Search:

Type: Posts; User: summit-dude

Page 1 of 3 1 2 3

Search: Search took 0.01 seconds.

  1. Replies
    1
    Views
    272

    VoyagerII or voyagerIII?

    VoyagerII or voyagerIII?
  2. Replies
    14
    Views
    1,444

    Don't forget to bind your llids when you restore...

    Don't forget to bind your llids when you restore the config...
  3. Replies
    14
    Views
    1,444

    We're you able to back up the old 530? If you...

    We're you able to back up the old 530? If you were able to you can just dump that config into your new 530. If you didn't you will need to configure the new ch530. Be careful when you do because if...
  4. Replies
    14
    Views
    1,444

    You beat me to the post! I have only had to...

    You beat me to the post! I have only had to replace one CH-530 in my 10 year career at trane! Usually someone leaned on the contrast button...
  5. Replies
    11
    Views
    777

    Scroo is exactly right. If the box is configured...

    Scroo is exactly right. If the box is configured as a varitrane box and you have a pressure transducer installed the box will enter pressure dependent mode if the transducer doesnt read airflow....
  6. Replies
    11
    Views
    777

    One important detail here; the BCU. What kind of...

    One important detail here; the BCU. What kind of BCU do you have. If its a BMTX you can land the cards on either of the comm 4 links. If its a BMTW you will need a comm 4 card to install in one of...
  7. Replies
    2
    Views
    239

    Bandwidth BAC-net IP

    Anyone know of a good freeware bandwith tool I can use to check my IP network?
  8. Replies
    5
    Views
    297

    Maybe the triacs are trashed on the VV-550 check...

    Maybe the triacs are trashed on the VV-550 check those as well... Also make sure the * ** enable box is unchecked. If the minimum is set to 0 and the stat is ran a to ** it will override the damper...
  9. Replies
    6
    Views
    381

    I have. If its the board I just dealt with you...

    I have. If its the board I just dealt with you cant adjust the UCM address on it except through the command module. We ended up having to change the boards to the Comm-4 module that is now supported....
  10. Replies
    9
    Views
    661

    Browse to your VAV and select the status pages....

    Browse to your VAV and select the status pages. on the first page you will see space temperature setpoint BAS. Click on the blue arrow and an override dialog box will show up. If you are in the...
  11. Replies
    15
    Views
    937

    Comm-5 is actually 4500 feet before you need a...

    Comm-5 is actually 4500 feet before you need a repeater, you can add another 4500 feet after that.Comm 4 doesnt support bus topology but for something we dont support when done properly it works...
  12. Replies
    15
    Views
    937

    Looks like you found it! lol. We are also taught...

    Looks like you found it! lol. We are also taught this at the factory we dont support free topology or bus topology only a daisy chain. Our tech support gurus will actually cut you off your backbone...
  13. Replies
    1
    Views
    380

    Run a pid loop to 300% add your next pump at 95%...

    Run a pid loop to 300% add your next pump at 95% then divide the output by the number of pumps requested to keep your pump speed the same. Store your current lead in a local variable and add one to...
  14. Replies
    2
    Views
    206

    Try toggling the occupancy snvt on the chiller...

    Try toggling the occupancy snvt on the chiller that's not starting for you. We typically write to the occupancy command not stop start.
  15. Replies
    3
    Views
    413

    Ok the 11 domain will be DSN A we use a 1 domain...

    Ok the 11 domain will be DSN A we use a 1 domain to install in a Bcu 11 means the link was formatted with Rover if yor domain was 13 the link would have been formatted with a Bcu. All you bindings...
  16. Can't believe you have one of these. Late 90's...

    Can't believe you have one of these. Late 90's the 2/3/4 cards had a problem with the software. After it logged so many comm errors it would start scanning comm 3. The module you have was a very cool...
  17. Replies
    9
    Views
    661

    When a Tracer SC discovers equipment for the...

    When a Tracer SC discovers equipment for the first time it turns the local set point off. Browse to your VAV and look at the status pages, look for space temperature set point BAS. If that point is...
  18. Replies
    9
    Views
    661

    Log in as the user, on the trane toolbar on the...

