Search:

Type: Posts; User: ntech64

Page 1 of 3 1 2 3

Search: Search took 0.01 seconds.

  1. Replies
    3
    Views
    977

    CAREFUL! Older MMI cables had a RJ11 (phone)...

    CAREFUL!

    Older MMI cables had a RJ11 (phone) end on them that accepted only 4 pins. The PXC series requires a RJ11 end that accepts 6 pins. There isn't any wires in the pin slot on each end, but...
  2. Replies
    37
    Views
    4,031

    ::DD:

    ::DD:
  3. Replies
    4
    Views
    672

    If you don't already know programming (or...

    If you don't already know programming (or scripting) from being in IT, then take a basic programming course to get the concepts down. Other than that, you'll have at least a passing familiarity with...
  4. Check for a receive light at a TEC. If you...

    Check for a receive light at a TEC.

    If you have one, then check your FLN baud rates.

    If not, make sure your FLN wires didn't get cut.

    Otherwise, you may have a bad MEC. There's only one UART...
  5. Replies
    4
    Views
    2,277

    This one is essential: TLA - Three Letter...

    This one is essential:

    TLA - Three Letter Acronym
  6. Replies
    2
    Views
    639

    How is server virtualization going to help system...

    How is server virtualization going to help system performance?
  7. Replies
    18
    Views
    4,319

    That version of the AEM Configuration Tool does...

    That version of the AEM Configuration Tool does not support the new AEM 2100. Manually configure the AEM using HyperTerminal.
  8. Replies
    18
    Views
    4,319

    What are the errors? What are you using to...

    What are the errors? What are you using to "download" to the AEM?

    :confused:
  9. Replies
    18
    Views
    4,319

    AEMs are just configured with a 9 pin to 9 pin...

    AEMs are just configured with a 9 pin to 9 pin null modem cable and Hyperterminal.

    Follow the Getting Started for "Setting Up APOGEE Ethernet Microserver". It should be darn close to seting up the...
  10. This virus attacks Siemens Industrial Control...

    This virus attacks Siemens Industrial Control Systems software. The Building Automation Software is safe... for now.
  11. Replies
    20
    Views
    3,399

    ????? :eek2: ?????

    ????? :eek2: ?????
  12. Replies
    9
    Views
    1,575

    Some systems index the device's information using...

    Some systems index the device's information using the device instance number. He may be running into an issue like that. I also have to agree with BACnet that unique instance numbers should be used...
  13. Replies
    4
    Views
    784

    Microsoft SQL Server also requires less...

    Microsoft SQL Server also requires less administration. A huge point of contention for me is that Oracle doesn't have the ability to auto-increment a table index without using sequences... which is a...
  14. Replies
    5
    Views
    1,390

    When you say "configuration" are you talking...

    When you say "configuration" are you talking about the different applications? (2023 = VAV with Hot Water Reheat)

    I'm pretty sure there's a different PDF for each TEC application. What application...
  15. Replies
    15
    Views
    2,653

    As BSunday21 noted, there are sometimes issues...

    As BSunday21 noted, there are sometimes issues with older firmware revisions co-existing with newer revisions. Generally, Siemens can provide a firmware build upgrade (not a major revision upgrade)...
  16. Replies
    37
    Views
    4,031

    The MicroTech II's are finicky devices... Make...

    The MicroTech II's are finicky devices...

    Make sure the devices have consecutive MAC addresses.
    I've sometimes had trouble writing setpoints at any priority other than 8.
  17. Thread: Daikin BACNet

    by ntech64
    Replies
    13
    Views
    2,091

    I've definitely done it before. It was a couple...

    I've definitely done it before. It was a couple of years ago and I don't remember the specifics, but I'll call BS on the Daikin rep.
  18. Replies
    6
    Views
    2,217

    Found this in the BACstac Installation Guide (see...

