Search:

Type: Posts; User: hueyman

Page 1 of 2 1 2

Search: Search took 0.01 seconds.

  1. Replies
    9
    Views
    825

    Disconnected jace from bus and connected laptop....

    Disconnected jace from bus and connected laptop. No go. Then I searched my history on this site and realized I asked this question back in 2007. Digo answered it. Well, I'm retiring in three weeks so...
  2. Replies
    9
    Views
    825

    Features match but the OAT is wired to one of the...

    Features match but the OAT is wired to one of the points on the NDIO board in the FX40.
    I could temp. override the point in the FX16 if system will run off laptop but, again, just looking for...
  3. Replies
    9
    Views
    825

    What should i be looking for in the licence...

    What should i be looking for in the licence manager?
  4. Replies
    9
    Views
    825

    Cagey, I have a station copy and a...

    Cagey,

    I have a station copy and a dist backup file. Not looking to upgrade as the property won't approve a fix if it's not completely broken. The FX40 controls the central plant, AHUs,...
  5. Replies
    9
    Views
    825

    Thanks Reaper. I will give it a try.

    Thanks Reaper. I will give it a try.
  6. Replies
    9
    Views
    825

    FX40/Workbench Question

    I have a copy of our latest FX40 B/U on my laptop. If I connect laptop to N2 bus
    and disconnect FX40 from N2 bus, can the laptop control the system as local station
    in workbench? May be a dumb...
  7. Replies
    8
    Views
    2,660

    Thanks Chris. I think I'll post a bit more before...

    Thanks Chris. I think I'll post a bit more before signing up.
  8. Replies
    8
    Views
    2,660

    Trane chiller controls

    We had two CVHB 2 stage units that we retrofitted with electronic UCP controls. With the UCP upgrade came with electronic vane actuators and bypass actuators to replace the pnuematics. I belive they...
  9. Replies
    15
    Views
    2,036

    When our BAS was upgraded to an FX40 with FX...

    When our BAS was upgraded to an FX40 with FX controllers and UNTs we had to retain our ancient Honeywell Delta system for fire monitoring/alarm because the new system was not UL rated. We are in the...
  10. Replies
    9
    Views
    914

    Thanks. Changing the profile to default did the...

    Thanks. Changing the profile to default did the trick when accessing with a web browser. What I also noticed when I had access to workbench and a saved station is I couldn't see the point slot view...
  11. Replies
    9
    Views
    914

    tried the modified address but it goes to "cannot...

    tried the modified address but it goes to "cannot display page".
  12. Replies
    9
    Views
    914

    Yes it is embedded workbench accessible via web...

    Yes it is embedded workbench accessible via web browser. I have done logic programming with it using some of the kitcontrol modules. I am setup as role=administrator and permissions=superuser. This...
  13. Replies
    9
    Views
    914

    Accessing with web browser. Is the slot view only...

    Accessing with web browser. Is the slot view only accessible with WB or WB PRO?
  14. Replies
    9
    Views
    914

    FX40 points - slot view

    I would like to hide some of the options in the Action pull down of a writable point. Previous posts indicate it is done by modifying the action items in the point slot sheet. How do you access the...
  15. Replies
    5
    Views
    717

    It's a fairly large, complicated dist program for...

    It's a fairly large, complicated dist program for a CP with 3 FXcontrollers. I'm trying to simulate what effect input changes in one assembly will have on the final output of 4 or 5 linked assemblys....
  16. Replies
    5
    Views
    717

    Guess I can keep the session open on my spare PC...

    Guess I can keep the session open on my spare PC until I'm completely done with the simulator. I get a lot of interruptions and sometimes have to close it up and start all over the next day. :nopity:...
  17. Replies
    5
    Views
    717

    FX Builder simulator question.

    Is there a way to save a simulator file and load it back into the simulator at a later session? It's a lot of work to setu the parameters for a simulator session every time you close/reopen FX...
  18. Thread: fx40 email

    by hueyman
    Replies
    19
    Views
    2,326

    #1servicetech, what email service do you use that...

    #1servicetech, what email service do you use that does not require smtp ssl?
    I can't find one. I've got 4 email accounts and all require ssl connections.

