Search:

Type: Posts; User: airdata870

Page 1 of 9 1 2 3 4

Search: Search took 0.01 seconds.

  1. Replies
    8
    Views
    651

    That is exactly what is the problem is.I balance...

    That is exactly what is the problem is.I balance commercial systems daily,and see this senerio quite often and usually move the takeoff before the elbow or farther down from the elbow.In my opinion...
  2. Replies
    17
    Views
    5,601

    UTabtech, Download version 3.0 from their...

    UTabtech, Download version 3.0 from their website,in the preference page highlight the USB box and highlight the dropdown to LON1 and you schould be go to go. Good luck
  3. Replies
    3
    Views
    2,145

    Do you know for sure that the systems were...

    Do you know for sure that the systems were properly air balanced and the vvt dampers/bypass set up correctly?This system must be balanced as a constant volume system to detemine the static setpoint....
  4. Thread: magnahelic

    by airdata870
    Replies
    8
    Views
    606

    If you had all the right readings it should work....

    If you had all the right readings it should work. Could explain in detail what you did, with #'s and i will tell you what is wrong.we need details. thanks
  5. Replies
    6
    Views
    1,270

    we use this product.it work good

    we use this product.it work good
  6. Replies
    24
    Views
    4,839

    HI siemenstech29.i also am a tab tech,could i get...

    HI siemenstech29.i also am a tab tech,could i get a coy of the manual,it would be nice to set up the balancer tool properly. thanks.
  7. Replies
    6
    Views
    1,110

    You might try the local Mammoth rep, our rep can...

    You might try the local Mammoth rep, our rep can log-on their website and download the info and e-mail it to me.Why they don't let everyone access the info is beyond me.Good luck
  8. Replies
    5
    Views
    806

    When i start-up trane negitive valves i use Dwyer...

    When i start-up trane negitive valves i use Dwyer magnehelic -.25 to +.25 range, works great. good luck
  9. Thread: Intellipac

    by airdata870
    Replies
    12
    Views
    984

    1.5" should be the highest setting used??

    1.5" should be the highest setting used??
  10. Replies
    200
    Views
    12,671

    Would you care to speak more about this? i have...

    Would you care to speak more about this? i have not heard of this being a issue. thanks.
  11. A Dedication to the clueless control company

    Yes your job is important and required to complete the jobs but...PLEASE PLEASE functiun check each piece of equipment, you can dump programs into a controller just because it supposedly will work...
  12. Replies
    17
    Views
    5,601

    2.3 was made for the spyder controllers,but will...

    2.3 was made for the spyder controllers,but will work on exel 10 controllers, the only difference that i can tell, is that you can change duct size and input k-factors. no valve override,that would...
  13. Replies
    10
    Views
    985

    you hit it right on the head.

    you hit it right on the head.
  14. Replies
    17
    Views
    5,601

    I have RapidBalance 1.0 and 2.3 niether supports...

    I have RapidBalance 1.0 and 2.3 niether supports the usb adaptor,that is my # 1 complaint.Why it wasn't addressed with the new version is beyond me. good luck
  15. Replies
    5
    Views
    1,068

    I have two valve core removers and i have never...

    I have two valve core removers and i have never had a problem with mine, and if i don't have to go back to a job i don't think price is a issue. good luck
  16. Thread: Twisting

    by airdata870
    Replies
    21
    Views
    3,017

    unbelievable!!!!!!!!

    unbelievable!!!!!!!!
  17. Replies
    24
    Views
    4,226

    Just curious is flex duct outside accepted by...

    Just curious is flex duct outside accepted by code where you at?
  18. Replies
    3
    Views
    1,306

    The two tubes should be for the flow sensor.

    The two tubes should be for the flow sensor.
  19. you better change the tittle from this, Controls...

    you better change the tittle from this,
    Controls Discussions about HVAC controls in general, including automation, DDC and pneumatics.:D
  20. Replies
    16
    Views
    2,389

    hey superfittertech, who manufactures the scr...

    hey superfittertech, who manufactures the scr controllers for the nailer boxes?
  21. Replies
    16
    Views
    2,389

    superfittertech, could you explain the...

    superfittertech, could you explain the diference,the kb uses a triac to adjust voltage. my uderstanding of the overheating comes from slowing the motor down to far.
  22. Replies
    16
    Views
    2,389

    hey j-fish, here is a data sheet on the ones we...

    hey j-fish, here is a data sheet on the ones we use.You can get them at johnstone supply.http://www.johnstonesupply.com/corp/OnlineCatalog/ProductDetails/tabid/1780/Default.aspx?Product_Code=G32-399...
  23. Replies
    15
    Views
    897

    hey sigma, I've been using vista for about 9 mo....

    hey sigma, I've been using vista for about 9 mo. now, i don't see much difference from XP. I agree with the others you should be able to right click on picture, to save as,then you should get your...
  24. Replies
    16
    Views
    2,389

    what brand box do you have? got a model # you...

    what brand box do you have? got a model # you can get speed controllers at most hvac/electrical wholesale houses.
  25. Replies
    8
    Views
    3,619

    Fan law #1 CFM old/CFM new x PD old = PD new...

    Fan law #1 CFM old/CFM new x PD old = PD new
    22000/17000=1.294 x 14= 18.11"
    hope you remembered a new belt :) good luck