv or piston system? What is the indoor wetbulb temperature? There should be a chart on the outdoor units back cover. What are the model and...
  42. Replies
    14
    Views
    2,960

    Didn't want to go there shophound (about the...

    Didn't want to go there shophound (about the techs} but well said!! It's sad that with all the training and education available to the techs, they still want to use pressures to diagnose problems.
  43. Replies
    14
    Views
    2,960

    Sorry to hear of the problems with your techs...

    Sorry to hear of the problems with your techs diagnosing your cooling problem. If there is an indoor thermal expansion device the tech needs to get into the attic to see that it exists. If there is a...
  44. Replies
    30
    Views
    9,163

    Thanks beenthere. Trying to find some way of...

    Thanks beenthere. Trying to find some way of getting customer what he wants, without getting company into trouble.
  45. Replies
    30
    Views
    9,163

    beenthere trust your opinion and advise. Maybe...

    beenthere trust your opinion and advise. Maybe should repost, but here goes ,variable speed fan drive(Carrier}, attic system heatpump,not insulated well and new construction. What humidifier would...
  46. Replies
    12
    Views
    5,545

    Depending on the model Jenn-Air you have will...

    Depending on the model Jenn-Air you have will determine length of run,elbows,flex duct,material,etc... need to know this before calling Jenn-Air.You should have the installation instructions with the...
  47. Replies
    12
    Views
    5,545

    I have not seen pvc used on a Jenn-Air system. I...

    I have not seen pvc used on a Jenn-Air system. I would definitely check the instructions or get a hold of Jenn-Air to see if this is permissable.
  48. Replies
    10
    Views
    2,310

    I agree with the "bald one" and due to the amount...

    I agree with the "bald one" and due to the amount of water leaking during the summer, IMHO think it may be under charged or has a refrigerant leak. You need to get a pro.
  49. Replies
    8
    Views
    1,590

    C'mon guys at 285*F steam is not the actual...

    C'mon guys at 285*F steam is not the actual temperature on the coils,just the temperature coming from your steam machine. Breakdown of oil and refrigerant though is something I did not think of,and...
  50. Replies
    8
    Views
    1,590

    Thanks guys for the response and the link. I am...

    Thanks guys for the response and the link. I am definitly going to research the cleaning process more and hopefully find something that can reduce the time and maintain safety.