Search:

Type: Posts; User: sodd81927

Page 1 of 8 1 2 3 4

Search: Search took 0.02 seconds.

  1. Replies
    64
    Views
    3,409

    Do you ever go to the bank? Bank robbers do ,...

    Do you ever go to the bank? Bank robbers do , ever go out to eat? Resturants are robbed to, people are robbed, shot and terroized daily in the best of neighborhoods and towns. You should read the...
  2. Replies
    16
    Views
    1,167

    a broken suction reed will only decrease pumping...

    a broken suction reed will only decrease pumping capacity it will not cause leak back unless it damages discharge valve.
  3. Replies
    9
    Views
    866

    Just a quick note If you have a unit that eat's a...

    Just a quick note If you have a unit that eat's a lot of cap's increase the voltage rating ,ie from 370 to 440. I had a customer with a trailer park and 40 rheem 2 1/2 ton heat pumps I was going 3 to...
  4. Replies
    64
    Views
    3,409

    If I worked in Sevierville that would be great...

    If I worked in Sevierville that would be great But I travel all over east TN KY VA and GA and sometimes at night. One of the rep's for a customer asked if I was a good shot, I told him If I shoot at...
  5. Replies
    16
    Views
    1,167

    I just reread your post If this is mp39 your head...

    I just reread your post If this is mp39 your head pressure is way too high at 205 psi find that problem first someone may have mixed gas or you could have air in system.
  6. Replies
    16
    Views
    1,167

    Mp39 low temp? this does not sound right. Check ...

    Mp39 low temp? this does not sound right. Check your liquid filters and suction temp if your superheat is to high at the compressor your problem will haunt you forever.If you have proper superheat...
  7. Replies
    64
    Views
    3,409

    Kimber Ultra Carry .45 inside waistband custom...

    Kimber Ultra Carry .45 inside waistband custom holster fits like a glove never leave home with out it. First rule of gunfight have a gun. better to have it and not need it than to need it and not...
  8. Replies
    6
    Views
    699

    When in doubt I look for the condensing unit tag...

    When in doubt I look for the condensing unit tag to determine what it was designed for then look at TXV, pull whatever is in unit change drier and recharge. I have repaired a lot of problem cases...
  9. Replies
    62
    Views
    5,390

    PREACH IT and while your at it kiddies give real...

    PREACH IT and while your at it kiddies give real numbers for head preasure, suction preasure, temps,voltage and amp's because none of my instruments have [a little low,a little high, ok or seems...
  10. I use them a lot but did not know till I wired...

    I use them a lot but did not know till I wired one in the shop to find out. they start over each time so you cannot use as cumulitive timer but you can use the mechanical timers used for domestic...
  11. Replies
    42
    Views
    9,809

    The latetest from copeland Max superheat is...

    The latetest from copeland Max superheat is whatever it takes to keep your discharge temp below 225 deg. f . I do market rack service and I like to see suction header temp no higher than 40 deg low...
  12. Replies
    17
    Views
    2,243

    Check your amp draw with both and stay under...

    Check your amp draw with both and stay under normal run load amp's. If the smaller will do the job use it. One to large will cause the windings to overheat.
  13. Replies
    14
    Views
    6,178

    I have used the LA-CO heat stick on evap's and...

    I have used the LA-CO heat stick on evap's and steel condensers works very well never had any problems with it. Another great product for aluninum evaporators is a heat cure epoxy that turns from red...
  14. Replies
    190
    Views
    7,015

    Blues brothers?

    Blues brothers?
  15. Thread: S series

    by sodd81927
    Replies
    12
    Views
    872

    This may be obvious but have you checked to be...

    This may be obvious but have you checked to be shure the machine is level all around. I have had a lot of calls on cubers that were not level.
  16. Replies
    34
    Views
    3,083

    Having all the right tools $20,000 + ...

    Having all the right tools $20,000 + Knowing how to use them Priceless
  17. Replies
    10
    Views
    1,765

    Have this often on Hussman wide island coffin...

    Have this often on Hussman wide island coffin cases and have had three omz hill coils in past 4 years.
  18. Replies
    1
    Views
    529

    I do market refrigeration in Knoxville. Just...

    I do market refrigeration in Knoxville. Just about all the HVAC Co's in the area are begging for good tech's My email is in my profile contact me with more info and I can give you some leads.
  19. Don't do it MP39 will fractionate because of the...

    Don't do it MP39 will fractionate because of the variable speed in auto unit's and can build head presure so fast as to blow the hoses off or grenade the compressor. I have witnessed this first hand,...
  20. Replies
    7
    Views
    1,029

    One of my FORMER employes always said "When in...

    One of my FORMER employes always said "When in doubt jump it out" LOL .
  21. Replies
    38
    Views
    1,666

    Before we bought all new Shivalay vans we had...

    Before we bought all new Shivalay vans we had 6cyl E350's , one of my guys asked one morning when we were getting new trucks because he was tired of scraping bugs off of back windows I asked why he...
  22. Thread: p-traps

    by sodd81927
    Replies
    19
    Views
    1,212

    Look first at maybe to much defrost or not enough...

    Look first at maybe to much defrost or not enough fan delay, door being left open long periods, no curtains, refrigeration not being stoped when door is open. Check all these more common isues first...
  23. Replies
    18
    Views
    1,926

    Hundred years ago when I did underground service...

    Hundred years ago when I did underground service installs I heated and bent PVC by heating it with my truck exaust. NOT the best way to go but it worked till I could buy an electric bender.
  24. Replies
    34
    Views
    3,083

    I could not imagine trying to work on supermarket...

    I could not imagine trying to work on supermarket racks without at least 3 set's of guages that's what I carry plus another 4 single high side and 3 low side gauge's and no less than three meters and...
  25. Replies
    11
    Views
    1,737

    Copeland compressor stators are a shrink fit...

    Copeland compressor stators are a shrink fit without the proper puller to remove them you will damage the body. The body has to be heated to reinstall some motor shops may be able to pull them for...