  1. Replies
    42
    Views
    6,699

    Rover is never going to read your UPCM, you'll...

    Rover is never going to read your UPCM, you'll need to go into a bit more detail about your problem and would probably be better served if you started a new thread.
  2. Replies
    55
    Views
    3,986

    Eh, I don't have a lot of experience outside of...

    Eh, I don't have a lot of experience outside of Trane, Tridium and KMC so I'd have to say Trane's UC400 is pretty crappy because they fail like 95 going North and Trane's AH541 sucked as well. ...
  3. Replies
    2
    Views
    336

    It's a MOD02085 if anyone ever needs it. That's...

    It's a MOD02085 if anyone ever needs it. That's for the plastic cover-BTW
  4. Replies
    2
    Views
    336

    Trane ZN511 part number

    Kind of straight forward question like the title says, does anyone know the part number or have the serial number of a Trane ZN511? I need to order a replacement.

    Thanks,
  5. Replies
    4
    Views
    765

    The only way I know to have the BCU use Bacnet/IP...

    The only way I know to have the BCU use Bacnet/IP and have the PC be connected to your ISP is to purchase two static IP's from your ISP, one for the PC and one for the BCU. This way they'll be on the...
  6. I don't know what Version of Summit you're...

    I don't know what Version of Summit you're running but I've only seen this problem with v.17 and Windows 7 or higher. You must add the latest service packs to allow ethernet to work with Win 7 or...
  7. Replies
    4
    Views
    765

    It depends on how Summit connects to the...

    It depends on how Summit connects to the workstation. If Summit uses a simple Ethernet connection then you should be able to use DHCP to connect to your ISP and ethernet to connect to the BCU. If the...
  8. Replies
    2
    Views
    642

    Trane VAV's (or any VAV that I'm aware of for...

    Trane VAV's (or any VAV that I'm aware of for that matter) cannot control humidity. Humidity control and discharge air reheat must be accomplished at the air mover (AHU, RTU, SCU, whatever).

    The...
  9. Replies
    12
    Views
    1,467

    .....um, I could be wrong but I thing q-tip was...

    .....um, I could be wrong but I thing q-tip was agreeing with you and directing his statement "Yup, read above..." to the OP suggesting that he follow your advice.

    Again, I could be wrong but...
  10. Replies
    9
    Views
    1,487

    You'll still need Tracer TU to enable the write...

    You'll still need Tracer TU to enable the write points you want to control. You'll be able to pull them in and you can attempt to write to them, but the RTU won't respond to your commands until the...
  11. Thread: Graphics ?

    by mallron
    Replies
    12
    Views
    3,236

    I realize this is an old thread, but wanted to...

    I realize this is an old thread, but wanted to say "thanks" as this thread just helped me tremendously.
  12. Replies
    19
    Views
    2,729

    As the others have mentioned, you shouldn't need...

    As the others have mentioned, you shouldn't need Trane for anything UNTIL 10% of your UC400's fail within the first year as has happened to me on every single stinkin' UC400 job I have ever done. If...
  13. Replies
    3
    Views
    885

    Most of the time Trane will not reset the Auth...

    Most of the time Trane will not reset the Auth code unless there has been some sort of failure on the original PC the software was installed on. If you simply want to use Summit on a different PC...
  14. Replies
    10
    Views
    2,531

    If you decide to use the conventional terminals...

    If you decide to use the conventional terminals keep in mind that the BCI takes priority of the trane sensor terminals and the trane terminals take priority over the conventional terminals so the BCI...
  15. Replies
    8
    Views
    1,279

    I think it would be good to know if this is a...

    I think it would be good to know if this is a factory installation or a retrofit. If this is a factory AHU/RTU then there should be a predetermined landing point for smoke.
  16. Replies
    7
    Views
    1,661

    what panel is on that chiller? I'm not sure...

    what panel is on that chiller? I'm not sure there is a BACnet retrofit available for chillers that old.
  17. Replies
    10
    Views
    1,666

    I have several VFD's out there that are being...

    I have several VFD's out there that are being controlled via 2-wire comm and haven't had any problems with them at all, but there's still that part of me that prefers hard wired control.
  18. Replies
    11
    Views
    1,821

    Put a temp sensor in the return in you don't have...

    Put a temp sensor in the return in you don't have one in the space and jack you daytime warm-up and morning warm up settings to 80 or so. I assume you have heat in the RTU?

    Make triple sure that...
  19. Replies
    8
    Views
    1,271

    And yes they are Danfoss drives with Tranes name...

    And yes they are Danfoss drives with Tranes name on them.
  20. Replies
    8
    Views
    1,271

    I have done a few of these but I remember...

    I have done a few of these but I remember installing BACnet cards because they originally shipped with LON cards and we had to get BACnet cards overnighted. Set-up was simple however and they worked...
  21. Replies
    2
    Views
    711

    IP wouldn't be tough if you have Summit. You...

    IP wouldn't be tough if you have Summit. You would definitely need a hi cap card and reference all the info you would want to expose as BI, BO, AI's and AO's. If you have Summit
    it would be a ton...
  22. did you guys ever get this one figured out? I'm...

    did you guys ever get this one figured out? I'm having a similar issue except the Corel controller doesn't seem to take the start/stop command at all, but I get temps etc at my front end.
  23. Replies
    3
    Views
    887

    The BMTX BCU is capable of communicating to the...

    The BMTX BCU is capable of communicating to the UCP 1 and/or the UCP 695 panels. The BCU must be 2007 or later and have
    the latest firmware. I've wired up quite a few of them.
  24. Thread: Trane CPL

    by mallron
    Replies
    2
    Views
    806

    connect to the BCU with you Tracer Summit...

    connect to the BCU with you Tracer Summit software and choose "set-up" then scroll down to "custom programming". a window will pop up, close it and choose "program" at the top of the screen, then...
  25. Replies
    3
    Views
    882

    I'm still trying to figure this one out. I think...