    Thanks
  19. Thread: fx40 email

    by hueyman
    Replies
    19
    Views
    2,326

    This capture is off of my laptop using local...

    This capture is off of my laptop using local platform as I won't have access to the jace until I'm back to work monday. I set it up as it reads on the jace.
  20. Thread: fx40 email

    by hueyman
    Replies
    19
    Views
    2,326

    Checked the tcp/ip settings in the platform and...

    Checked the tcp/ip settings in the platform and there was no dns assigned. Added dns address using same as gateway and added hostname "gateway.2wire.net". This is the same setup used in the...
  21. Thread: fx40 email

    by hueyman
    Replies
    19
    Views
    2,326

    I had an email address in the reply to box and...

    I had an email address in the reply to box and tried a couple different addresses. The authentication has a check mark in the box. Still getting the same error. I'm confused on the dns and gateway...
  22. Thread: fx40 email

    by hueyman
    Replies
    19
    Views
    2,326

    fx40 email

    While trying to setup the outgoing account for email alarms I've not been able to get the email sent. I am using mail server (host) "smtp.att.yahoo.com" and have my account name and password in the...
  23. Replies
    1
    Views
    519

    Exact error message is "error sychronising file"...

    Exact error message is "error sychronising file" . Anyone?

    Thx,
    Mike
  24. Replies
    1
    Views
    519

    Fx16 upload error

    Uploading an APD from an FX16 to laptop using FX Commpro N2. At the very end of the upload (100%) I receive a synchronization error message. The file seems to download intact and I can open it in FX...
  25. Thread: JCI UNT

    by hueyman
    Replies
    7
    Views
    720

    Thanks all. Just wanted to confirm before I start...

    Thanks all. Just wanted to confirm before I start the grunt work.
  26. Thread: JCI UNT

    by hueyman
    Replies
    7
    Views
    720

    Not using a custom application. Just need to land...

    Not using a custom application. Just need to land another temp sensor on the closest UNT to get the sensor reading on the network (N2 and FX40). Thought maybe there was a different way to feed one of...
  27. Thread: JCI UNT

    by hueyman
    Replies
    7
    Views
    720

    JCI UNT

    Working with 1144 UNT. Spec sheet indicates six AIs available. There are six AI terminal blocks and six switches on the two dip switch blocks. Four of the AIs are wired to sensors and the other two...
  28. Replies
    17
    Views
    1,943

    thanks CCIKelly. I'll pass this on to our vendor.

    thanks CCIKelly. I'll pass this on to our vendor.
  29. Replies
    17
    Views
    1,943

    Anyone know where I can find additional info on...

    Anyone know where I can find additional info on this recall? We have 25 UNT1144 just installed last year and the third one just started dropping in/out of scan.

    Thanks
  30. Replies
    17
    Views
    1,943

    anymore info on this UNT recall?

    anymore info on this UNT recall?
  31. Replies
    10
    Views
    1,280

    Trend data stored in default directory...

    Trend data stored in default directory c:\unity\ui\ims . Should be one file for each day. You can transfer the files to another media using OS2 or dos commands or just delete some of the older...
  32. Replies
    10
    Views
    1,280

    The Unity operates under IBM OS2. I'll check the...

    The Unity operates under IBM OS2. I'll check the directories on our system sunday and let you know the exact default location of the trend files. I believe these can be diverted to another storage...
  33. Replies
    7
    Views
    1,238

    Thanks, ddcfreek. Now that you mention it, I...

    Thanks, ddcfreek. Now that you mention it, I noticed the manual refers to commissioning in the LON section only. I can add boolean points to replace the enums but thats a lot of rework at 30 to 40...
  34. Replies
    7
    Views
    1,238

    FX Workbench Question

    After creating a new local station on workbench I create a new N2 device and use an APD file for the resource file. The points are created for the device but they are all numeric or enum points. Some...
  35. Thread: Pneumatic

    by hueyman
    Replies
    21
    Views
    1,746

    If i understand correctly, both valve actuators...

