Search:

Type: Posts; User: mechmike2

Page 1 of 6 1 2 3 4

Search: Search took 0.01 seconds.

  1. Replies
    10
    Views
    310

    As always check software manager to be sure...

    As always check software manager to be sure modules match up and upgrade if needed
  2. Replies
    10
    Views
    310

    You will have no problem commissioning, or...

    You will have no problem commissioning, or working in general, on a Vykon jace with Webs workbench.
  3. Replies
    3
    Views
    252

    Google Phoenix SRV-100. Thats what we used or a...

    Google Phoenix SRV-100. Thats what we used or a fairly large Bacnet integration. Phoenix Rep.had to set up the server and expose the points, was a pain in the ass getting them to show points I...
  4. Replies
    5
    Views
    465

    Strange thing happened recently when I used...

    Strange thing happened recently when I used station copier to change name of a site. After changing the name and rebooting when I opened the App. Director there were 2 stations on the Jace Old name...
  5. Replies
    6
    Views
    300

    add your email to profile and I'll send you some...

    add your email to profile and I'll send you some docs
  6. Replies
    44
    Views
    1,674

    The drive creates it own 24 VDC for the DI's

    The drive creates it own 24 VDC for the DI's
  7. Replies
    1
    Views
    296

    There are some decent graphics in the...

    There are some decent graphics in the kitPxGraphics module. You can put together a decent ERV, animated wheel included.
  8. Replies
    71
    Views
    5,611

    I am also wondering what device you are talking...

    I am also wondering what device you are talking about. It would be great to get what a Jace offers without having to pay licensing fees, upgrade fees, memory upgrade fees,...

    Shenanigans ??
  9. Replies
    71
    Views
    5,611

    What I love about Niagara is that I can bring in...

    What I love about Niagara is that I can bring in multiple devices talking different protocols and bring them in to one place and give the end user what they want. Nothing in life is cheap.
  10. Replies
    7
    Views
    854

    Part 1 Ductwork Part 2 Piping Part 3 Service...

    Part 1 Ductwork
    Part 2 Piping
    Part 3 Service
    Part 4 Realize I'm 40 and hate doing above.
  11. Replies
    1
    Views
    408

    Start/Stop loops in the 15c is how scheduling is...

    Start/Stop loops in the 15c is how scheduling is done. You would link schedule from the "A" to the Start/Stop loop, then use a Logic Loop to control a DO (FanEnable) off the Start/Stop.
  12. Thread: Btu

    by mechmike2
    Replies
    9
    Views
    616

    Love it.

    Love it.
  13. Sorry, the Reflash tool is for Spyders.

    Sorry, the Reflash tool is for Spyders.
  14. Replies
    8
    Views
    517

    Does Effective Set Point reflect last change?

    Does Effective Set Point reflect last change?
  15. Add email to profile

    Add email to profile
  16. There is a reflash tool to upgrade or downgrade...

    There is a reflash tool to upgrade or downgrade firmware
  17. Replies
    1
    Views
    471

    Carrier Field Assistant 6.0

    I was told it was possible to use Firefox instead of I.E. as interface. Just installed FA 6.0 but can't find where to change default browser, still uses I.E..

    Anyone know?
  18. Replies
    33
    Views
    3,579

    I like the Niagara platform, constant version...

    I like the Niagara platform, constant version suck, but what else can do what it does? License a driver and integrate a device. Granted some are easier than others and docs sometimes suck, but who...
  19. Chipkin has some good manuals

    Chipkin has some good manuals
  20. Replies
    6
    Views
    581

    Done a few 15C to AX and the first definitely...

    Done a few 15C to AX and the first definitely sucks, but ain't that always the case?
    There is a "15C for learn" object that you would copy to lon network, match up device, do a learn, upload, and...
  21. Station Dislpay name in supervisor keeps changing

    How do you keep the display name of a niagara station in a supervisor from changing. Have reset it over and over but always goes back. Cannot figure out where it derives the display name.
  22. Replies
    9
    Views
    936

    If I recall correctly LonSpec backups are .ntb...

    If I recall correctly LonSpec backups are .ntb files unsure what .mdb files are.
  23. Replies
    5
    Views
    950

    you know whats weird---I get that same stupid...

    you know whats weird---I get that same stupid face thing for the letter P on one of my stations when it text messages. Don't know why. Just thought I'd throw it out there.
  24. Replies
    4
    Views
    454

    Each unit now has its own OA sensor. What they...

    Each unit now has its own OA sensor. What they want is a uniform OA temp which will be the same for all units. If I pick 1 unit to broadcast its OA temp then done deal, but where I could do that on a...
  25. Replies
    4
    Views
    454

    Carrier RTU-Open Outside Air Question

    Have a customer with a few sites that each have appx. 20 Carriers with RTU-Open controllers. The units, as is, use their individual OA sensor for various control strategy's. What customer would like...
  26. Replies
    5
    Views
    578

    7.67 is latest version as far as I know

    7.67 is latest version as far as I know
  27. Replies
    0
    Views
    365

    Reliatel to AX integration issue

    Doing a Trane Reliatel integration and am having an issue where I need to be able to allow the tenant to have set point adjustment from the wall sensor but only between ranges. Sensor installed are...
  28. Replies
    2
    Views
    403

    Sent you a palette that contains a 15C for Learn...

