Search:

Type: Posts; User: CerealKiller

Page 1 of 4 1 2 3 4

Search: Search took 0.01 seconds.

  1. Replies
    4
    Views
    239

    The expansion module is discovering (as a device)...

    The expansion module is discovering (as a device) using the Maxline driver, so I'd assume its P1 communication?
  2. Replies
    4
    Views
    239

    OK. Was given WCIS 2.1.1 which doesn't have the...

    OK. Was given WCIS 2.1.1 which doesn't have the terminal emulation. Does anyone have a newer version?
  3. Replies
    4
    Views
    239

    Siemens TEC Expansion Modules

    Pulling in Siemens into Ax

    Have some MAUs that are using app 2497 with expansion module PXM-AI8. I see the points mapping for the 2497 (DOs and DIs), but haven't figured out how to pull sensor...
  4. Replies
    1
    Views
    167

    Nevermind. Finally found owner's manual which...

    Nevermind. Finally found owner's manual which gives me enough info.
  5. Can you upload/download the controller? Also,...

    Can you upload/download the controller? Also, make sure the xml path points to the correct location, (i.e. lonHoneywellAxWizard.lmnl )
  6. Replies
    1
    Views
    167

    Siemens TEC Application Notes

    Pulling in TECs into Ax with the Maxline driver and trying to get docs. Have application notes for everything but 2273 & 2274.

    Customer appears to have a 2273 HP app for a 2 stg DX, 2 stg elec...
  7. Replies
    7
    Views
    674

    Ah! Thanks! Boxed myself into the thought of...

    Ah! Thanks! Boxed myself into the thought of needing an "action" to manipulate it.
  8. Replies
    7
    Views
    674

    No, there are earliest start time and earliest...

    No, there are earliest start time and earliest stop time settings within the (VykonPro) OSS block that use AbsTime. Trying to figure out how to expose them.
  9. Replies
    9
    Views
    594

    Have you verified the configuration in the...

    Have you verified the configuration in the router? I'd would also try connecting to it locally at the JACE with a good patch cord and see if it comes online......would verify your Ethernet...
  10. Replies
    7
    Views
    674

    Tridium Custom Programs

    Was trying to find a way to write AbsTime into the OSS blocks for start & stop times to expose on graphic. Haven't seen a way yet, but I know there is a RelTime command block in the VykonPro module....
  11. Replies
    7
    Views
    510

    Seems that the weather.jars work for a while,...

    Seems that the weather.jars work for a while, then just crap out. We have had some 3.4.43 stations constantly re-boot because of an issue with this jar. There are alternatives. I believe google...
  12. Replies
    10
    Views
    707

    Thanks smmedlin! Found our TUNCOS logic and...

    Thanks smmedlin!

    Found our TUNCOS logic and NDIO point polling eating it up. Also, set the Non-Critical Flag for the runtime extensions.
  13. Replies
    10
    Views
    707

    E Series JACEs

    Seems to me that Honeywell's genius idea to eliminate the need of batteries is to have the unit constantly process data recovery and hog up resources. These JACEs are slow, slow, slow....

    Is...
  14. Gotta love DIY'ers......first off, JACE needs to...

    Gotta love DIY'ers......first off, JACE needs to be licensed for "LCDProgrammable". Is he able to access that palette and set-up comms?
  15. Replies
    26
    Views
    3,993

    I discovered as a dynamic device and converted...

    I discovered as a dynamic device and converted the XIF file from the lonmark site to lnml. Program IDs matched. Wouldn't commission in AX though, but was able to config online and bring it...
  16. Replies
    26
    Views
    3,993

    Digging up an old thread......but having similar...

    Digging up an old thread......but having similar problems here with the LCI-R card.

    I too noticed nciOAMinPos coming in as SNVT_temp_p, instead of SNVT_lev_percent. I also do not see any change...
  17. Replies
    5
    Views
    588

    The points are selected for view. I have several...

    The points are selected for view. I have several conditions that must be true before I enable a fan, yet I always have one or two of them giving me a -1 value instead of a 0.
  18. Replies
    5
    Views
    588

    I referenced Vern's Level II Webs class booklet. ...

    I referenced Vern's Level II Webs class booklet. He mentioned that in an XL10 controller, you have to write a non-zero value to each of the data fields for the point to actually turn on. Not true...
  19. Replies
    5
    Views
    588

    Sharing binary status on Spyders

    Hoping someone can help me out here...

    I created nvo and nvi by using NV Config view in the Spyder (set to SNVT_switch). I exposed the state on the wiresheet and linked my logic. Generated NVs. ...
  20. OK. Created a nvo (temp p)and linked it directly...

    OK. Created a nvo (temp p)and linked it directly to the physical point. Created a nvi (temp p) and lon linked like mentioned above on the lon network wiresheet. Link worked.

    I do not see...
  21. I did the conversion and it took care of the...

    I did the conversion and it took care of the error. I have a nvoOATemp point in the points list, but it still does not show up when I go to do the lon binding on the lon network wiresheet.
  22. Spyder Programming Help - OAT Sharing

    For the life of me, I can't get the process down on how to do this. Any help would be appreciated.

    I have an OA Temp Sensor on UI1. I generated NVs, then went to Lon Point Manager. Located UI1...
  23. Replies
    5
    Views
    490

    Thanks for clarifying that Sam. I know Echelon...

    Thanks for clarifying that Sam. I know Echelon recommends that on their network, but really didn't occur to me about doing the same for DIs.

    Our vendor recommended Citel DLA.
  24. Replies
    5
    Views
    490

    Thanks for the replies. Will try wiring the...

    Thanks for the replies.

    Will try wiring the closer buildings direct and go with the relay solution on the farthest.

    Osiyo, thanks for the controller operation explanation.
  25. Replies
    5
    Views
    490

    DI line length

    I have a medium sized facilty with three storage buildings. Two of them are roughly 250' away and the other is about 500' away. All I have to do in those three buildings is to monitor the status of...
Results 1 to 25 of 85