    I have had a few of the older WCI's that decide...

    I have had a few of the older WCI's that decide they are not going to join the network for seemingly no reason, replaced them with new and starts working. I know Trane is now coming out with an...
  4. Replies
    18
    Views
    1,171

    It has been my experience that for whatever...

    It has been my experience that for whatever reason BACnet / Ethernet doesn't work in some cases, and have found that the BACnet / IP connection is more successful. Although agree it should work, a...
  5. Replies
    18
    Views
    1,171

    you use the BCUconfig.exe and you use a RS-232 to...

    you use the BCUconfig.exe and you use a RS-232 to RJ-11 cable. the mini-monitor port is in a couple different places depending on your Which flavor of BCU you have. But they are all marked...
  6. Replies
    18
    Views
    1,171

    Program files>TracerSummit>Bin>BCUConfig.exe ...

    Program files>TracerSummit>Bin>BCUConfig.exe This is the tool used to set and IP in the BCU. You connect to the mini monitor port on the BCU and download IP info.
  7. Replies
    35
    Views
    5,135

    Found one :)

    Found one :)
  8. Replies
    35
    Views
    5,135

    does anyone know where i can buy one online?...

    does anyone know where i can buy one online? Their websites says a few places near me that sell them but they don't actually carry it
  9. Replies
    4
    Views
    772

    does it not compile all the info on the app? i...

    does it not compile all the info on the app? i only have the temp module that logs, so when i pull a report on the fluke connect app it only shows the temp readings.
  10. Replies
    4
    Views
    772

    Fluke Connect

    i recently got the Fluke FC-3000 DMM and the Temperature module to go along with it. HOLY CRAP is this thing sweet. I love the functionality of fluke connect so far. Really cool Stuff!
  11. are you giving that SC away for free????? :grin2:

    are you giving that SC away for free????? :grin2:
  12. I love an good SC upgrade but a BAS R'Newal to a...

    I love an good SC upgrade but a BAS R'Newal to a BMTX might be a more cost effective solution.
  13. Replies
    19
    Views
    1,814

    AHA...Well like I said I know in Tracer SC you...

    AHA...Well like I said I know in Tracer SC you get default alarm classes of :

    1 - HVAC - Critical
    2 - HVAC - Service Required
    3 - HVAC - Warning
    4 - HVAC - Information
  14. Replies
    23
    Views
    3,309

    Crazy enough yesterday I had a customer Give me...

    Crazy enough yesterday I had a customer Give me this laptop bag for free...And I can honestly say its the best one I have had yet! its HUGE but not difficult to carry. Tons of room I REALLY like it....
  15. Replies
    19
    Views
    1,814

    as far as I know Trane does them as follows: ...

    as far as I know Trane does them as follows:

    1 - HVAC - Critical
    2 - HVAC - Service Required
    3 - HVAC - Warning
    4 - HVAC - Information
  16. Replies
    19
    Views
    1,814

    Are you using Tridium? wouldn't you setup the...

    Are you using Tridium? wouldn't you setup the notification classes in tridium? I think the alarms are just alarms and you decide what notification class you want them to be routed to. I could be...
  17. Replies
    23
    Views
    3,309

    Well where is Veto, lets get them in here and...

    Well where is Veto, lets get them in here and provide some feedback so they can make a sweet laptop backpack geared towards control technicians!
  18. Replies
    21
    Views
    3,027

    I have had This happen to me a few times...Is the...

    I have had This happen to me a few times...Is the Dynaview in direct sunlight? I have seen people put a sun shield above them to keep the sun from overheating the display. Its strange though i have...
  19. Replies
    17
    Views
    1,637

    Make sure that in Rover configuration your Supply...

    Make sure that in Rover configuration your Supply temperature is indeed setup to "fail at end of range". There is a little checkbox in the config that needs to be checked otherwise the fail logic in...
  20. Replies
    44
    Views
    4,099

    Tracer summit is a great product with Many...

    Tracer summit is a great product with Many options available for future upgrades. Trane is now offering help with planning financially for how to upgrade and replace as needed if you are interested...
  21. Replies
    17
    Views
    1,637

    .

    .
  22. Replies
    17
    Views
    1,637

    Integral you mean? Just Take whatever your "P" is...

    Integral you mean? Just Take whatever your "P" is (hopefully an AV) and run that into a divide block, Divide by 4. Take the output of the math block and run it into the "I". Then adjust your "P" as...
  23. Replies
    13
    Views
    1,628

    The Chillers either have and LCI card or...

    The Chillers either have and LCI card or something of that nature communicating with the BCU Via lon or and older protocol. They are probably using the BCU so they can Run chiller Plant manager to...
  24. You could also have used a BO in Tracer Summit...

    You could also have used a BO in Tracer Summit that was referenced to a Schedule or possibly some CPL....I like Carrier1's Logic though .
  25. Replies
    17
    Views
    1,637

    I agree, This is Exactly what Trane recommends....