    Sent you a palette that contains a 15C for Learn device that makes it easier to work these devices. More info. on Buildings Forum on these devices also.
  29. Replies
    1
    Views
    249

    Adding modules to FX-60

    Have to add a Lon network to an FX-60, there are no lon modules install as it came, it is licensed for lonworks. I am leary of connecting to Johnson device with my Webs workbench and transferring the...
  30. Thread: vav help

    by mechmike2
    Replies
    6
    Views
    730

    KMC has some offerings for standalone VAVs. Going...

    KMC has some offerings for standalone VAVs. Going to try out their "Simple VAV" on a box tomorrow to see how they work.

    Envirotec another option for standalone.
  31. Replies
    4
    Views
    469

    After you set up your Rapidzone system the last...

    After you set up your Rapidzone system the last tab is "Finish" in which you can save the job. After saving job a network tab opens up, if you open the network tab it brings up another screen and if...
  32. Replies
    10
    Views
    845

    I have 5.1 Tools on an older laptop, trying to...

    I have 5.1 Tools on an older laptop, trying to get the new 6.0 version because I can't get 5.1 to work on new Windows 7 computer, unsure why.
  33. Replies
    10
    Views
    845

    Sent a copy of mod stat report off to a Carrier...

    Sent a copy of mod stat report off to a Carrier controls tech I know and he noted error that stated "could not allocate mem spaces", means that board needs replacing.
  34. Replies
    10
    Views
    845

    Carrier RTU Open Question

    Have an RTU that has quit twice on a "Program Stopped Alarm". Literature rather lacking on what causes the alarm. Downloading controller rings it back for a while. Anyone seen this before?
  35. Replies
    3
    Views
    486

    That is pretty much the same way I have it set up...

    That is pretty much the same way I have it set up now, just trying to get the 1 and done included in the sequence.
  36. Replies
    3
    Views
    486

    Spyder Morning Warm Up

    I am trying to figure a way to do morning warm up in a spyder. I am stuck at keeping warm up off after Return Air reaches set point or should I say keeping warm up from re-initializing if RA should...
  37. Replies
    3
    Views
    443

    Sent you some docs. Check out 74-2958 around page...

    Sent you some docs. Check out 74-2958 around page 60 is point lists
  38. Replies
    17
    Views
    2,001

    A series fan box is a constant volume application...

    A series fan box is a constant volume application where , if balanced properly, delivers the same amount of air to the space constantly. They work OK if balanced properly. I think people complain...
  39. Replies
    6
    Views
    530

    Thanks for the info.. If a lon integration is not...

    Thanks for the info.. If a lon integration is not possible can't a TCI be installed and I could use a Comm 4 driver on Jace? From what I have been researching it seems to be a good alternative, other...
  40. Replies
    6
    Views
    530

    That would be greatly appreciated. Serial # is...

    That would be greatly appreciated. Serial # is J97H72633. Having a difficult time getting info about these units.
  41. Replies
    6
    Views
    530

    Old Intellipak integration question

    Wonder if anyone knows if all Trane Intellipak RTUs are compatible with LCI-I cards. Unit is from 1997 and design sequence is "M". Was told I may need to check #'s on boards to determine if cards...
  42. Replies
    19
    Views
    3,687

    I have a customer with a number of 1997...

    I have a customer with a number of 1997 Intellipaks and is looking to install LCI cards in them to integrate into a lon network. Does anyone know if the LCI is compatible with a the older I-Paks,...
  43. Replies
    11
    Views
    1,486

    I have worked with it.

    I have worked with it.
  44. Replies
    11
    Views
    1,486

    You may want to see if the York units are...

    You may want to see if the York units are configured correctly, that requires using their Simplicity software tool which you can get from your local York/JCI dealer, if I remember correctly there is...
  45. Replies
    11
    Views
    1,486

    Are your York units Intelli-Comfort with...

    Are your York units Intelli-Comfort with FieldServer bacnet gateways?
  46. Replies
    7
    Views
    663

    Did one recently with xl10s and 15cs about 250...

    Did one recently with xl10s and 15cs about 250 devices, put in 3 jaces and supervisor. Time consuming, very. All 15cs were programmed differently so couldn't make one RTU template. Vavs and Fpts...
  47. Replies
    3
    Views
    413

    Thanks for the info. Now i'm getting licensing...

    Thanks for the info. Now i'm getting licensing errors, jace won't boot. Will go by distributors shop Monday with jace in hand, license is in and valid but still dead in water. Should have waited till...
  48. Replies
    3
    Views
    413

    connecting to a new fx60

    Have a job that speced an Fx60 jace. I am a Webs user and have never hooked up to a new Fx jace. Thought all FX jaces have an embedded workbench in them and could be accessed through browser but am...
  49. Replies
    9
    Views
    1,264

    I opened up one of the Venom apps and I see what...

    I opened up one of the Venom apps and I see what you mean, you don't have the option to bring the AV in as an enum point. Definitely curious as to how they were able to. Only way I know to bring in...
  50. Replies
    9
    Views
    1,264

    It looks like you are trying to add a network...

    It looks like you are trying to add a network point from spyder tool into niagara point folder. You would have to add the point to the spyder control program and then proxy it into niagara
Results 1 to 50 of 269