Search Results - HVAC-Talk: Heating, Air & Refrigeration Discussion

Search:

Type: Posts; User: motorsport

Search: Search took 0.00 seconds.

  1. Mnl controllers are fully programable so you will...

    Mnl controllers are fully programable so you will have to get the program out of the old controller and download it to the new controller with WPT.
  2. Replies
    2
    Views
    403

    It's an open licensed vycon branded Softjace or...

    It's an open licensed vycon branded Softjace or websup.
    Probably a Softjace with windows 7.
  3. You can use numeric Totalizer ext from kitcontrol...

    You can use numeric Totalizer ext from kitcontrol
    Drop it on the kw block change the properties from
    Minutes to hour composite out the total slot and then
    Link that to another numeric writable...
  4. Thread: JCI plugins

    by motorsport
    Replies
    2
    Views
    602

    JCI plugins

    Does anybody know if the plugins for jci branded distect lnprg 8a,8b and
    12a controllers will work on a non jci jace (vycon branded) if so does any body have
    them.
    Thanks in advance
  5. Replies
    3
    Views
    436

    Thanks guys They are series boxs with floating...

    Thanks guys
    They are series boxs with floating actuated for baseboard I can alter
    For what I need I just was not sure how to establish flow stpts since
    It takes a min and max in % not cfm I am...
  6. Replies
    3
    Views
    436

    distect vcp vav

    Hello all
    Does any body have a working program for a vcp vav
    In gfx and possibly a bog file of the points for ax.
    I will make it worth your while
    Thanks
  7. Replies
    15
    Views
    1,262

    Can you commission and bind the controllers with...

    Can you commission and bind the controllers with no problem
    had a Similar problem but the controller would fail commissioning there are updated jar files for certain mp580s depending on board date...
  8. Replies
    1
    Views
    486

    Jace Ndio Thermistors

    I need to make tabular chart to read 10k ohm thermisters with a 11k shunt.I have the chart from-40 to 200 degC in a exxel chart how can i convert the chart to xml so i can import it into the tabular...
  9. Check your Email

    Check your Email
  10. Replies
    3
    Views
    921

    what version of niagara

    what version of niagara
  11. I may be able to help you email in my profile

    I may be able to help you email in my profile
  12. Replies
    5
    Views
    534

    Thanks Everyone Found the problem 1when you use...

    Thanks Everyone
    Found the problem 1when you use the net2 addapter it is only 10 mbps net1 is 100 mbps the jaces were on a a switch that did not ajust to the speed it was on 100 mbps.2 for some...
  13. Replies
    5
    Views
    534

    Jace2 net adapters

    Has anyone had problem with using the second net adapter for there primary
    connection I have a few out there that I left the default ip info on net1 and put my connection info on net2.I am having...
  14. Replies
    1
    Views
    466

    EPM 6000 Power Meter

    Any one able to get the pulse output from a epm6000 the terminal are kyz but it says it will send a pulse output but cant get it working.Thanks in advance.
  15. Replies
    2
    Views
    355

    Obix driver can pull the Schuedule that is in the...

    Obix driver can pull the Schuedule that is in the r2 jace into ax.This is a little
    tuff to get going but it works very well you can see the Schuedule in r2 as well as ax it comes in as a...
  16. Replies
    7
    Views
    843

    If you do decide to take the risk make sure you...

    If you do decide to take the risk make sure you keep the same wire thru out the bus most likely 18 gauge trane purple wire and use i think they are 82.5 ohm terminaters make sure your ohm readings on...
  17. Replies
    1
    Views
    402

    Trane BCU Forsale

    bmtw with comm 3,4,5 card also has I/O module and webserver.
    My email is in my profile
  18. Replies
    17
    Views
    2,438

    If you are trying to use xp good luck,let me know...

    If you are trying to use xp good luck,let me know if and how you do it
    I have had no luck with this on anything other than win 98 machine.
  19. Thread: Distech gfx

    by motorsport
    Replies
    4
    Views
    762

    Has anybody heard about any issues with bindings...

    Has anybody heard about any issues with bindings with the gfx.I am on 3.3.22 ax and my vcp vavs go nuts after i bind in and out of comm fail if i leave them unbound they seem to work alot better but...
  20. Replies
    1
    Views
    376

    Paulir, Just curious have you tried to not bind...

    Paulir,
    Just curious have you tried to not bind the controller,I am having similar issues with ecp-vav gfx but my points are also going in and out of com fail
    If i dont bind the controller just...
  21. Replies
    14
    Views
    1,368

    Zandman, Were you able to make the two...

    Zandman,

    Were you able to make the two stations talk.If so try the schedule and alarming features. I have been using them a lot.

    motorsport
  22. Replies
    14
    Views
    1,368

    Zandman, Did you get the databases and jars...

    Zandman,

    Did you get the databases and jars that i sent you.
  23. Replies
    14
    Views
    1,368

    Yes I can send you the databases but you will...

    Yes I can send you the databases but you will have to have ax version 3.2 or higher and obix license on the ax station this is free as far as I know.You also need r2 version 522 and the license for...
  24. Replies
    14
    Views
    1,368

    control tech

    I have 25 or so uncs(r2 jaces) with a supervisor and 15 ax jaces with a supervisor and obix is working well although I am mostly going from r2 to ax it is possible to export ax points to r2.If you...