    Log in as the user, on the trane toolbar on the right select user, preferences, about little more than half way down the page the data field for data display units preferences will allow you to...
  19. Replies
    9
    Views
    1,829

    You shouldn't need this add on to forward event...

    You shouldn't need this add on to forward event classes. When is the last time summit was closed and the database compacted? How large is your database? How many workstations and Bcu's? Sounds almost...
  20. Replies
    15
    Views
    937

    Trane standard: level 4 twisted pair, more than...

    Trane standard: level 4 twisted pair, more than 60 devices requires a repeater near the middle of the device count, 105 ohm resistors on both ends of each segment. Bcu's will not be happy unless this...
  21. Replies
    5
    Views
    1,058

    Sounds like your IT guy needs to do a little work...

    Sounds like your IT guy needs to do a little work and make sure that the bcu ip address isnt being assigned out in a dhcp pool just a thought
  22. Replies
    6
    Views
    903

    Trane has several variables that only apply to...

    Trane has several variables that only apply to the trane profile for an MP-581 used in summit and are not lon certified these are like a multi state point but probably won't mean much to you. You...
  23. Thread: Loetec LIP

    by summit-dude
    Replies
    19
    Views
    1,944

    I have the manuals and their tech support has...

    I have the manuals and their tech support has been no help ready to give up and try another way of doing the integration. Tried the settings as a foreign device no BBMD b/c I already have one on the...
  24. Thread: Loetec LIP

    by summit-dude
    Replies
    19
    Views
    1,944

    ok got firmware updated but it still wont serve...

    ok got firmware updated but it still wont serve up any points, I have no duplicate addresses, Baud rates match any ideas
  25. Replies
    10
    Views
    1,525

    It is a standard ISA card slot 10/100 m card and...

    It is a standard ISA card slot 10/100 m card and just about any card will work as long as it is jumper configurable for 10 meg 1/2 duplex
  26. Thread: Loetec LIP

    by summit-dude
    Replies
    19
    Views
    1,944

    Loetec LIP

    Trying to integrate MS/tp to BAC-net IP through a Loytec LIP. I tried to download new Firmware and the router wont eat the code I'm using a null modem cable is this the correct cable or should I be...
  27. Replies
    4
    Views
    1,054

    Read/write the variables in the program instead...

    Read/write the variables in the program instead of using radio connections this is not what trane recommends but it will keep you from getting tha compile error
  28. Replies
    14
    Views
    1,802

    What kind of comm failure??? I've never seen a...

    What kind of comm failure??? I've never seen a comm failure alarm on an MP that involved the comm link, only a comm failure to an EX module or a display screen I wouldn't go ripping out the comm...
  29. Replies
    11
    Views
    1,541

    Do you have user profiles set up or does everyone...

    Do you have user profiles set up or does everyone sign in using a default username and password??? Find out what priority the overrides are at and insure that you don't have some kinda screwy CPL...
  30. Replies
    3
    Views
    890

    Reconnect the return air temp sensor and check...

    Reconnect the return air temp sensor and check the return humidity sensor and the OA humidity sensor I bet you will find one of them failed. If you find one of them failed you can disconnect the OA...
  31. Replies
    23
    Views
    7,265

    For our stuff I find that using a proportional...

    For our stuff I find that using a proportional bias, a large error dead band and long program execution works best for me. 4* error deadband, conservative gains and 15 second program execution for...
  32. Replies
    7
    Views
    2,151

    M 100 Tech is right this changed a few years ago...

    M 100 Tech is right this changed a few years ago the end user can not contact Tech support direct any more too many people trying to register more than one computer per licensed copy. If you contact...
  33. Thread: Trane BCU

    by summit-dude
    Replies
    20
    Views
    2,708

    I believe that any 10/100 ISA card will work just...

