Search:

Type: Posts; User: pault

Page 1 of 2 1 2

Search: Search took 0.01 seconds.

  1. Replies
    5
    Views
    352

    Inhibit will not hide already raised alarms, it...

    Inhibit will not hide already raised alarms, it will just stop their state change, i.e. inhibited active alarms will not return to normal during maintenance works.
  2. Replies
    5
    Views
    352

    Look on "Alarm Inhibit" property on Alarm...

    Look on "Alarm Inhibit" property on Alarm Extensions. All you have to do is to change it to "true" for the maintenance period and alarm will be deactivated.
    If you want to control a group of alarms,...
  3. Replies
    21
    Views
    2,527

    In a strict sense, non-A modules are Lon devices...

    In a strict sense, non-A modules are Lon devices (they do communicate via FT10 and could be commissioned using standard tools), but they are not LonMark devices and have no SNVTs, except a couple...
  4. Replies
    21
    Views
    2,527

    Do you have Xenta 401 there (controller) or just...

    Do you have Xenta 401 there (controller) or just modules like 411, 421, 451 ?
  5. Replies
    4
    Views
    427

    Good catch. I remember I saw something similar...

    Good catch. I remember I saw something similar with another lon module (lonTac.jar maybe?) -- looks like Tridium sometimes includes devices with the same ProgramId in multiple lon files. Probably...
  6. Replies
    4
    Views
    427

    Looks like Add dialog box failed, because...

    Looks like Add dialog box failed, because somewhere deep inside it's java code something tries to create enum with two identical tags -- hard to say why it happened. Have you tried to restart the...
  7. Replies
    11
    Views
    601

    FTP method should be absolutely fine.

    FTP method should be absolutely fine.
  8. Replies
    4
    Views
    352

    Points imported from other devices into Jace also...

    Points imported from other devices into Jace also will appear in Lon Link Manager. If they are not bound, Jace uses polling to read them. If bound, Jace receives updates when other devices decide to...
  9. This is much quicker indeed.

    This is much quicker indeed.
  10. Or you could open Slot view of your room folder...

    Or you could open Slot view of your room folder and add a new String slot. The value could be entered in Properties view.
  11. Thread: VykonPRO module

    by pault
    Replies
    34
    Views
    5,679

    Sent

    Sent
  12. Thread: VykonPRO module

    by pault
    Replies
    34
    Views
    5,679

    Can't see your e-mail

    Can't see your e-mail
  13. Replies
    8
    Views
    877

    Voyant is Distech, OEM version. So you could get...

    Voyant is Distech, OEM version. So you could get completely identical Distech controller, except for blue cover, not a grey one.
  14. Replies
    6
    Views
    1,213

    I can't comment on this, but it seems legit....

    I can't comment on this, but it seems legit. Schneider has a lot of lines all over the world and it is a pain to support them. So they created Struxureware to use it as an integration platform for...
  15. Thread: Alerton Controls

    by pault
    Replies
    9
    Views
    1,791

    If I remember correctly, SA-651 is not...

    If I remember correctly, SA-651 is not programmable, just configurable using Microset unit. TX653P and APLC are programmable. You need TDS software and AC-2650 cable. You may try to create this cable...
  16. Replies
    1
    Views
    930

    I think the driver is available for Tridium...

    I think the driver is available for Tridium Niagara AX from a third-party developer. Haven't tested it myself.
  17. Replies
    4
    Views
    1,734

    Do you have mobile.jar in your installation?

    Do you have mobile.jar in your installation?
  18. Replies
    10
    Views
    2,217

    try command "sudo su" before running install...

    try command "sudo su" before running install script
  19. Replies
    10
    Views
    2,217

    I was able to install AX on Ubuntu quite quickly....

    I was able to install AX on Ubuntu quite quickly. What are your problems?
  20. I don't ask about client's details, just a...

    I don't ask about client's details, just a general description. Why start the thread if you can't tell anything, except how good your appliances are?

    348381
  21. Could you give an example for such cloud-based...

    Could you give an example for such cloud-based system? What SCADA-software is used? Was it hosted on some popular cloud (Amazon AWS, Google Engine, Microsoft Azure)?
  22. Replies
    4
    Views
    554

    Confirm

    Confirm
  23. Replies
    2
    Views
    577

    Xentas talk LON directly, but they have to be...

    Xentas talk LON directly, but they have to be specially programmed for LonMark-compatible communication. Without it you won't be able to see any points.
  24. Thread: Tridium shakeup

    by pault
    Replies
    8
    Views
    1,254

    Somebody new:...

    Somebody new: http://twitter.com/NiagaraDev/statuses/250218389518315521
  25. Replies
    41
    Views
    5,104

    Are you sure there is more than one? I mean they...

    Are you sure there is more than one? I mean they are TOO similar :)
  26. Thread: Visiologic

    by pault
    Replies
    3
    Views
    1,086

    Maybe it is Alerton VisualLogic programming...

    Maybe it is Alerton VisualLogic programming environment? Indeed it works as Visio plug-in.