    Found this in the BACstac Installation Guide (see attached). I was only able to make sense of some of them... but it looks like there might be some settings buried in there that could help.
  19. Thread: Apogee/Reno

    by ntech64
    Replies
    38
    Views
    4,652

    RENO provides the ability to dial a prefix (ex....

    RENO provides the ability to dial a prefix (ex. dial 9 to get an outside number), so that part isn't a problem. However, I've heard of problems when people try to use something other than a pure...
  20. Thread: Apogee/Reno

    by ntech64
    Replies
    38
    Views
    4,652

    Default dipswitch settings should be fine. No...

    Default dipswitch settings should be fine. No modem programming... just Plug-and-Play.
  21. Default: 9600, 8, None, 1, None The speed may...

    Default: 9600, 8, None, 1, None

    The speed may have been changed... 38400 is the next one I would try.
  22. Thread: Apogee/Reno

    by ntech64
    Replies
    38
    Views
    4,652

    This should be all you need:...

    This should be all you need:
    http://www.belkin.com/IWCatProductPage.process?Product_Id=65387
  23. Thread: Apogee/Reno

    by ntech64
    Replies
    38
    Views
    4,652

    I don't think so... but it's been a little while...

    I don't think so... but it's been a little while since I've opened a new box.
  24. Thread: Siemens Apogee

    by ntech64
    Replies
    5
    Views
    1,371

    Contract customers get priority service... so it...

    Contract customers get priority service... so it might be worthwhile to get a contract if you think you may be requiring Siemens' services several times a year. Otherwise, you may be stuck with an...
  25. Thread: Apogee/Reno

    by ntech64
    Replies
    38
    Views
    4,652

    Reno likes external serial modems best... US...

    Reno likes external serial modems best...
    US Robotics V.92 External 56K Faxmodem - USR5686E
  26. Replies
    4
    Views
    1,405

    The newest version of Insight (3.10) also...

    The newest version of Insight (3.10) also includes a newer version of Cimetrics BACstac. The last few versions of Insight included various flavors of BACstac version 4.3, and Insight rev 3.10...
  27. Replies
    6
    Views
    2,217

    All of the settings are under: ...

    All of the settings are under:

    HKEY_LOCAL_MACHINE\SYSTEM\CurrentControlSet\Services\BACstac\Parameters

    ...but I'm not certain which one would pertain to this particular issue. Also, I've seen...
  28. Replies
    7
    Views
    1,085

    I'm pretty sure there are already some threads...

    I'm pretty sure there are already some threads about the differences between BACnet/IP and BACnet Ethernet... but you are correct in one regard and incorrect in another.

    BACnet Ethernet only deals...
  29. Replies
    7
    Views
    1,085

    Overall a good synopsis, but I think you have TCP...

    Overall a good synopsis, but I think you have TCP and IP confused. IP exists at Layer 3 of the OSI model. TCP and UDP are Layer 4 constructs that are used for connection oriented or connectionless...
  30. Replies
    1
    Views
    1,278

    Use the Insight Online Documentation. Getting...

    Use the Insight Online Documentation.

    Getting Started > Setting up AEM > Installation and Setup > Configuring an AEM 200
  31. Replies
    5
    Views
    1,226

    That's a lot of good information (emphasis on A...

    That's a lot of good information (emphasis on A LOT), but not all of it is pertinent to this particular situation.

    Siemens MBC and Insight2.8 ... front-end software on Win98
  32. Replies
    2
    Views
    486

    If the point shows up black on graphics, then...

    If the point shows up black on graphics, then either the point itself or the panel in which the point resides is failed. Check the panel for power and proper operation, wiring for the point, and any...
  33. I believe this is the "optimization" that's in...

    I believe this is the "optimization" that's in the RENO settings dialog box (last tab?). Turn off optimization and see if it corrects the issue.
  34. Replies
    20
    Views
    1,830

    I've seen integration to an Andover system via a...

    I've seen integration to an Andover system via a Modbus driver at the field panel level... BACnet Server would probably work if Andover supports it... but it's going to take some hardware or software...
  35. Replies
    20
    Views
    1,830

    ? I'm not sure I understand this question......

