    if I recall correctly, bcm-tux turns each tux...

    if I recall correctly, bcm-tux turns each tux into a bacnet virtual device, so you should be able to explore these virtual devices and see points. But I guess you are saying that this is a no go?...
  2. Replies
    17
    Views
    833

    seems like a nice and friendly gesture, thanks...

    seems like a nice and friendly gesture, thanks makeitwork
  3. Replies
    8
    Views
    350

    probably have to create some bs functional block...

    probably have to create some bs functional block in lonmaker. I have not used lonmaker in like 8 yrs, you may have some sentimental attachment to lonmaker, but the newer lns tools are far better and...
  4. Replies
    1
    Views
    215

    depends on whose graphical programming. the...

    depends on whose graphical programming.
    the blocks should be kind of similar, one main difference is typically tstat block has a deadband parameter that can be above/below or split across the...
  5. Replies
    8
    Views
    350

    yes, it is always good practice to...

    yes, it is always good practice to remove/uninstall old version of plugins, and then install new ones.
    if you are testing out scc-410 for first time, I think it is a pretty nice little controller.
    ...
  6. Replies
    8
    Views
    350

    :ditto:

    :ditto:
  7. Replies
    55
    Views
    3,986

    I don't use any kmc stuff, but are you saying...

    I don't use any kmc stuff, but are you saying that simply vav must have a changeover sensor for every box?
    you can't just tell it it is a clg only unit?
  8. Replies
    289
    Views
    56,430

    cool

    cool
  9. Replies
    289
    Views
    56,430

    you probably have to use the "BU" (Bit unpack)...

    you probably have to use the "BU" (Bit unpack) argument in your point mapping and dump into a BV.
    Do you have the install/operation guide for FLG?
    If not, go here:...
  10. along the same lines:...

    along the same lines:
    http://www.atkinsonelectronics.com/manufacturing/product_pdfs/SSRM.pdf

    have not used it, but atkinson makes good products in general.

    good luck.
  11. Replies
    2
    Views
    215

    I think Kele used to sell Lumisys, may be go on...

    I think Kele used to sell Lumisys, may be go on kele site and do a search for archive Lumisys manuals.

    good luck.
  12. Replies
    9
    Views
    1,048

    do you seriously think that they will keep the...

    do you seriously think that they will keep the manufacturing in Canada?
  13. Thread: Circon Basic

    by amigo
    Replies
    3
    Views
    385

    yes, and if I am not mistaken pricing seems to be...

    yes, and if I am not mistaken pricing seems to be very similar to 300 prg
  14. Replies
    7
    Views
    344

    are you sure it is MNL-700 and not MNL-800?...

    are you sure it is MNL-700 and not MNL-800?
    anyway, from my little experience with MNL, it is full programmable, meaning whoever wrote the code in there for some strange reason used snvt_count_inc_f...
  15. Replies
    7
    Views
    344

    if you have not tried putting -1 or 255 in there...

    if you have not tried putting -1 or 255 in there as a shot in the dark then try it.

    if all fails, may be post the make and model of the device/equipment itself, and then maybe someone here has...
  16. Replies
    7
    Views
    344

    snvt count_inc_f is a floating point, 4 bytes,...

    snvt count_inc_f is a floating point, 4 bytes, which means it basically can have a full range of numbers. If sending nan does not work, then in that case I believe you need to find out from...
  17. Replies
    7
    Views
    344

    typically each snvt type will have a predefined...

    typically each snvt type will have a predefined null/invalid value (refer to master snvt list (google it if you don't have it)), so I would start by looking at which snvt type is your nci and then...
  18. Thread: Circon Basic

    by amigo
    Replies
    3
    Views
    385

    according to the circon basic manual, the...

    according to the circon basic manual, the function only works in uhc-300, and uhc-320

    good luck.

    ps, if the job can afford it, I would look at scc-410, fully programmable graphically and seems...
  19. Replies
    8
    Views
    431

    I think you are getting screwed by $$$$, most...

    I think you are getting screwed by $$$$, most likely any decent generic one will work.
    if you want exact, just do yourself and company a favor and order online...
  20. Replies
    9
    Views
    544

    you mean you wanna sell it?

    you mean you wanna sell it?
  21. Thread: LVIS Modbus

    by amigo
    Replies
    7
    Views
    399

    I think he is trying to write data to the LVIS so...

    I think he is trying to write data to the LVIS so it can be displayed and interacted with. He probably has some other PLC that is getting metering data from somewhere and is the master on the...
  22. Thread: JCI ZFR1810-0

    by amigo
    Replies
    4
    Views
    404

    I believe he is referring to: BACnet Quick Test...

    I believe he is referring to: BACnet Quick Test
    http://www.polarsoft.biz/bqt.html
  23. VLDs basically come in two main flavors, VLD-362...

    VLDs basically come in two main flavors, VLD-362 or VLD-362-FF
    FF stands for fixed function , meaning non-programmable only configurable.

    If you have the FF model then I may be able to get you a...
  24. Replies
    14
    Views
    872

    NYC_Controls, there are many rs485 to ethernet...

