Search:

Type: Posts; User: shovelhead

Page 1 of 6 1 2 3 4

Search: Search took 0.01 seconds.

  1. XL15c loosing points configuration in AX

    Has anyone had 15c controllers just loose their points configuration in AX? I have several controllers loose the points configuration only, I re-download them and they loose them again in a day....
  2. Replies
    7
    Views
    504

    I've been to both classes, I think you'll be...

    I've been to both classes, I think you'll be fine. They didn't go over any controls theory such as how a building works, the go over area control, VAS, chiller plant control and such. Configuration...
  3. Replies
    7
    Views
    727

    There isn't anything that you can do, the demo...

    There isn't anything that you can do, the demo license expires every year just like the work bench license does.
  4. Replies
    5
    Views
    891

    If you have a BCU, on the BMTS and the BMTX, the...

    If you have a BCU, on the BMTS and the BMTX, the daughter boards are flat for comm4, flat with a cylinder protruding from the board is comm3 isolated and the lon board has the square neuron chip on...
  5. Replies
    5
    Views
    796

    You are exactly right, the SC does not do comm4,...

    You are exactly right, the SC does not do comm4, a BCU is need fot a gateway. It's pretty bad when their new "cutting edge" system doesn't support their own protocol.
  6. They are talking about variable flow primary and...

    They are talking about variable flow primary and they are nothing new. A chiller has a life capability from the evaporator to the condenser, it's usually around 14 to15 psi, the most efficent pumping...
  7. Replies
    11
    Views
    1,335

    Did you upload all of the controllers using the...

    Did you upload all of the controllers using the upload command under each controller? Did you link manage the controllers?
  8. Replies
    3
    Views
    372

    What version of Summit are you running? You do...

    What version of Summit are you running? You do not have to delete a site before connecting to a different site, summit uses update tags to check for changed data. The first thing that should be...
  9. Replies
    2
    Views
    274

    Remove the cover or open the door, on the right...

    Remove the cover or open the door, on the right see if there's a seven segment display. If so what's the display doing, a -P means that the database is gone on the BCU. If there's a dash moving up...
  10. Replies
    7
    Views
    922

    Honeywell WEBS has a open and a closed license...

    Honeywell WEBS has a open and a closed license but you you have to know about the open and closed license and ask as well as pay more for the open. Once the JACE is bought you have to have the owner...
  11. Replies
    8
    Views
    1,081

    After I unzip my software and go to the setup...

    After I unzip my software and go to the setup exe, I also have a serial tunneling install exe. After the installation there is a serial tunneling application placed in my Windows XP control panel to...
  12. Replies
    8
    Views
    1,081

    Using the ASD driver from Lynxspring. I'm...

    Using the ASD driver from Lynxspring. I'm tunneling with XPSI over the net as well as local.
  13. Replies
    9
    Views
    569

    Can I do the recommissioning with hyperterminal?...

    Can I do the recommissioning with hyperterminal? The control is the one line display before the opti-view. It was also set-up with the quick commission using the dip switches.
  14. Replies
    9
    Views
    569

    Yeah, I'm using a JACE and just like klrogers, I...

    Yeah, I'm using a JACE and just like klrogers, I write to the point in the elink but the elink doesn't seem to be writing to the chiller. I went into the elink with hyperterminal looking for a way to...
  15. Replies
    8
    Views
    1,081

    What driver are you trying to tunnel through? I...

    What driver are you trying to tunnel through? I have tunneling working fine for the ASD driver.
  16. Replies
    9
    Views
    569

    I have it in remote.

    I have it in remote.
  17. Replies
    9
    Views
    569

    York YS with ELink

    Has anyone integrated a YS and used the start/stop point YT_S01_PO7 to enable and disable the machine? I can write to the BACnet point but the point will not confirm the write and start the machine....
  18. Replies
    12
    Views
    2,341

    I'm using the Lynxspring driver, my question is,...

    I'm using the Lynxspring driver, my question is, it appears that the controllers have different write priorities. If I write @def it sometimes appears that the controller ignores the command on...
  19. Did you change the addresses on the VAVs? They...

    Did you change the addresses on the VAVs? They were the same on the command modules. The addresses can only be up to 127 also if I remember correctly.
  20. Replies
    11
    Views
    1,244

    Look at the poll scheduler statistics, what's the...

    Look at the poll scheduler statistics, what's the dibs bucket doing?
  21. You were right I forgot the "2". If only I could...

    You were right I forgot the "2". If only I could type decently I would be a hellofagood programmer. Most of mu problems end up being typos.
  22. I just put my email in my profile, I thought I...

    I just put my email in my profile, I thought I had already put it there.
  23. Let me look at the program and I'll try and...

    Let me look at the program and I'll try and answer it, you should practice programming the 15c, there's a simulator avaliable online that will attach to the Lonspec software. As for integral, it's...
  24. Replies
    4
    Views
    1,862

    zigmund, I worked for Trane for 16 years and...

    zigmund, I worked for Trane for 16 years and don't recall ever seeing a comm4 like repeated. These links typically had in the 30's number of devices and up to around 400 feet of wire. It is polarity...
  25. You alreay have the hard part done, you...

    You alreay have the hard part done, you understand HVAC. The rest is learning to use a software program. I own my own company and would not hire anyone who didn't know HVAC, that's a real problem...
Results 1 to 25 of 136
Page 1 of 6 1 2 3 4