  1. Not following exactly but it just uses the ohm...

    Not following exactly but it just uses the ohm reading. Writes the converted ohm reading to nvoSpaceTemp as a analog value.
  2. Replies
    9
    Views
    360

    Yes a laptop copy would work. The software needs...

    Yes a laptop copy would work. The software needs to be equal or greater to the site version.
  3. Replies
    9
    Views
    360

    Do you have Tracer Summit yourself or there...

    Do you have Tracer Summit yourself or there locally? The software is provided with that to change the IP. If it is already IP then it is fairly simple to change it. You use the IP Validation...
  4. Yes and Yes while in pcmedit you can select...

    Yes and Yes

    while in pcmedit you can select the input the temp is on and bring up the sensor list and pick the right one and it will auto populate the range and offset
  5. Replies
    1
    Views
    190

    If it is a space control unit then you can not do...

    If it is a space control unit then you can not do SA control like you want without major modification.
  6. You must place these points in service and write...

    You must place these points in service and write to them. Starting with BO1 below
    BO1 System Control Command =Command the unit to standalone- or BAS-controlled operation. Inactive = Standalone...
  7. What version is the BCU running at? Status, Obj...

    What version is the BCU running at? Status, Obj Properties, Device, BCU, Firmware Version
  8. Never seen that before. But that is a pretty old...

    Never seen that before. But that is a pretty old version. V16 is at SP 8. I would try that first, get it up to latest code. This includes gettings the BCU up to latest code also. Just installing...
  9. Replies
    5
    Views
    427

    What is the error code? That would help us give...

    What is the error code? That would help us give suggestions.
  10. Replies
    8
    Views
    439

    There is a free program that allows you to change...

    There is a free program that allows you to change the units from Celsius.

    Then the points can be placed in service through BACnet. Under the point property instead of value there should be a...
  11. Thread: Trane WCIs

    by scrooloose
    Replies
    8
    Views
    695

    Set rotary to zeros. After 7-10 sec the WCI...

    Set rotary to zeros. After 7-10 sec the WCI should blink all lights and do a reset sequence. Power off the WCI and UC at that time. Set your rotary on the UC and WCI to the correct settings. ...
  12. Thank you Cletus_berfed, this document worked...

    Thank you Cletus_berfed, this document worked perfectly.
  13. Thank you, i will try this out tomorrow and see...

    Thank you, i will try this out tomorrow and see what i can read.
  14. Fulton Reliance Boiler Modbus point list

    I am not having any luck on fultons site finding a modbus point list.

    I have a Fulton Reliance RLN-2000 hydronic boiler. My modbus is landed on the Sola Touch screen on Com2 port which it calls...
  15. Replies
    5
    Views
    662

    What browser types have you tried? Are you at...

    What browser types have you tried?

    Are you at the latest TU service pack?
  16. Replies
    2
    Views
    467

    ES has to subscribe to alarms in the SC. You can...

    ES has to subscribe to alarms in the SC. You can find this under settings and alarm subscriptions i believe. Subscribe to 1-4
  17. Replies
    3
    Views
    574

    The VAVs hooked to a BCU and programmed into a...

    The VAVs hooked to a BCU and programmed into a site there? Or they standalone?

    If there is a BCU then Yes. You will need to record the auth number down for the machine you wish to use. Then...
  18. Replies
    2
    Views
    433

    The older units did not follow profiles and...

    The older units did not follow profiles and whatnot as well as the new firmwares. So if you got a older green board or one that just wont accept an upgrade i would say that is your issue.
  19. Replies
    14
    Views
    1,936

    Yes you need tracer summit to change the BCU to...

    Yes you need tracer summit to change the BCU to BACnet/IP through a utility called ip validate/bcu config. You use a mini monitor cable to do this. Since you are already talking via RS-232 you...
  20. Replies
    14
    Views
    1,936

    Nothing is wired to the LON in your picture. ...

    Nothing is wired to the LON in your picture. Only thing wired up is the Comm4 link, so the chiller is talking that.

    To get BACnet/IP out of the BCU you will need to load an IP in it, then make...
  21. Years ago I had used a program NL Util. Not sure...

    Years ago I had used a program NL Util. Not sure if it does all you want but you might check it out.
  22. Replies
    3
    Views
    442

    Yes you are correct.

    Yes you are correct.
  23. Replies
    17
    Views
    1,788

    Its checking for a value out of range. So if...

    Its checking for a value out of range. So if your input is setup as 4-20ma, you will get a fail if it is below 4 or above 20. Thermistors out of there temperature range, etc..

    When the fail is...
  24. Replies
    17
    Views
    1,788

    P of 2 and 20 sec PID runtime to start be worth a...

    P of 2 and 20 sec PID runtime to start be worth a shot.
  25. Replies
    17
    Views
    1,788

    no integral is not in seconds. Advantage of...

    no integral is not in seconds.

    Advantage of feedback is the PID knows last value. So if you have another program controlling the value based on something (freezestat, low limits, etc..) it knows...
  26. Replies
    17
    Views
    1,788

    What is your P, I and PID run frequency?

