  1. Replies
    2
    Views
    222

    Try using displayName instead of AbsoluteOrd....

    Try using displayName instead of AbsoluteOrd. Then once the points populate click the edit slot button and then select fallback if nothing is writing into these points.
  2. Replies
    12
    Views
    827

    Me personally, I would go with Lon. On the Bacnet...

    Me personally, I would go with Lon. On the Bacnet spyder if you use the Sylk IO you can only use 2 and with the Lon you can use 3.
  3. Replies
    12
    Views
    827

    Oh you can change it in the properties and save...

    Oh you can change it in the properties and save it just fine, but if you look in the application director you will see write denied and if you upload the config you will see it revert back to 127
  4. Replies
    8
    Views
    484

    Nice job, tell Mr. Jobe I said hello.

    Nice job, tell Mr. Jobe I said hello.
  5. Replies
    17
    Views
    1,311

    Yeah we just bit the bullet and didn't charge any...

    Yeah we just bit the bullet and didn't charge any of our customers. We did have one jace that died in the reboot process, all the lights went out and stayed out. Haven't tried serial shell yet to see...
  6. Replies
    17
    Views
    1,311

    Wasn't that fun. Spent all day yesterday and part...

    Wasn't that fun. Spent all day yesterday and part of this morning fixing I don't know how many jaces.You would think Tridium would have made provisions for this since it happened before in 3.4 I...
  7. The default ignores the history groupings. I am...

    The default ignores the history groupings. I am not sure how you can accomplish what you are trying to do since the history grouping just groups the history names and each history name has to be...
  8. I am not sure the doc explains this, but if you...

    I am not sure the doc explains this, but if you already have your histories configured the easiest way to do this is right click on the config of the station and go to views>Metadata Browser. Expand...
  9. Thats pretty much what I have done in the past....

    Thats pretty much what I have done in the past. If it has the Copeland compressor module for the digital scroll I believe you have to send a minimum of like 1.2 volts to the module for the compressor...
  10. Replies
    4
    Views
    273

    I have seen this before years ago. I went through...

    I have seen this before years ago. I went through my notes and found this.

    Global Schedules

    Problem: Global schedules would not download because of conflict with special day.

    Solution: Went...
  11. Replies
    6
    Views
    379

    What is the CPU usage while it is running.

    What is the CPU usage while it is running.
  12. Replies
    6
    Views
    379

    Is that the last error you get in the station...

    Is that the last error you get in the station output before it fails? If not, post that. You can also use Spy to look at the system log.
  13. Replies
    4
    Views
    377

    Use workbench to go into the module and copy the...

    Use workbench to go into the module and copy the gifs you need to change to your desktop. Then use paint or something to rotate them, save them and then just copy them into the station.
  14. Replies
    12
    Views
    827

    Keep in mind that you cannot adjust the Max...

    Keep in mind that you cannot adjust the Max Master on the Spyder.
  15. Replies
    14
    Views
    1,660

    It's our demo site, it was created that way to...

    It's our demo site, it was created that way to match our website.
  16. Replies
    14
    Views
    1,660

    Lol, This is just our demo station I created. My...

    Lol, This is just our demo station I created. My humidity setpoint on my AHU is 1.8" also. :LOL:
  17. Replies
    14
    Views
    1,660

    I did these with http://bassg.com/ graphics...

    I did these with http://bassg.com/ graphics except the dashboard. Prices are very reasonable.

    685211685221685231685241
  18. Replies
    2
    Views
    703

    You might try deleting your Niagara directory...

    You might try deleting your Niagara directory under your user account and try to login again. Maybe something got corrupted when it was downloading the jar files.
  19. Replies
    6
    Views
    605

    Sorry I meant to say link the weather state to a...

    Sorry I meant to say link the weather state to a status enum to status boolen, not status string to status boolean.
  20. Replies
    6
    Views
    605

    You could probably use the state property in the...

    You could probably use the state property in the current conditions which is an enumerated value. Link that to a status string to status boolean conversion from KitControl and set your appropriate...
  21. The ultimate solution would be to use a Loytec...

    The ultimate solution would be to use a Loytec LIP router and bring everything back to the jace over IP, especially if you have a bunch of controllers on each one of those segments.
  22. Thread: AX3-PPC-O

    by lwarren
    Replies
    3
    Views
    395

    Does it have Spyders on it? I replaced a bad 600...

    Does it have Spyders on it? I replaced a bad 600 at a site with a 300 because it only had 5 controllers on it. 4 XL10"s and 1 Spyder. I won't ever use one of those again if there are spyders...
  23. Thread: Niagara Summit

    by lwarren
    Replies
    12
    Views
    1,035

    Looking forward to meeting some you guys.

    Looking forward to meeting some you guys.
  24. Thread: Niagara Summit

    by lwarren
    Replies
    12
    Views
    1,035

    Niagara Summit

    Who is going to the Summit this year?
  25. I do it all the time. But I usually use 3/8" poly...

    I do it all the time. But I usually use 3/8" poly for the main run.
  26. Replies
    3
    Views
    1,362

    Try subtracting 128 from any alarm value that is...

