Search:

Type: Posts; User: krac

Page 1 of 8 1 2 3 4

Search: Search took 0.01 seconds.

  1. Thread: Andover CX 9400

    by krac
    Replies
    6
    Views
    334

    Its been a while since I have used a terminal...

    Its been a while since I have used a terminal connection to a CX controller, (Thank God!) but if you can get connected (you will need login/PW) turn on your terminal program text capture and issue a...
  2. Replies
    3
    Views
    250

    The LGR1000 has three networks, local, 2401 which...

    The LGR1000 has three networks, local, 2401 which has bacnet devices, and 2402 which is connecting to the DataGuard network. Not sure how the WebCTRL Server connects to the LGR1000 but all I see is...
  3. Replies
    3
    Views
    250

    ALC LGR1000 Bacnet IP to Jace

    One of our customers recently took over a site that has what looks like an up to date WebCtrl server accessing a network of what looks like CMNet and Bacnet MSTP/Arcnet devices. Looking at the...
  4. Replies
    6
    Views
    471

    That is the standard Tridium power supply that...

    That is the standard Tridium power supply that depending who you purchase from costs over $110 which makes it one of the most expensive power supplies on the market for any application.
    For this...
  5. Thread: Jace Alternative

    by krac
    Replies
    8
    Views
    473

    If the existing controls are Bacnet MSTP checkout...

    If the existing controls are Bacnet MSTP checkout the Easy I/O FG-20. HTML-5, MSTP/Modbus support and should cost you around Pricing Removed From Post
  6. Replies
    6
    Views
    471

    Jace power supply options

    Working on a Data Center project that we need to mount the Jace 7 controllers in a 2 post equipment rack and need to find a 208vac to 15vdc power supply that will be installed in a UL listed panel. ...
  7. Thread: Niagara Summit

    by krac
    Replies
    22
    Views
    1,798

    The security outside the sessions was amusing....

    The security outside the sessions was amusing. Wonder how many other venders were trying to sneak into the sessions. I know I am losing sleep over the release of Niagara 4.01, even if it is 2 years...
  8. Replies
    16
    Views
    873

    The Fluke 125 S is a dual channel 40 mHz scope...

    The Fluke 125 S is a dual channel 40 mHz scope with a comm diagnostic function that made troubleshooting RS-485 networks for dummies like me real simple. Only problem is the price of $3000. The...
  9. Replies
    16
    Views
    873

    Rented a Fluke 125S which has a built-in function...

    Rented a Fluke 125S which has a built-in function for testing RS-485 and other serial types. The 125S quickly showed us the bacnet MS/TP bus had issues and allowed us to visual see the results of...
  10. Replies
    16
    Views
    1,305

    We are able to write values to AO/DO points and I...

    We are able to write values to AO/DO points and I think we can actually override them but have not tested that yet. Yes, the gateway needs a device address between 1 and 30, and the baud is 9600.
  11. Replies
    16
    Views
    1,305

    We are using the Maxline driver with the Easy I/O...

    We are using the Maxline driver with the Easy I/O gateway that is actually one of the Easy I/O FG-20 controllers that we had download the gateway firmware into. The Driver/gateway discovered all the...
  12. Replies
    16
    Views
    1,305

    We are in the process of moving a C-Bus network...

    We are in the process of moving a C-Bus network over to Tridium using a gateway and driver. Tested the gateway way out a few weeks ago and we were able to discover all the C-Bus devices and points. ...
  13. Replies
    12
    Views
    1,170

    I built Numeric bits writable as Hex address of...

    I built Numeric bits writable as Hex address of 10 with Numeric bits beginning bit 8 and number of bits 8.

    Since you are using Hex 10 is actual 0A, but figure you already have that covered.
  14. Replies
    8
    Views
    628

    We have a Fuji portable ultrasonic meter we use...

    We have a Fuji portable ultrasonic meter we use for flow testing. There is a company that sells a made in China ultrasonic meter that looked interesting: ...
  15. Replies
    12
    Views
    1,170

    This is a little different then most...

    This is a little different then most implementations but not that bad. You need to use Numeric bit point for the analog values (two for each address) with bits 0-7 for the low byte value and 8-15...
  16. I have played with the Notifier web interface and...

    I have played with the Notifier web interface and don't see anyway to edit or add a Bacnet device instance. When the gateway is restarted in goes through a discovery process (I captured the...
  17. Having the same problem with a Tridium to...

    Having the same problem with a Tridium to Notifier integration today. I can discover Gateway device, but the point discovery only shows enum (multi-state inputs) for the panel and a & b networks....
  18. Replies
    5
    Views
    616

    Wow reading this thread about Adaptive...

    Wow reading this thread about Adaptive Intelligent Recovery and figured I might learn something new, only to see an AC256 Drum program used as an example! Had to read it a couple of times just to...
  19. Great question!

    Great question!
  20. Thread: LON Null value

    by krac
    Replies
    2
    Views
    366

    The ENE Workplace Tech program in the MZ treats...

    The ENE Workplace Tech program in the MZ treats any value other than 1 as off. Just figured out that I can enter a value as sci notation. Entered 2e+038 as 2E38 in the slot and override is...
  21. Thread: LON Null value

    by krac
    Replies
    2
    Views
    366

    LON Null value

    Finishing up our ENE Lon to Tridium upgrade, and found some nVI points SNVT_count_inc_f (Type 52) that you can use to manual override equipment on off or auto. Problem is on=1, 0=off, and auto in...
  22. Replies
    21
    Views
    6,133

    We used the Maxline ASD driver on a recent...

    We used the Maxline ASD driver on a recent project with good results. The driver supports serial tunneling but haven't been able to make a reliable connection. I think the problem is with XPSI which...
  23. Replies
    43
    Views
    3,055

    For the JCI integration we used an FX-60 because...

    For the JCI integration we used an FX-60 because we know the N2 driver is solid. Found several VMA's offline and needed to troubleshoot an N2 bus wiring issue. For the ALC we left the Langate in...
  24. Replies
    43
    Views
    3,055

    Finally over the Invensys LON learning curve (at...

    Finally over the Invensys LON learning curve (at least I hope so) Found copies of all the Workplace Tech project files which allowed us to get a handle on what is going on inside the MZ's. Discovered...
  25. Replies
    43
    Views
    3,055

    Looks like the Node Utility program only works...

    Looks like the Node Utility program only works directly connected to the local lon bus. Is there an export function that is part of LonMaker running on the server?

    One issue I am having is not...
Results 1 to 25 of 198