    What is your P, I and PID run frequency?
  27. Replies
    7
    Views
    584

    if it has the t-stat terminals on the board then...

    if it has the t-stat terminals on the board then just use those and remove the Trane thermostat from 1,2,3 terminals. I believe that is all you have to do.
  28. Replies
    14
    Views
    1,936

    If i read what you want right, a BCU will not...

    If i read what you want right, a BCU will not talk BACnet MSTP. So you can not interface directly to the BCU that way. You can do BACnet/IP with a BCU.
  29. Replies
    9
    Views
    728

    I dont remember exactly off hand but it should be...

    I dont remember exactly off hand but it should be something like Site: School, BCU-1 Chiller 1, High Head Pressure in alarm and a date stamp

    I believe it gives you most of what you see in the...
  30. Replies
    9
    Views
    728

    You use outlook 2007 with a valid account made in...

    You use outlook 2007 with a valid account made in it that can send out emails. You must have Summit and Outlook running at all times for emails to be sent. You can only define one alarm class to be...
  31. Replies
    32
    Views
    2,545

    Can you find that board with the neuron id and...

    Can you find that board with the neuron id and isolate it from the link and see if your lon problems go away? Almost looks like you have a bad board that is flooding the link.
  32. Replies
    5
    Views
    604

    Go to Tracer ES Home, then select all buildings,...

    Go to Tracer ES Home, then select all buildings, next page check mark the building you want to delete and hit advanced, next page hit delete
  33. Replies
    1
    Views
    409

    They are called "Common Boxes". When adding vavs...

    They are called "Common Boxes". When adding vavs to the VAS you set up how many common boxes you want to keep occupied during start/stop of the RTU. You can go to vas and then members tab and the...
  34. You might try creating a new area. See if its...

    You might try creating a new area. See if its still grayed. Make sure you have all security rights you need also. When upgrading from that old user privileges changed.

    If you try all this and...
  35. Have you isolated anything out? Have you got on...

    Have you isolated anything out? Have you got on the mstp link and seen how it responds? Is it slow?

    Is the trane controller and the siemens router on the same subnet? Are they on a customers...
  36. Are you integrating into a Tracer SC directly on...

    Are you integrating into a Tracer SC directly on the mstp link or is this a router that is converting over to bacnet/IP and into a SC or BCU? Sorry i am not fimilar with the ATEC.
  37. Replies
    11
    Views
    668

    I 100% agree with qtip here. That is their job...

    I 100% agree with qtip here. That is their job and they need to get the software and input it themselves. Especially since its free as stated earlier. I personally have never inputted values for a...
  38. Replies
    11
    Views
    668

    Air Flow Gain AV-18 Gain set when air balancing ...

    Air Flow Gain AV-18 Gain set when air balancing
    Factory default 1.0 Range 0.000 to 2.000
  39. Replies
    11
    Views
    1,212

    Its based on box type and if it has a flow ring...

    Its based on box type and if it has a flow ring and transducer. Then if that is setup correct it has to be reading flow. It will switch between the modes automatically based on if it successfully...
  40. Replies
    3
    Views
    594

    Not sure if JCI does it the same way, but do you...

    Not sure if JCI does it the same way, but do you have the BACnet user able to perform writes? Maybe make it a super user to test.

    Also when exporting points did you allow anything in the 1-16...
  41. Replies
    4
    Views
    485

    The SC is a native BACnet device. So anything...

    The SC is a native BACnet device. So anything brought into the panel will be available to you to pull in via IP. We do not have to build a point database like we use to in the old BCUs. If you...
  42. Replies
    9
    Views
    1,149

    You can make the BAS setpoint adjustment at the...

    You can make the BAS setpoint adjustment at the vav itself. You can also make global bas setpoint adjustments from the spaces page depending on what version of SC you are running.
  43. Even if you upgrade to a bridge/SC you will still...

    Even if you upgrade to a bridge/SC you will still need the CM4.1 in place.
  44. Replies
    3
    Views
    571

    I would say that almost all bindings are...

    I would say that almost all bindings are typically done in a BCU. So once you remove the BCU the bindings are lost. There is two domains that exist, an A and B. Trane by default commissions both...
  45. Replies
    13
    Views
    1,049

    Rover discovers the link on a ZL domain. If you...

    Rover discovers the link on a ZL domain. If you set the Jace up to a specific domain and set domain B to not used then rover will not discover it. You can either have the Jace set one of the...
  46. Replies
    15
    Views
    1,438

    The repeater can be anywhere in the link long as...

    The repeater can be anywhere in the link long as it leaves <60 on one side. So it may be physically anywhere. Trane repeaters also do not show up on a scan or in the BCU. So you would not see it...
  47. Replies
    4
    Views
    655

    Also check what voltage you read with it the...

    Also check what voltage you read with it the wires unhooked. If it still reads 13 unwired then not a vsd issue.
  48. Replies
    9
    Views
    1,149

    Each user preference can be set to display what...

    Each user preference can be set to display what they want. So log in as the user and then go to preferences and select display units you want to see.
  49. The bcu can reside on the network in the ethernet...

    The bcu can reside on the network in the ethernet mode. Just plug the BCU and the PC both into a switch. Ethernet does not cross subnets so if for some reason the network you plugged the bcu into...
  50. Replies
    2
    Views
    549

    Are you running a sql database setup on a larger...

    Are you running a sql database setup on a larger site?