    ?

    I'm not sure I understand this question... Are we talking about BACnet Server Option? If so, the answer is no. BACnet Server Option requires a license to be purchased.
  36. Replies
    20
    Views
    1,830

    The Insight BACnet Client license is a "per...

    The Insight BACnet Client license is a "per server" not a "per seat" license. One license will cover the whole system.
  37. I don't have any experience with this particular...

    I don't have any experience with this particular meter, but you will be building it as an LPACI point once it's operational. Also, you may need a Pulse Scaler if the meter puts out a very high...
  38. Thread: Bacnet Network

    by ntech64
    Replies
    18
    Views
    2,447

    ^ This information is not correct. Chipkin's...

    ^ This information is not correct.


    Chipkin's website does have a lot of good info (see previous post).
  39. Thread: insight rev

    by ntech64
    Replies
    5
    Views
    1,010

    3.4 is only supported up to Windows 2000 SP2......

    3.4 is only supported up to Windows 2000 SP2... which is not only a very old operating system, but it is also not the latest SP for that OS.
  40. Thread: Insight

    by ntech64
    Replies
    18
    Views
    1,169

    Okay, I've attached some screen shots for this......

    Okay, I've attached some screen shots for this...

    hosts_sec.jpg

    Right-click on the hosts file and view the Security tab. You should see something like what's in the screen shot. If you see...
  41. Thread: Insight

    by ntech64
    Replies
    18
    Views
    1,169

    Probably. A reinstall of Insight wouldn't...

    Probably.



    A reinstall of Insight wouldn't be likely to cure this problem. A fresh OS might... but I'd rather fix the problem than spend the time reinstalling (personal preference).
  42. Thread: insight rev

    by ntech64
    Replies
    5
    Views
    1,010

    3.10 No. Two revs at a time. (3.4 > 3.6 >...

    3.10



    No. Two revs at a time. (3.4 > 3.6 > 3.8 > 3.10)



    No idea.
  43. Thread: Insight

    by ntech64
    Replies
    18
    Views
    1,169

    Can you ping the server by name or IP address?...

    Can you ping the server by name or IP address? Are there DNS servers defined if you type "ipconfig /all" at a command prompt? What are the permissions on the hosts file?
  44. Thread: Insight

    by ntech64
    Replies
    18
    Views
    1,169

    You issue sounds like the permissions on the...

    You issue sounds like the permissions on the hosts file got messed up.
  45. Thread: Insight

    by ntech64
    Replies
    18
    Views
    1,169

    System Profile uses name resolution to show PC's...

    System Profile uses name resolution to show PC's latched or unlatched. I'd check DNS and/or your hosts file (again) to see if everything's okay.

    If everything is listed with it's name and correct...
  46. Replies
    20
    Views
    1,830

    One Insight BACnet Server Option license will...

    One Insight BACnet Server Option license will cover the whole process. It's not a seat license like the ones required to open Insight.

    The access group is required in order to be able to pick and...
  47. Replies
    20
    Views
    1,830

    Once the option is installed, you'll have to...

    Once the option is installed, you'll have to choose what points are accessible via BACnet. Virtual panels are created with the appropriate BACnet objects within them. Be aware that if you have a lot...
  48. Replies
    3
    Views
    788

    What's the rumor? ...that Siemens is starting...

    What's the rumor?

    ...that Siemens is starting to make BACnet field panels and TECs? That's been the case for a while now.
  49. Replies
    14
    Views
    1,573

    It is true that the subpoints can only be in NONE...

    It is true that the subpoints can only be in NONE or OVRD... except when they are unbundled. Then they can be in any of the Apogee priorities (OPER, SMOKE, EMER, PDL). My example code was written...
  50. Replies
    14
    Views
    1,573

    If it won't accept commands except through OIP,...

    If it won't accept commands except through OIP, then the points probably aren't unbundled.