    NYC_Controls, there are many rs485 to ethernet serial adapters available in the market, just make sure whatever you choose has the capability for "Paired Mode or Serial Tunneling" Obviously you will...
  25. Replies
    8
    Views
    566

    I know nothing about ACM, but from what you are...

    I know nothing about ACM, but from what you are describing, you are dealing with the metallic blue distech free programmable controllers, ec-8, ec-12, etc.
    In those, a lot of the point had...
  26. Replies
    28
    Views
    1,813

    yes, good point.

    yes, good point.
  27. Replies
    28
    Views
    1,813

    I think he probably is just using the wrong...

    I think he probably is just using the wrong terminology.
    Wayne is right, if it is just a switch, typically it won't control a vfd. If it is a transducer, then it gives a variable signal depending on...
  28. jtplumbing88, I had some questions for you can...

    jtplumbing88, I had some questions for you can you please contact me via my email in my profile.
    cheers
  29. I don't know eBCON, but may be enter the same IP...

    I don't know eBCON, but may be enter the same IP address in both parameters. What DDNS is providing you is the external IP address as far as I know.

    good luck.
  30. Just get DDNS and just type the url into a...

    Just get DDNS and just type the url into a resolver to get the IP address, something like this:
    http://tracert.com/resolver

    then use it in the entelliweb or whatever delta is using as application...
  31. Replies
    4
    Views
    610

    Envision by itself will not allow the pages to be...

    Envision by itself will not allow the pages to be viewed via a web browser.
    You can use BCM-WEB, or get the latest version of Alerton software called Compass that now replaces Envision.
    good luck.
  32. Replies
    3
    Views
    425

    Rover is not for reading the BCU, it is for...

    Rover is not for reading the BCU, it is for reading and setting up comm5 field devices, vav, heatpump, fancoil, etc.
    For BCU you need Trane's Tracer Summit software, no way around it that I know....
  33. Replies
    4
    Views
    423

    sounds more like the device is resetting, but...

    sounds more like the device is resetting, but what scroo is saying may be true as well. How a device behaves on comm loss is really what the manufacturer decides to code in.

    Unfortunately you are...
  34. Replies
    1
    Views
    482

    regarding the max COV subscription, this is...

    regarding the max COV subscription, this is normally set by manufacturer of the device. Typically is non-changeable or should not be changed.
    it basically means the head end/or another bacnet peer...
  35. Replies
    3
    Views
    442

    Ok, thanks.

    Ok, thanks.
  36. Replies
    3
    Views
    442

    Distech dealer in North West US

    Anyone know who the Distech dealers are in North west US? Washington state/Seattle area?
  37. will do, thx

    will do, thx
  38. FX-PCT Programming & Commissioning Tool Manual

    Can someone please send me the programming/userguide for FX-PCT Programming & Commissioning Tool?
    I have not worked with any of this line and would like to start reading about how they are...
  39. Replies
    4
    Views
    367

    when you are in the main device manager table...

    when you are in the main device manager table window there is one of the menus on top, I think it says renumber vlcs, that is where you go.
    Sorry I am just going by memory it has been years since I...
  40. Replies
    4
    Views
    367

    If I remember right, in envision under device...

    If I remember right, in envision under device manager, you discover the vlcs and then in one of the menus you can renumber(change device id)
    Do not remember the exact procedure but I know it starts...
  41. Replies
    18
    Views
    1,114

    I tend to agree with crab, certainly looks like a...

    I tend to agree with crab, certainly looks like a LON card, the thick chip is usually the FT-10 transceiver chip. And looks like third terminal is unused.

    good luck.
  42. most of bacnet software that I run, locks up...

    most of bacnet software that I run, locks up port for other applications, i could never figure out why they do this, has it something to do with winpcap or such?
  43. Replies
    26
    Views
    2,460

    I actually prefer a coupler, so if someone messes...

    I actually prefer a coupler, so if someone messes with the switch you just lose one switch.
    Although I myself have yet to mess with Dali and don't know the topology or how it handles a short on the...
  44. Replies
    26
    Views
    2,460

    thx. is there a toggle mode in the coupler as...

    thx.
    is there a toggle mode in the coupler as well? were only one contact can be used, like a flip/flop action?
  45. Replies
    26
    Views
    2,460

    thx, would appreciate a pdf link to exact Pass...

    thx, would appreciate a pdf link to exact Pass Legrand 2 button Momentary
  46. Replies
    26
    Views
    2,460

    Dali field devices (swithes, etc.) were from...

    Dali field devices (swithes, etc.) were from Loytec or Eaton or?
  47. Typically but not always, the local device is...

    Typically but not always, the local device is also the Network interface. Typically you want the network interface to sit at domain zero, so it receives broadcast messages from everyone,...
  48. Replies
    5
    Views
    477

    +1

    +1
  49. Replies
    5
    Views
    533

    If it is a newer PCO, it is most likely was...

    If it is a newer PCO, it is most likely was programmed with the "1 Tool". this is the Carel's latest programming software.
    It is not freely available, and usually only restricted to manufacturers....
  50. Replies
    5
    Views
    477

    I didn't see anywhere in there how you setup the...

    I didn't see anywhere in there how you setup the BACnet side of things, like object types and IDs?