Search:

Type: Posts; User: david5307

Search: Search took 0.00 seconds.

  1. Thread: PLENUM TEMP

    by david5307
    Replies
    5
    Views
    1,809

    many things could effect the plenum temp. gas...

    many things could effect the plenum temp.

    gas pressure
    cfm: if to high temp rise will be lower
  2. Replies
    7
    Views
    2,808

    lake source heat pump can be very efficient....

    lake source heat pump can be very efficient. intallation should be done by a contractor that specializes in this type of unit or one with lots of experience with water source hp. depth of line in...
  3. Replies
    1
    Views
    780

    you made need a vacuum breaker on the steam...

    you made need a vacuum breaker on the steam piping
    you would install a check valve on pipe that would not allow steam to escape but would allow air into piping after steam is shut off.
  4. Replies
    31
    Views
    3,789

    just stay away from carrier rtu and another piece...

    just stay away from carrier rtu and another piece of junk is tranes new pesedent rtu
  5. Replies
    12
    Views
    2,855

    elctric heat selection formulas

    thanks for the diagram. i actually found some and these strips are wired in the wye instead of delta also found some formulas that might be helpful

    kW = cfm x delta T x 1.985/3413

    cfm = kW x...
  6. Replies
    20
    Views
    7,182

    in regards to the post from boat racer. these...

    in regards to the post from boat racer. these boxes were bought without any controls. they have novar dampers that are also the equipment controler. the front end computer is called continuum. first...
  7. Replies
    20
    Views
    7,182

    i finally figured out the problem. found prints...

    i finally figured out the problem. found prints on building and it specified that the damper was to close when there is no need for cooling. also found some info on the boxes which sayed that the fan...
  8. Replies
    12
    Views
    2,855

    the wire diagram on the unit illistrated two...

    the wire diagram on the unit illistrated two different
    types of strips. i would like to find a web site with examples of 3-phase strip wiring diagrams. the reason is i know the strips are bad and i...
  9. Replies
    20
    Views
    7,182

    i meant that i do agree with you about the...

    i meant that i do agree with you about the entering air shuting down.
  10. Replies
    20
    Views
    7,182

    i don't agree with you about the entering air. i...

    i don't agree with you about the entering air.
    i work on another building with titus parallel and series fpb that has a min heat cfm and the parrallel boxes, the fan come on when there is a call for...
  11. Replies
    12
    Views
    2,855

    anyone have a wire diagram for three phase heat...

    anyone have a wire diagram for three phase heat strips
    there are six terminal posts for strips 460v
  12. Replies
    20
    Views
    7,182

    you are right. there is no di to prove fan is...

    you are right. there is no di to prove fan is operating.
    can't remember what type of controls it has. its something along the line of novar, not trane, siemens, johnson
    while scanning the controls...
  13. Replies
    13
    Views
    5,384

    not leaving any coil cleaner on there to long are...

    not leaving any coil cleaner on there to long are ya? i've seen that take'em out
  14. Replies
    4
    Views
    788

    this a vav system with dx roof tops. they supply...

    this a vav system with dx roof tops. they supply 55 deg air to the vav boxes. the exterior boxes have parallel fan wich pulls air from the attic with common return.

    there is no make up air, maybe...
  15. Replies
    20
    Views
    7,182

    the temp is measured by the contols. there are...

    the temp is measured by the contols. there are only two contactors in the box. one for fan(heat1 and one for heat2). yes there is a o-10vdc for the damper actuator at the supply air duct intering the...
  16. Replies
    20
    Views
    7,182

    what is a dc ramp? these controls have digital...

    what is a dc ramp? these controls have digital outputs for fan/heat stage 1 and heat stage 2 and it has an analog out for damper position. the only inputs seem to be a damper count(what ever that is)...
  17. Replies
    4
    Views
    788

    i am not sure what you are asking but the first...

    i am not sure what you are asking but the first stage is the fan in the box which pulls from the attic space with common return...
  18. Replies
    20
    Views
    7,182

    i am talking about the fan in the fan powered vav...

    i am talking about the fan in the fan powered vav box. the system has rtu that supply 55deg air to all the fan powered vav boxes on the exterior of the building and to all of the vav boxes in the...
  19. Replies
    4
    Views
    788

    what are some common problems that would cause...

    what are some common problems that would cause about 80% of the buildings exterior zones to be cold if all the fpb have electric heat and the ddc program shows to be calling for the. there is no air...
  20. Replies
    20
    Views
    7,182

    i have a bunch enviro-tec vfr fan powered vav...

    i have a bunch enviro-tec vfr fan powered vav boxes with electric strips that are not heating. found one box while looking at the ddc controls that was calling for stage 2 heat but not stage one,...
  21. Replies
    9
    Views
    987

    you got your money's worth

    if this furnace is that old be carefull, i've seen a lot of cracked heat exchangers with units that old.
    the fan is started in when the unit reaches a certain temp depending on the manufacturer....
  22. Replies
    1
    Views
    565

    i worked on a trane ahu with a time delay relay...

    i worked on a trane ahu with a time delay relay that mounted to the indoor fan relay. the ralay is bad and there was no wiring diagram or manuals. i've never seen a relay like this and thought it was...