    I believe that any 10/100 ISA card will work just fine with a BMTW power down the BCU install the card hook up to the BCU and connect with summit and the program should dump into the BCU as the...
  34. Replies
    8
    Views
    1,361

    latest and greatest service pack fixes the IE 7...

    latest and greatest service pack fixes the IE 7 problem but don't use google or yahoo toolbar programs it drives summit crazy I have customers using v16 and IE7 with no problems.

    I installed V-17...
  35. Thread: Trane SCC

    by summit-dude
    Replies
    7
    Views
    958

    Don't select it, just click the dropdown arrow on...

    Don't select it, just click the dropdown arrow on the box and set it to not used thats it
  36. Replies
    4
    Views
    518

    Never seen a demo copy of rover and any disc you...

    Never seen a demo copy of rover and any disc you get ur hands on is going to make you register it before it will run. Sorry dude
  37. I have to agree with Willf the programmers don't...

    I have to agree with Willf the programmers don't allways do a good job programming for lon profiles properly. If an SCC or DAC profile is enabled and best practices have been used all you need to use...
  38. Replies
    10
    Views
    1,224

    Don't undestand the whole trac-net and tron stuff...

    Don't undestand the whole trac-net and tron stuff the BCI and UC lines are out and they are awesome we just had our first SC job with BCI-I's and UC 400's go in and it is sweet!!! And yes it is real...
  39. Replies
    7
    Views
    600

    Chiller dude I don't work for a franchise but do...

    Chiller dude I don't work for a franchise but do work for the factory and have tons of expierence in this you can make your own decision on who to believe, point your browser to pacific geek . com...
  40. do have to agree with willf on this the LCI's are...

    do have to agree with willf on this the LCI's are pretty consistant and we have very few problems with them.
  41. Replies
    7
    Views
    708

    I suppose I could have misundestood as well or...

    I suppose I could have misundestood as well or be just plain wron (wouldn't be the first time) but this is the only thing I could find in the LCI-I documentation for any type of heat status.
  42. Replies
    7
    Views
    708

    NVO Heat Cool is the output it is a Multi state...

    NVO Heat Cool is the output it is a Multi state output SNVT_HVAC_MODE index 40 on the LCI-I a value of 0 will be auto 1 will be heat 3 will be cool I hope this helps you and sorry it took so long to...
  43. LCI-I or LCI-R? DAC or SCC?

    LCI-I or LCI-R? DAC or SCC?
  44. Replies
    2
    Views
    1,366

    You need to tell the computer which port to use...

    You need to tell the computer which port to use it is outlined in the help menu in rover as well as the setup documentation you got with the software package If you dont have a hard copy you can...
  45. Replies
    26
    Views
    7,662

    I agree with some of what you are saying and I...

    I agree with some of what you are saying and I can assure you I've never squirmed sitting across the table from a comissioning agent though in fact I have a few that call me about advice on Trane...
  46. Replies
    26
    Views
    7,662

    Sorry dude I must have been drinking the koolaid...

    Sorry dude I must have been drinking the koolaid but this roll out has been in the works for about two years before they actually went to market with the product and R&D and devolopment goes back to...
  47. Replies
    13
    Views
    1,270

    I had a simmilar issue with Rover and Lon-maker...

    I had a simmilar issue with Rover and Lon-maker on my laptop I had to uninstall lon-maker for Rover to work again as they don't play nice with each other I've had no issues with lon maker or ln...
  48. Replies
    7
    Views
    708

    Many of the NVO's that you see are trane nvo's ...

    Many of the NVO's that you see are trane nvo's I'm not familiar with the nvo you are looking for will look through some info and see if I can find you a good point for heat active.
  49. Replies
    26
    Views
    7,662

    it is not like the BCU for lon because it is not...

    it is not like the BCU for lon because it is not a network manager it polls for data the way a lon front end should. it will be fully interoperable for bac-net and lon talk soon and the ease of...
  50. Replies
    13
    Views
    1,270

    How old is the controller Does the device show up...

    How old is the controller Does the device show up with a red ? in the bulb next to the location lable in the nav tree? The blinking red light indicates that the node is un-installed who's front end...
Results 1 to 50 of 129