    Just to followup on this with the final solution:...

    Just to followup on this with the final solution:

    Shortly after my last post the comm problems came back with a vengence. I noticed that with the bus hook up or unhooked the bus was dead. So I...
  2. Replies
    12
    Views
    394

    That may very well be true. I got so caught up in...

    That may very well be true. I got so caught up in the "this has to be fixed now if not sooner" that the comm problem completely slipped off of the radar for several hours, and so missed the chance to...
  3. Replies
    12
    Views
    394

    Fixed! :grin2: We had a compressor fail the...

    Fixed! :grin2:

    We had a compressor fail the other day (second one) in a 3PH 6T HP. Two legs were drawing 45+A and the third less than 3A; voltage was unbalanced: 210-210-80. A resistance check...
  4. Replies
    12
    Views
    394

    Wow! They are zinging.... The three highest are...

    Wow! They are zinging.... The three highest are modules off-line due to equipment upgrades. The rest all fall in and out of com. I'll check voltages tomorrow.


    23
    19
    23
    1858
    ...
  5. Replies
    12
    Views
    394

    Ahh.. nice. I'll reset them and add that to the...

    Ahh.. nice. I'll reset them and add that to the troubleshooting mix. Thanks!
  6. Replies
    12
    Views
    394

    I know where to find them in ESS, but have never...

    I know where to find them in ESS, but have never quite understood exactly what information they conveyed, even after reading the manual over.
  7. Replies
    12
    Views
    394

    I'll double check and post back. Yes, for...

    I'll double check and post back.



    Yes, for well over a year since the system was installed in these three buildings.



    Yes, and have worked quite well.
  8. Replies
    12
    Views
    394

    Novar Mod Com Weirdness

    One of our Savvys began showing random com losses to random modules at random times about four weeks ago. Since then we have checked every connection on the bus and found nothing lose or unhooked....
  9. Replies
    11
    Views
    2,192

    This is an old thread, but I encountered the same...

    This is an old thread, but I encountered the same problem with our Savvy.

    I have two scripts which scrape data from the web interface and log it to a SQL db from which we generate trending graphs...
  10. Replies
    0
    Views
    346

    Novar IOM2 Transition Board

    Hi,

    I'm looking for a used IOM2 base/transition board. My email addy is in my profile.

    Thanks,
    Chris
  11. Replies
    2
    Views
    714

    Is this a Carrier economizer package? If so,...

    Is this a Carrier economizer package?

    If so, this document: http://www.docs.hvacpartners.com/idc/groups/public/documents/techlit/40rm-24si.pdf

    on page 9, lower right side, suggests that you...
  12. Replies
    54
    Views
    8,402

    Would anyone be willing to do some packet...

    Would anyone be willing to do some packet captures with tcpdump or wireshark on the comms between iScope and an executive controller like Savvy? I'm particularly interested in data logging comms.
    ...