    I agree, This is Exactly what Trane recommends. Use the Plot function in TGP to help you, also add the feedback input into the PID.
  26. Replies
    44
    Views
    4,099

    I'm Glad to hear you found someone at Trane to...

    I'm Glad to hear you found someone at Trane to work with. If you are looking into upgrading this building eventually, you should talk with your Trane Rep about the Tracer SC and the Legacy bridge....
  27. Answering my own question....I didn't notice that...

    Answering my own question....I didn't notice that now in the new station wizard "Use secure connection" is checked off by default.
  28. cant open Fox connection port 1911 in tridium

    I have not used tridium AX in over a year but im wondering if something has changed, I can open a secure fox connection or log on via a webpage with HTTPS but in workbench the regular old fox 1911...
  29. Replies
    5
    Views
    690

    If you think the 581's are hard wait til you get...

    If you think the 581's are hard wait til you get to the 580's :grin2:
  30. Gave that a shot, still doesnt like it. Definetly...

    Gave that a shot, still doesnt like it. Definetly must be something in the ASD driver that doesnt like the path
  31. Infocon ASD driver export tags not working

    I am using the Infocon ASD driver and trying to use export tags. Setting any export tags in the ASD network provides me with naming errors below. If i set up a point under the lon network or bacnet...
  32. Replies
    6
    Views
    950

    i dont have a model # or anything but those are...

    i dont have a model # or anything but those are some really good answers and i have a lot to go on now thank you all for the help
  33. Replies
    1
    Views
    507

    AX Load Shedding

    had anyone used the EDL shedding logic in kitControl? I am trying to use it but im having difficulties understaning it all (cause im an idiot!:putergreet:) is there a .bog of a job someone did or...
  34. Replies
    11
    Views
    3,668

    wow that would be super useful can i have a copy...

    wow that would be super useful can i have a copy too?
  35. Replies
    0
    Views
    435

    Thermostat to use with Jace io board

    does anyone know of a digital stat that has temp setpoint and temp feedback that will work directly to an IO board? im trying to save myself from running a bus for a BACnet or lon stat. Thanks in...
  36. Replies
    6
    Views
    950

    Older Unit heater Venting qeustion

    Hello all,

    Ive got an older atmosheric type gas fired unit heater that I got from and old warehouse I used to work at and now I want to install it in a garage, My qeustion is I am not super...
  37. Replies
    5
    Views
    1,548

    where is you area?

    where is you area?
  38. i was just reading something on alerton support...

    i was just reading something on alerton support network website today about WEBtalk VM for windows 7, theres a zip file with instructions on how to do it and the executables you need.
  39. Replies
    12
    Views
    1,725

    yea i get on the android once in awhile too. but...

    yea i get on the android once in awhile too. but agreed it def isnt easy to navigate.
  40. Replies
    12
    Views
    1,725

    HVAC-Talk Mobile???

    wouldnt that be sweet?
  41. Replies
    7
    Views
    1,703

    need ice rink floorplan graphic

    i am looking for an ice rink surrounded by a square building, anyone have a decent floorplan kicking around for this?
  42. Replies
    6
    Views
    766

    yea sounds like that users profile is set to unit...

    yea sounds like that users profile is set to unit conversion to C. does it work fine if you log in using a different user?
  43. im not very familiar with delta but its LON...

    im not very familiar with delta but its LON right? and are you talking they "lock up" like the bus drops out? or the jace actually has an actual "crash"?
  44. Replies
    13
    Views
    1,295

    i talked to tridium and they say that R2 doesnt...

    i talked to tridium and they say that R2 doesnt support SSL authentication.
  45. Replies
    13
    Views
    1,295

    you my friend have made my day! thank you!

    you my friend have made my day! thank you!
  46. Replies
    13
    Views
    1,295

    ahhhh i am going to call tridium tomorrow and get...

    ahhhh i am going to call tridium tomorrow and get the ssl enabled, then ill be able to use gmail thank you!
  47. Replies
    1
    Views
    401

    routing alarms from r2 to AX

    I have a large site that has multiple r2 jaces and an r2 supervisor, there are also a few AX jaces with an AX supervisor. To make a long story short im trying to get emails out and am unable to use...
  48. Replies
    13
    Views
    1,295

    well when i inherited this sites issues the...

    well when i inherited this sites issues the postcast server free edition was on there and i dont know it just ddint seem to work very well, then so many people have had their hands in it i was just...
  49. Replies
    13
    Views
    1,295

    ya the research ive been doing shows me that im...

    ya the research ive been doing shows me that im kinda screwed lol. Any smtp servers out ther that dont require SSL?
  50. Replies
    13
    Views
    1,295

    using gmail as smtp host in r2

    hello all

    i have an r2 site where they were using a program < postcastserver > that uses the actual supervisor machine as the smtp server and it works like crap. So i was messing around today...