    If i understand correctly, both valve actuators are pneumatic. One controlled by transducer and one controlled by pnematic stat. Cheapest way would probably be to feed 2 seperate pneumatic...
  36. Thread: Pneumatic

    by hueyman
    Replies
    21
    Views
    1,746

    We used Honeywell pneumatics for years for...

    We used Honeywell pneumatics for years for controlling actuators. There are all kinds of inexpensive pneumatic relays, reversers, lockouts, selectors etc... that we used to stage sequences from one...
  37. Replies
    10
    Views
    785

    Thanks guys. I deleted a lot of lines from the...

    Thanks guys. I deleted a lot of lines from the users Nav file and the navigation is now restricted to graphic pages/points only. :) I tried working with the categories per ddcfreak and made a mess....
  38. Replies
    10
    Views
    785

    Yes I am accessing an fx40 via internet explorer...

    Yes I am accessing an fx40 via internet explorer on a network connection. Using the basic wb web profile does eliminate the side bar but the menu bar still has a pulldown on the left side to enable...
  39. Replies
    10
    Views
    785

    Anyone:confused: TIA

    Anyone:confused:

    TIA
  40. Replies
    10
    Views
    785

    Ok, got the user set to basic wb web profile and...

    Ok, got the user set to basic wb web profile and am still able to get to all the device points by the menu bar navigation pull down on the left. I can expand a device and click on points to get the...
  41. Replies
    10
    Views
    785

    When I set user profile to basic wb web the only...

    When I set user profile to basic wb web the only difference i notice is the home screen brings up an error message with no graphic. All other functions including the menu bar is still present and...
  42. Replies
    10
    Views
    785

    FX40/workbench navigation

    I'm trying to modify user access so that only points on graphic screens can be accessed. The point detail manager and point extension manager would not be available as a pull down option. I have...
  43. Thread: Integration

    by hueyman
    Replies
    12
    Views
    1,037

    Problem we had trying to integrate our old...

    Problem we had trying to integrate our old fire/security system with the new bas was the new system was not UL approved. Insurance wouldn't cover the building without a UL approved fire system.
  44. Replies
    0
    Views
    384

    FX40 N2 device commisioning

    FX40 supervising Fx16,Fx15,UNT's and Fx07's. When adding another UNT or FX07 to the system do you need to run commisioning in HVACPRO (UNT) and WorkBench (FX devices) to get them to respond to...
  45. Thread: FX40/UNT help

    by hueyman
    Replies
    11
    Views
    863

    Ok to close the thread, the % of heat numeric...

    Ok to close the thread, the % of heat numeric writable point could switch the heat on/off by overriding but the % would never change on its own. The tech made some adjustments to the heating d-band...
  46. Thread: FX40/UNT help

    by hueyman
    Replies
    11
    Views
    863

    When I previously looked at the FX40 points for...

    When I previously looked at the FX40 points for the AHUs, I did not see a percent of heating point. The only point related to the heat was the booleen BO3 point which in named HTG-C. It is either...
  47. Thread: FX40/UNT help

    by hueyman
    Replies
    11
    Views
    863

    Ninax, the jumper configurations are good....

    Ninax, the jumper configurations are good. feeding 24V to the src common an using the no output to energize heating relay. I deleted the booleen writable and left the booleen point mapped to BO3....
  48. Thread: FX40/UNT help

    by hueyman
    Replies
    11
    Views
    863

    Ninax, when I attempted to force heating on/off...

    Ninax, when I attempted to force heating on/off with the existing boolean writable the output to BO3 changes state but the UNT does not. I thought it might be because the UNT is looking for a numeric...
  49. Thread: FX40/UNT help

    by hueyman
    Replies
    11
    Views
    863

    minimum on/off times are set to .5 and cycles per...

    minimum on/off times are set to .5 and cycles per hr. at 30.
  50. Thread: FX40/UNT help

    by hueyman
    Replies
    11
    Views
    863

    FX40/UNT help

    We have multiple fan coil units controlled by JCI UNT1144 controllers. The UNTs were programmed with HVACPRO as single path RAT reset with the heat controlled by RAT. BO1 is for supply fan, BO2 for...
Results 1 to 50 of 61
Page 1 of 2 1 2