    Alerton has a Programming Guide or something similar, describing all commands with few examples. Anyway,...
  27. Replies
    13
    Views
    2,581

    That might be a problem :) Niagara is a quite...

    That might be a problem :)
    Niagara is a quite big framework with some not so simple mechanisms.

    I recommend you to build a very simple command line WS client first (without any Niagara stuff)...
  28. Replies
    13
    Views
    2,581

    You could use any generic Java web service...

    You could use any generic Java web service library (e.g. JAX-WS 2.0) to build SOAP client for Niagara.
  29. Replies
    2
    Views
    766

    Exactly. You have to be more explicit than that.

    Exactly.
    You have to be more explicit than that.
  30. Replies
    8
    Views
    1,368

    > What will tridium do with out java ??? Java...

    > What will tridium do with out java ???

    Java is gone and I haven't noticed? :)
  31. Thread: Alerton to AX

    by pault
    Replies
    8
    Views
    1,516

    I will need VisualLogic to program BCM. And...

    I will need VisualLogic to program BCM. And probably IBEX TDS to read programs from existing controllers in case there are no point lists available.
  32. Replies
    2
    Views
    730

    It is possible, sure. But I don't think CSV...

    It is possible, sure. But I don't think CSV driver will help you here.
    You have to look on Program service and write a script to create / configure whatever you want. It does require Java knowledge.
  33. Replies
    10
    Views
    1,273

    I haven't used it personally yet, but I know...

    I haven't used it personally yet, but I know people who used it successfully. Not with Staefa driver though.
  34. Replies
    10
    Views
    1,273

    NorthBT also have some drivers for Staefa legacy...

    NorthBT also have some drivers for Staefa legacy systems. You could use their Compas system as a gateway to some standard protocol like BACnet.
  35. Replies
    10
    Views
    1,273

    There is a third-party Staefa Smart II driverfro...

    There is a third-party Staefa Smart II driverfro AX. Don't know if it will be good for you.
  36. Replies
    10
    Views
    1,273

    And which Desigo version you have?

    And which Desigo version you have?
  37. Replies
    10
    Views
    1,273

    Could you elaborate a little more on how NCRE/A's...

    Could you elaborate a little more on how NCRE/A's are currently connected to Desigo PC?
  38. Replies
    31
    Views
    3,858

    I've got mine for free in the past, but I've got...

    I've got mine for free in the past, but I've got your point.

    Still I find it unreasonable to demand free SSL from Tridium, because many others web-enabled device vendors do not have this feature...
  39. Replies
    31
    Views
    3,858

    Interesting, I've got it for free (in Europe). ...

    Interesting, I've got it for free (in Europe).

    Have you got a certificate from them?
  40. Replies
    31
    Views
    3,858

    Because one has to buy a certificate from...

    Because one has to buy a certificate from certificate authority -- this is how SSL works. You don't know this also? Really? :)

    P.S. Tridium does not charge for SSL.
  41. Replies
    31
    Views
    3,858

    I'm curious how do you know it, if you clearly...

    I'm curious how do you know it, if you clearly have a very limited (if any) experience with Niagara? I could tell because you don't know about 3.6 release and you don't have access to RSA...
  42. Replies
    8
    Views
    1,717

    SketchUp is very good for 3D floor plans.

    SketchUp is very good for 3D floor plans.
  43. Replies
    31
    Views
    3,858

    Tridium just published it's description of the...

    Tridium just published it's description of the matter. It is basically "if you give an access to the whole file system -- don't be surprised that any file could be downloaded". No hidden bugs or...
  44. Replies
    31
    Views
    3,858

    Looks quite cheap. "To a hacker such as Rios,...

    Looks quite cheap. "To a hacker such as Rios, that was virtually no security at all", “within five minutes, I’ve found what I’m looking for”.

    Looks like he found how to download config.bog, which...
  45. Maybe some random bug. It happens.

    Maybe some random bug. It happens.
  46. The ord (address) of the point should not contain...

    The ord (address) of the point should not contain degree symbol. The "units" facets could have degree F, it is not a problem.

    Could you let us see the name of the point you are trying to import?
  47. It looks like there is a symbol 0xba (degree) in...

    It looks like there is a symbol 0xba (degree) in point's ord, which is not allowed.
    Could you check this ord?
  48. Replies
    70
    Views
    5,513

    Just one short remark. Loytec itself states that...

    Just one short remark. Loytec itself states that their WCP Certificate is the same as BTL Certificate: http://loytec.com/en/products/btlcertified
  49. Thread: Alerton Experts?

    by pault
    Replies
    18
    Views
    1,505

    That's odd, AI or AV are supposed to be used for...

    That's odd, AI or AV are supposed to be used for such values.

    Anyway, have you tried to open standard Envision templates to see all objects in instance 1? The values you want to get might be...
  50. Thread: Edison Awards

    by pault
    Replies
    7
    Views
    704

    They explain their reasons:

    They explain their reasons: