Search:
Type: Posts; User: nohelphere
Search: Search took 0.01 seconds.
-
05-09-2013, 04:48 PM
Thread: Proof that nothing can beat a NAE
by nohelphere- Replies
- 5
- Views
- 319
That's great...
That's great...
-
04-26-2013, 01:25 PM
Thread: Integrating Alerton to Metasys MSEA
by nohelphere- Replies
- 11
- Views
- 265
We put them using IP and had issues with the...
We put them using IP and had issues with the older VLX's. I didn't try to do this over MSTP.. I had a thread on it a few months back..
... -
04-26-2013, 01:24 PM
Thread: Alerton integration into JCI NAE
by nohelphere- Replies
- 9
- Views
- 337
Update on this- The 2 BBMD's removed didn't...
Update on this-
The 2 BBMD's removed didn't help. Apparently the older VLX's were suseptable to comm problems and the NAE's were pinging them to death with the interlocks, so they would drop out.... -
04-23-2013, 09:32 PM
Thread: ABB Binary COV reporting
by nohelphere- Replies
- 0
- Views
- 90
ABB Binary COV reporting
Has anyone ever had issue with the newer ABB Electronic Eclipse bypass not changing binary points over Bacnet?
I have a hand-auto point mapped and it will not change states unless I delete it and... -
04-18-2013, 07:18 AM
Thread: EASY IO Analog Input filter
by nohelphere- Replies
- 5
- Views
- 202
Thanks a ton for the info, the doc I have either...
Thanks a ton for the info, the doc I have either isn't very good, or the 12 hour days are catching up and I missed it. I have a fairly large scan time value because it looks like it is in...
-
04-17-2013, 10:29 PM
Thread: DanFoss
by nohelphere- Replies
- 7
- Views
- 716
Dan Foss sent out their rep and got it fixed. ...
Dan Foss sent out their rep and got it fixed. Apparently, version 4.0 was never supposed to be shipped, but we ended up with 8 of them. I guess the patch is 4.0.1. Once mapped- it seems pretty...
-
04-17-2013, 10:24 PM
Thread: EASY IO Analog Input filter
by nohelphere- Replies
- 5
- Views
- 202
Thanks for the help guys- the sensor was...
Thanks for the help guys- the sensor was configured for a custom table, when all it needed was to be put as platinum. EasyIO is not my strong suite and I was told that startup had already been done....
-
04-16-2013, 07:59 PM
Thread: EASY IO Analog Input filter
by nohelphere- Replies
- 5
- Views
- 202
EASY IO Analog Input filter
Hello All,
Has anyone had experience with the temperature reading on an EasyIO controller jumping around like crazy? It's for supply air temp for an AHU and it will jump around 2 degrees instead... -
04-09-2013, 12:43 PM
Thread: DanFoss
by nohelphere- Replies
- 7
- Views
- 716
Any luck? The drives I have are supposedly...
Any luck? The drives I have are supposedly "embedded" Bacnet but I can't discover...
-
04-05-2013, 03:41 PM
Thread: JCI Metasys on Android OS?
by nohelphere- Replies
- 2
- Views
- 227
It will work with RAP. Fairly well actually...
It will work with RAP. Fairly well actually after it has been setup. It has to have an ADs/x though. Graphics won't work on an apple product but anything that will support Silverlight, it will.
-
03-21-2013, 09:34 PM
Thread: JCI NAE features
by nohelphere- Replies
- 11
- Views
- 472
If this is possible I would love to hear a...
If this is possible I would love to hear a solution. It's painful the way it is setup now.
When we remote desktop in, where are these .xml files kept? -
03-05-2013, 09:13 AM
Thread: Alerton integration into JCI NAE
by nohelphere- Replies
- 9
- Views
- 337
Update.. I've found 2 BBMD devices on the...
Update.. I've found 2 BBMD devices on the Alerton side. My theory is that the BBMD's are broadcasting everytime I have an interlock that is looking for something. What is strange is that all...
-
03-01-2013, 09:14 PM
Thread: Alerton integration into JCI NAE
by nohelphere- Replies
- 9
- Views
- 337
Correct on all accounts I believe. The VLXs seem...
Correct on all accounts I believe. The VLXs seem to be similar to a JCI NCE. I was talking to the local Alerton rep today and he was saying the older VLXs had issues dropping out if the traffic is...
-
02-28-2013, 11:50 PM
Thread: Alerton integration into JCI NAE
by nohelphere- Replies
- 9
- Views
- 337
So, I have all devices that are on the BCMs and...
So, I have all devices that are on the BCMs and the VLXs mapped. When I put in an interlock, it kills the VLXs only, the BCMs stand loud and proud. All devices have unique id's.
Next step that I... -
02-28-2013, 07:59 PM
Thread: Alerton integration into JCI NAE
by nohelphere- Replies
- 9
- Views
- 337
Alerton integration into JCI NAE
Hello all,
I did a search but couldn't find anything- I may be blind. I've mapped Alerton Bacnet / IP devices into NAE's without issue. However- anytime I try to use an interlock that looks at a... -
02-07-2013, 10:50 PM
Thread: Phoenix Bacnet integration
by nohelphere- Replies
- 6
- Views
- 325
The Phoenix system will need to be setup to be...
The Phoenix system will need to be setup to be commandable.
-
02-04-2013, 07:42 PM
Thread: BacNet IP intergation to Metasys
by nohelphere- Replies
- 15
- Views
- 853
Did you reboot the NAE after you enabled the site...
Did you reboot the NAE after you enabled the site to be a Bacnet network?
-
02-01-2013, 10:29 PM
Thread: Metasys Graphics
by nohelphere- Replies
- 16
- Views
- 941
We had this problem running IE9. If you...
We had this problem running IE9. If you uninstall the update the GGT graphic will load.
-
01-06-2013, 11:20 PM
Thread: JCI - FEC / NCE pulse
by nohelphere- Replies
- 3
- Views
- 490
It has to be a BI and it has to be assigned as...
It has to be a BI and it has to be assigned as accumulator object in cct.
-
12-18-2012, 10:29 AM
Thread: DanFoss
by nohelphere- Replies
- 7
- Views
- 716
What issues are you having? we are doing an...
What issues are you having? we are doing an indentical setup- startup will be next month.
-
12-17-2012, 03:30 PM
Thread: Dan Foss Bacnet
by nohelphere- Replies
- 5
- Views
- 495
What software do you use?
What software do you use?
-
12-17-2012, 03:29 PM
Thread: NCE
by nohelphere- Replies
- 3
- Views
- 437
In theory it shouldn't be an issue- however I...
In theory it shouldn't be an issue- however I would make sure the instance numbers on the trunk are unique. I have had issues with instance numbers being the same on later versions where on the...
-
12-14-2012, 01:42 AM
Thread: Dan Foss Bacnet
by nohelphere- Replies
- 5
- Views
- 495
Thanks man, I should of just PM'd you- I figured...
Thanks man, I should of just PM'd you- I figured you had it..
-
12-13-2012, 02:46 PM
Thread: Dan Foss Bacnet
by nohelphere- Replies
- 5
- Views
- 495
Dan Foss Bacnet
Does anyone have a Dan Foss Bacnet point mapping list with instance numbers? I'm building the database offline and haven't found any literature online. I could be blind however...
Thanks -
12-13-2012, 02:26 PM
Thread: Tridium Training
by nohelphere- Replies
- 7
- Views
- 585
I was in this class as well.. small world .. One...
I was in this class as well.. small world .. One thing that prepared me a lot for it was the study guide (CBT's) they give out prior to the course. I thought the CBT's were thought provoking in...
Results 1 to 25 of 41