    I'm still trying to figure this one out. I think it may be a problem with my PC specifically because I installed TU on a desktop that had basically the same config as my labtop and TU starts on the...
  26. Replies
    3
    Views
    882

    Tracer TU...again

    Anyone had issues with TU starting since the latest Java updates?

    I'm running Windows 7 and the only changes that have been made to my laptop since the last time I used TU
    were the Java updates...
  27. Replies
    4
    Views
    1,498

    You could have Trane replace the Tracer 100i...

    You could have Trane replace the Tracer 100i panel with a BCU relatively easily and would maybe cost 15k including a workstation and graphics. Having everything replaced with new controls would cost...
  28. Replies
    4
    Views
    911

    what board is in the unit? post a pic if you're...

    what board is in the unit? post a pic if you're not sure.
  29. Replies
    3
    Views
    1,022

    I work at a zoo that's controlled by Tracer...

    I work at a zoo that's controlled by Tracer Summit, but it's actually a High School.
  30. Replies
    2
    Views
    1,586

    I downloaded this, thanks Lunchbox

    I downloaded this, thanks Lunchbox
  31. I would try removing all override control except...

    I would try removing all override control except for heating/cooling setpoints and occupancy.
  32. Replies
    6
    Views
    1,038

    Welcome aboard or to-the-board rather. I...

    Welcome aboard or to-the-board rather.

    I really don't have much to offer other than to say that I would think that it shouldn't matter where on the comm link the devices reside just as long as...
  33. Thread: Trane

    by mallron
    Replies
    2
    Views
    783

    They're usually included in Rover service packs.

    They're usually included in Rover service packs.
  34. Replies
    20
    Views
    3,681

    I don't see the point in operating the drives in...

    I don't see the point in operating the drives in bypass. If the towers are in an industrial/process application in which the cooling systems are always close to or at full load that still doesn't...
  35. Replies
    19
    Views
    8,059

    The part number is SFT1002 if I remember...

    The part number is SFT1002 if I remember correctly. Try Trane parts with that part number.
  36. Replies
    6
    Views
    1,868

    emergency shutdown is used for the fire alarm in...

    emergency shutdown is used for the fire alarm in most applications. you want remote shutdown and it's on the LVTB or low voltage terminal board. there's a metal factory jumper in place on the...
  37. Replies
    10
    Views
    4,899

    Thanks, Joey.

    Thanks, Joey.
  38. Replies
    10
    Views
    4,899

    I just got the software last week, I guess they...

    I just got the software last week, I guess they were getting rid of old stock.
  39. Replies
    10
    Views
    4,899

    This was it, I was attempting to connect with the...

    This was it, I was attempting to connect with the adapter connected to the BACnet bus because there were no stat drops. It actually says this in the manual but who reads those anymore? I can...
  40. Replies
    10
    Views
    4,899

    Yup, it won't start unless it's licensed, well,...

    Yup, it won't start unless it's licensed, well, it will launch but you won't get far.

    Update, I performed a "repair" of the TU installation and now I can direct connect but still can't connect via...
  41. Replies
    10
    Views
    4,899

    Ok, I downloaded the latest version of the BACnet...

    Ok, I downloaded the latest version of the BACnet service tool and now I can download measurement conversions into the UC400, but I still can't connect with TU at all. TU is version 8.2 BTW.
  42. Replies
    10
    Views
    4,899

    Tracer TU Trane BACnet service tool UC400

    I'm in a real bind here. I'm working on (trying to anyway) a job with UC400 Trane VAV's and I can't get TU to communicate
    with the UC400's at all. I'm attempting to connect using a direct...
  43. Thread: Trane BCU

    by mallron
    Replies
    3
    Views
    880

    buy a upcm edit cable with the 9-pin adapter (two...

    buy a upcm edit cable with the 9-pin adapter (two separate parts).

    Your hyperterminal settings look good, but you can use the BCU IP config tool and the upcm edit cable if you have Summit on your...
  44. Replies
    29
    Views
    6,480

    This guy is full of sh!t and should be kicked in...

    This guy is full of sh!t and should be kicked in the ass for spreading such nonsense. (although i may get a good lashing for cursing, I just couldn't help it)
  45. Replies
    41
    Views
    8,610

    Mike Marston with Easy I/O hooked me up!!!!! He...

    Mike Marston with Easy I/O hooked me up!!!!! He set-up Sedona on my PC for me and tested everything to make sure the install was functional.

    Mike, I can't thank you enough!
  46. Replies
    5
    Views
    1,241

    Off topic, but what ever happened to Kwillmech...

    Off topic, but what ever happened to Kwillmech anyway? I haven't seen a post from him in 4ever.
  47. Replies
    41
    Views
    8,610

    you have mail

    you have mail
  48. Replies
    41
    Views
    8,610

    Off topic- if either of you guys could PLEASE...

    Off topic- if either of you guys could PLEASE send my a step by step of how/what files to copy over I would be forever in your debt. I've been trying to figure out what I'm supposed to be copying...
  49. Replies
    10
    Views
    2,424

    what type of AHU do you have? Is it Trane? VAV...

    what type of AHU do you have? Is it Trane? VAV or CAV? Indoor or outdoor? Intellipak or modular (if Trane)?
  50. Replies
    10
    Views
    2,424

    The charge should have been weighed into that...

    The charge should have been weighed into that system, it's very difficult to charge a system with multiple stages in the same circuit using only the traditional charging methods. First, the system...