Search:

Type: Posts; User: curlydogmaster

Page 1 of 2 1 2

Search: Search took 0.00 seconds.

  1. Replies
    5
    Views
    1,994

    My local Trane Parts Center got this one for me a...

    My local Trane Parts Center got this one for me a while back...
    It's not much but I hope it helps!
  2. Replies
    3
    Views
    1,220

    I can't believe this post has had over 120 reads...

    I can't believe this post has had over 120 reads and no one has more to offer but thanks to all who have taken the time to read.

    As I stated, Carrier rebuilt the slide valve about 4 years/10,000...
  3. Replies
    3
    Views
    1,220

    23XL Slide Valve Seals

    Hello All,
    We have a 23XL that is a back up machine so it sits sometime for months. Back in the summer wouldn't unload one night but that cleared up the next morning. It ran well for a month or so...
  4. Replies
    21
    Views
    4,261

    Wrap-Up: The the burned trigger had no output...

    Wrap-Up:
    The the burned trigger had no output
    The SCR's ohm'ed good so I ordered a new trigger board.
    Installed it today and the machine purrs like a kitten.


    Thanks again to all!
  5. Replies
    21
    Views
    4,261

    Before I started on the troubleshooting the L3...

    Before I started on the troubleshooting the L3 upper trigger section caught my eye (2nd from the right) in the wide photo.
    The other two photos are closeups of the L3 lower and upper trigger...
  6. Replies
    21
    Views
    4,261

    Yea, thought about that. No motor attached gets...

    Yea, thought about that.
    No motor attached gets me nothing.
    Hopefully something will show its self tomorrow but I wish I had a more clearcut proceedure for testing the SCR's and the trigger...
  7. Replies
    21
    Views
    4,261

    The motor megged at 2M @ 1000v so I can't blame...

    The motor megged at 2M @ 1000v so I can't blame the motor.
    I spent some time checking the starter for grounds, shorts, etc until I called the tech from Seimens as I was driving.
    He informed me that...
  8. Replies
    21
    Views
    4,261

    I'm not gonna try ATL...the building would...

    I'm not gonna try ATL...the building would brobably shake apart from the 3000 amp in-rush.
    I did disconnect the motor leads and I've got 480v line-to-line and 277v line-to-ground on the output of...
  9. Replies
    21
    Views
    4,261

    Water cooled. m/n: SSS14L-46A s/n: EHR-14B...

    Water cooled.
    m/n: SSS14L-46A
    s/n: EHR-14B
    p/n: 371-01210D007

    I does have a communications port.
    I'll talk to Seimens about identifying which phase but they couldn't even tell me it it was...
  10. Replies
    21
    Views
    4,261

    No loose parts or broken parts in the sss. No...

    No loose parts or broken parts in the sss.
    No burns or smokey places either.

    I did attempt to start it with out the coupling.
    It made it's signature "buzz" for like 1/4 of a second and tripped...
  11. Replies
    21
    Views
    4,261

    York YS Chiller Ground Fault

    I have a 265hp York YS with a solid state starter.

    About 3 weeks ago it tripped the 500amp Seimens GFI breaker back at the MDP but not the 400amp breaker on the front of the machine.
    I...
  12. Replies
    7
    Views
    1,350

    Thanks york56! That's exactly what I was looking...

    Thanks york56!
    That's exactly what I was looking for.
    Thanks to the others for you insight as well.
    This site is awesome!
  13. Replies
    7
    Views
    1,350

    York YS Oil Seepage

    I'm looking for what York states is the permissable rate of oil seal seepage into the catch bottle on a "YS" compressor.
    I once heard it was two of the 1-litre bottles full per year.
    A written...
Results 1 to 13 of 27