Search:

Type: Posts; User: controlgeek

Page 1 of 16 1 2 3 4

Search: Search took 0.01 seconds.

  1. Replies
    6
    Views
    262

    Is it offline?

    Is it offline?
  2. Replies
    7
    Views
    305

    Could I also get a copy? My email is in my...

    Could I also get a copy? My email is in my profile. TIA
  3. Me too! Tia

    Me too! Tia
  4. Replies
    6
    Views
    309

    I have used these to run N2 over fiber and they...

    I have used these to run N2 over fiber and they worked well.

    www.sitech-bitdriver.com/products/datasheets/2110.pdf
  5. Replies
    32
    Views
    1,245

    What is the busy time on the network? Have you...

    What is the busy time on the network? Have you looked at the tuning policy?
  6. Replies
    35
    Views
    2,596

    I would like a copy. My email is in my profile.

    I would like a copy. My email is in my profile.
  7. Replies
    29
    Views
    1,002

    Is the serial shell jumper in the correct...

    Is the serial shell jumper in the correct position for operation?
  8. Thread: Old Staefa

    by controlgeek
    Replies
    89
    Views
    12,343

    Thanks!

    Thanks!
  9. Thread: Old Staefa

    by controlgeek
    Replies
    89
    Views
    12,343

    Thanks for the info. I don't believe there is a...

    Thanks for the info. I don't believe there is a front end but will know more on Thursday at a visit. Can someone email me the software and pinout for the cable?

    Email is in my profile. TIA.
  10. Thread: Old Staefa

    by controlgeek
    Replies
    89
    Views
    12,343

    Will the pc tool allow me to pull existing logic...

    Will the pc tool allow me to pull existing logic out to view for an Ax integration? Getting ready to propose on one but havent done one yet. Could someone email me the software and pinout?

    Tia
  11. Replies
    2
    Views
    287

    Back in the day I used quite a few of these with...

    Back in the day I used quite a few of these with DX-9100's with good results. Of course this assumes you will still be using N2.
  12. Unless it happened very recently Distech has not...

    Unless it happened very recently Distech has not released AX 3.8 or the support package for it. When I have asked they say it will be at some point but have no date.
  13. Replies
    8
    Views
    358

    3.03 is the last DOS version of Hpro. It will...

    3.03 is the last DOS version of Hpro. It will upgrade the application to the winpro version so you shouldn't lose logic but if you upgrade by uploading the existing program in the controller and not...
  14. Replies
    8
    Views
    358

    One thing to pay attention to is that some ADF...

    One thing to pay attention to is that some ADF and BDF parameter numbers can change when you upgrade from the DOS Hpro to Winpro so some database references may need to be updated.
  15. Not that I have been able to and I haven't been...

    Not that I have been able to and I haven't been successful in getting Trane to sell me the software.
  16. In my experience Trane needs to perform some...

    In my experience Trane needs to perform some configuration and setup for communication to occur. Attached is a document I have on this. It is a bit dated but the process is probably similar.
  17. Replies
    7
    Views
    499

    Perhaps a clean dist and re-commissioning would...

    Perhaps a clean dist and re-commissioning would help?
  18. Replies
    7
    Views
    499

    Have you updated the license for the JACE?...

    Have you updated the license for the JACE? Starting in 3.6 I believe the JVM changed to a SUN one from an IBM? one and the features in the license is different.
  19. Replies
    10
    Views
    453

    Did you set the address on the UNT's to match the...

    Did you set the address on the UNT's to match the addresses in the NAE database?
  20. Replies
    7
    Views
    288

    There isn't a N1 driver I am aware of. You could...

    There isn't a N1 driver I am aware of. You could explore the OPC driver and a OPC to N1 gateway such as http://www.matrikonopc.com/opc-drivers/222/base-driver-details.aspx although I have no direct...
  21. Replies
    7
    Views
    288

    The S4 group makes a N2 to Bacnet router that can...

    The S4 group makes a N2 to Bacnet router that can coexist with the NCM's. You can bring everything into Ax via Bacnet and then migrate the GPL processes out over time when ready and remove the...
  22. Replies
    7
    Views
    393

    Tridium had a solutions group at the summit...

    Tridium had a solutions group at the summit saying they could assist with this but I have a feeling it wouldn't be budget friendly.
  23. Replies
    8
    Views
    675

    Actually terminal units have everything to do...

    Actually terminal units have everything to do with the amount of OSA being brought in. In a CV system the designer sized per minimum OSA per person as required by code. DCV allows minimum ventilation...
  24. Replies
    22
    Views
    1,908

    In the Niagara 4 breakout session I went to the...

    In the Niagara 4 breakout session I went to the re-certification question was asked and the answer was it would be an online module of some kind for people already Ax certified. I suppose that could...
  25. Replies
    22
    Views
    1,908

    I believe the plant controller came about from...

    I believe the plant controller came about from some vendors or manufacturers trying to provide a product that meets Bacnet IP certification where specifications require it. As far as NDIO goes in...
Results 1 to 25 of 386
Page 1 of 16 1 2 3 4
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine
Comfortech365 Virtual Event