    Try subtracting 128 from any alarm value that is over 128 and use that value.
  27. Replies
    2
    Views
    278

    You should be able to accomplish this easily...

    You should be able to accomplish this easily through the Alarm Instructions Manager. Just right click on the alarm service and select the alarm instructions manager view.
  28. Replies
    13
    Views
    620

    Yes.

    Yes.
  29. Replies
    13
    Views
    620

    No, in this example the DO will the have a value...

    No, in this example the DO will the have a value of 1 when the X input of the select is 0=Ocupied, 2=Bypass or 3=Standby. The DO will have a 0 input when the X input is 1=Unoccupied. The Bacnet Venom...
  30. Replies
    13
    Views
    620

    If you are actually using the share object from...

    If you are actually using the share object from another controller then link from the niShare_EffOcc to the X slot of the select.
  31. Replies
    13
    Views
    620

    Something like this. 663811

    Something like this.

    663811
  32. Replies
    13
    Views
    620

    That will only work if you are using the nviShare...

    That will only work if you are using the nviShare in that controller. IE, linked from another controllers nvoShare. Also the occupancy value is going to be a logical 0 for a lon occupancy point, so...
  33. Replies
    1
    Views
    328

    I put one in at our Corporate office a few years...

    I put one in at our Corporate office a few years ago for access control and HVAC. The biggest problem is that they arent updating the versions like they do regular jaces. I just installed one about a...
  34. Replies
    10
    Views
    1,810

    You need to discover Jace 1 in the niagara...

    You need to discover Jace 1 in the niagara network of your other jaces and then bring the OAT into the other jaces from Jace 1.
  35. Replies
    2
    Views
    358

    Just use the program service displayName = "point...

    Just use the program service displayName = "point name" then use the edit slot flags option.
  36. Replies
    12
    Views
    923

    If the XL50's are Lon you are going to have a...

    If the XL50's are Lon you are going to have a problem because the points have to made as Lon points to be exposed in the XL50 with the Honeywell CARE software.
  37. Replies
    9
    Views
    643

    Thanks. It was an awesome night and year. 16 and...

    Thanks. It was an awesome night and year. 16 and 0 in only their second year of UIL.
  38. Replies
    9
    Views
    643

    My son made Fox Sports Play of the year!

    Got to give a shout out to my son for making Fox Sports play of the year and ESPN Sportscenters Top 10 with the number 3 play with his TD run in their State Championship game at NRG Stadium in...
  39. Replies
    18
    Views
    1,118

    If this is a VAV unit then you should probably be...

    If this is a VAV unit then you should probably be writing to nviDACLSP.
  40. I don't think it was comm port settings I had to...

    I don't think it was comm port settings I had to change in the Continum software. It has been over a year since I did this, I should have made notes. I spent several days messing around with stuff in...
  41. I believe the pinout is correct. I don't remember...

    I believe the pinout is correct. I don't remember exactly what I did, but I had to get something setup right in the Andover Continuum software before my communications would work.
  42. Replies
    15
    Views
    1,096

    Your APDU timeout settings should match for all...

    Your APDU timeout settings should match for all of your devices on the network. I think the default APDU setting on the jace is 3000 milliseconds by default.
  43. Replies
    15
    Views
    1,096

    I have integrated many of these over the years...

    I have integrated many of these over the years with AX via Lon and BACnet without very many problems. Don't wast your time with AAon, call Orion Controls tech support www.orioncontrols.com as that is...
  44. Per Amigo's suggestion If you are not familiar...

    Per Amigo's suggestion If you are not familiar with this, right click on the LonNetwork and select the Lon Utilities Manager. In the Command dropdown select Reports. In the SubCommand dropdown you...
  45. Replies
    5
    Views
    1,105

    It's been awhile, but if I remember correctly the...

    It's been awhile, but if I remember correctly the Copeland digital scroll controller takes a 0-5 VDC signal and has to have at least 1.2 VDC for the compressor to run. So, if I remember correctly if...
  46. They should have discovered if they were truly on...

    They should have discovered if they were truly on the same domain. Niagara default domain is 0 Length. I believe the XL10's came from the factory with a domain length of 1 and domain id of 2C
  47. Replies
    6
    Views
    950

    Rip that piece of crap out and just bring the...

    Rip that piece of crap out and just bring the stuff in via modbus. You wont have anymore problems.
  48. Replies
    7
    Views
    930

    Always a good idea to check the software manager...

    Always a good idea to check the software manager on a Jace before making any changes. Glad you got it worked out. Make sure you have the latest consolidated patches for 3.8 as well.
  49. Replies
    7
    Views
    930

    Are you sure the workbench you are connecting to...

    Are you sure the workbench you are connecting to the Jace with has the same version modules? I would verify with the software manager.
  50. Replies
    7
    Views
    930

    Sounds like something got corrupt. I would save...

    Sounds like something got corrupt. I would save the logic to the Spyder Library. Add a new spyder to the network. Delete the nueron from the current spyder. Discover, and match to the new blank...
Results 1 to 50 of 1000