Search:

Type: Posts; User: sdt1104

Search: Search took 0.00 seconds.

  1. Replies
    9
    Views
    736

    Amigo is correct, you will have to use your...

    Amigo is correct, you will have to use your programing tool to replace the neuron ID with the new and send the config data to the new controller. We use MCL Tool.
  2. Replies
    1
    Views
    300

    What software version are you running Lon or BAS...

    What software version are you running
    Lon or BAS
    Usually all files are on the server and the workstation will access the system through the server. The files on the work station are usualy data...
  3. Did you contact Kele? They shoud have one that...

    Did you contact Kele? They shoud have one that goesa to zero, I know they make two styles of the wireless sensors, a 40dF and a 0dF.
  4. Thread: MO99 Retro

    by sdt1104
    Replies
    10
    Views
    1,482

    The global warming potential of MO99 is much...

    The global warming potential of MO99 is much worse than 407C. I am at government facility, and our environmental affairs department would not OK MO99 for that reason, we are using 407C. We have done...
  5. An after thought - life safety alarms will have...

    An after thought - life safety alarms will have the same affect. Check you smoke and fire safties.
  6. I have seen this qiute bit in our system. When...

    I have seen this qiute bit in our system. When power is applied the display remains dark. In the power cabinet the pirmary contactor coil is bad. when you cycle power on this contactor closes to...
  7. Replies
    53
    Views
    23,436

    Copeland is shipping R22 compressor with POE...

    Copeland is shipping R22 compressor with POE installed. Had to get the last one shipped in from California, they are available. We are using 407C because it is more environmentally friendly...
  8. Replies
    7
    Views
    1,139

    We looked at converting to MO 99, the Global...

    We looked at converting to MO 99, the Global Warming Potential is almost as bad a R22. 407C has a much lower Global Warming Potential, which made our Enviromential Affairs Department happy. We have...
  9. Replies
    16
    Views
    1,862

    Engineers are like teenagers you don't have to...

    Engineers are like teenagers you don't have to tell them anything cause they already know it all.
  10. Replies
    61
    Views
    5,715

    John Merkyl is correct it is common the place...

    John Merkyl is correct it is common the place srpinklers under coils in Texas. Had a facility with an 8 foot wall arouund the roof to hide equipment and block any breeze. When it hit 105 the rooftop...
  11. Replies
    4
    Views
    692

    Aerokroil in an excelland penatrating oil, made...

    Aerokroil in an excelland penatrating oil, made by Kono Labs. We use it quite a bit.
  12. Replies
    8
    Views
    1,226

    As a rule R22 does not care what oil is in the...

    As a rule R22 does not care what oil is in the system, even when retrofitting from R22 to 407C a residual of 5 % mineral oil is allowable. You may have to replace the driers once or twice, otherwise...
  13. Replies
    67
    Views
    6,543

    The global warming potential of "MO99" is 2265,...

    The global warming potential of "MO99" is 2265, and with 407C it is 1770. I think MO99 global warming potential may be worse than 22.

    Maybe this will be of help with the alternative refrigerants....
  14. Replies
    24
    Views
    3,504

    407 C

    407c is the closest match for mid range cooling
    does not require an agressive oil change, change the compressor oil, residual oil will not affect operation.

    http://www.nationalref.com/
Results 1 to 14 of 15
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine
Comfortech365 Virtual Event