Search:

Type: Posts; User: pare

Search: Search took 0.01 seconds.

  1. Thread: VMA1420 Wc-adjust

    by pare
    Replies
    13
    Views
    476

    I've only done it with an NAE. You add the point...

    I've only done it with an NAE. You add the point as an AO but still map it to the AI address (E.G. AI2), this allows you to send the point a command. I don't know how it is done through a Jace. ...
  2. Thread: VMA1420 Wc-adjust

    by pare
    Replies
    13
    Views
    476

    You may have to play around with the priorities...

    You may have to play around with the priorities to see which one works.
  3. Thread: VMA1420 Wc-adjust

    by pare
    Replies
    13
    Views
    476

    Add the slider adjust point as an analog output...

    Add the slider adjust point as an analog output and command to zero. This should override the point in the vma.
  4. Thread: CO2 Sensors

    by pare
    Replies
    5
    Views
    637

    * Any mA or VDC signal will work.

    * Any mA or VDC signal will work.
  5. Thread: CO2 Sensors

    by pare
    Replies
    5
    Views
    637

    CO2 Sensors

    Hi,

    We have 50+ buildings and are looking at standardizing our brand and type of CO2 sensor. We currently have multiple brands/types (many of which need replacement or calibration). Moving...
  6. Thread: NAE Optimal Start

    by pare
    Replies
    0
    Views
    379

    NAE Optimal Start

    I went through the help file for an explanation of what the Temp Differential paramater does. It seems to have a few purposes but my question is this; If the occupied heating setpoint is 21 deg C...
  7. Thread: DX9100 AO

    by pare
    Replies
    2
    Views
    671

    Beauty. I appreciate the additional information....

    Beauty. I appreciate the additional information. Thanks again!
  8. Thread: DX9100 AO

    by pare
    Replies
    2
    Views
    671

    DX9100 AO

    If "Enable Limits" is TRUE and both the "High Limit %" and "Low Limit %" are set to 100% and "Output Forcing" is TRUE and the "Forcing Level %" is set to 0%, does the AO go to 0% or 100%? Which one...
  9. Thread: NCM Calendar

    by pare
    Replies
    2
    Views
    415

    Good to know. Thanks.

    Good to know. Thanks.
  10. Thread: NCM Calendar

    by pare
    Replies
    2
    Views
    415

    NCM Calendar

    I have an NCM 350 with an OWS running PMI 12.03. The sheduling calendar stops at May 2012. Is there a way to add more years to the calendar or am I $%@# out of luck?
  11. Replies
    10
    Views
    2,852

    Green. I sent you the diagram and figures.

    Green. I sent you the diagram and figures.
  12. Replies
    10
    Views
    2,852

    You need to know total load,btu's,gas press...

    You need to know total load,btu's,gas press delivered,length of run,meter size,etc.call the Gas co.They'll help you out.

    I do know all of this. I just need to know if I use 150 feet as my...
  13. Replies
    10
    Views
    2,852

    I don't know of any 24" rule. Scratch what I...

    I don't know of any 24" rule.

    Scratch what I said about the 24 inch rule. I guess what I mean is if you add an appliance, and this appliance is not added to an existing branch E.g. the piping is...
  14. Replies
    10
    Views
    2,852

    Thanks for your response. I originally wanted to...

    Thanks for your response. I originally wanted to branch off the manifold inside but soon realised (after checking B.149.1) that some piping would be undersized due to the new LMR. Branching right...
  15. Replies
    10
    Views
    2,852

    Gas Pipe Sizing Question

    Adding a Natural Gas fire pit in the backyard. If I connect the piping to the firepit within 24 inches of the regulator will other appliances be affected? E.g. If the current "Longest Measured...
  16. Replies
    3
    Views
    1,006

    Thanks Dave, I did read the part about the +/-...

    Thanks Dave,

    I did read the part about the +/- 8 K reset but the document wasn't clear on whether or not this was achieved with the 10 VDC signal. If it is, then would I be correct in saying that...
  17. Replies
    3
    Views
    1,006

    Johnson Controls TC-8803-8041

    I have a building with many of these. These stats have a setpoint reset via a 0 to 10 VDC input on terminals 3 and 4. I would like to know how many degrees the setpoint is reset by based on the 0...
  18. Replies
    3
    Views
    393

    Thanks guys.

    Thanks guys.
  19. Replies
    3
    Views
    393

    Scheduling from an NCM

    If I have Alternate and Holiday days set up in my scheduling calendar, however, I leave the holiday or alternate schedule blank for the object that I am scheduling, when a holiday or alternate day...
  20. Thread: JC BASIC

    by pare
    Replies
    3
    Views
    477

    Thanks. You're right, I just read the Binary...

    Thanks. You're right, I just read the Binary Output Object technical bulletin and it confirmed that this is the case. Maybe I should read more often... :rolleyes:
  21. Thread: JC BASIC

    by pare
    Replies
    3
    Views
    477

    JC BASIC

    I am commanding an output with 2 seperate programs. One commands the output at priority 5 and the other commands the output at priority 6. Obviously, both would be commanding the output, however,...
  22. Replies
    12
    Views
    883

    Sounds like what I need. The NAE is an NAE55. ...

    Sounds like what I need. The NAE is an NAE55.



    Good questions. I think I'm going to let the contractors deal with this one. We havn't payed them yet.

    Just a quick note. We originally...
  23. Replies
    12
    Views
    883

    It says: "Server: 3/11/2009 8:30AM EDT" I...

    It says: "Server: 3/11/2009 8:30AM EDT"

    I tried Archiving and resetting the NAE... time is still off. Figured a download would be just as affective. I have a feeling it's going to have to be...
  24. Replies
    12
    Views
    883

    This is correct, any known solutions? Besides...

    This is correct, any known solutions? Besides ripping out the NAE :)
  25. Replies
    12
    Views
    883

    NAE time discrepancie

    I have a stand alone NAE that was ver 3.1, recently got upgraded to ver 4.1. The dst is enabled. When I browse the NAE focus window it shows the correct local time, when i hover over the site name...
  26. Replies
    9
    Views
    772

    You certainly can. All you need are 10 VDC...

    You certainly can. All you need are 10 VDC relays. Not sure how familiar you are with GX9100 programming but here is how you do it:

    -Create all your schedules
    -Use all the digital outputs until...
  27. Replies
    4
    Views
    556

    Thanks!

    Thanks!
  28. Replies
    4
    Views
    556

    However it still backs up fine?

    However it still backs up fine?
  29. Replies
    4
    Views
    556

    NAE security database backup

    I have a few NEAs all at rev 4.1 and SCT 4.1. When backing up the security database everything works fine and the status comes out as ok. However, when I go to tools/administrator in SCT, the user...
  30. Replies
    15
    Views
    1,450

    -Upload the calibration -Go to "Edit"...

    -Upload the calibration
    -Go to "Edit" calibration
    -For 1000 ohm nickel: If the AI is reading lower than it should, subtract 13 counts per degree from both of that AIs calibration coefficients....
  31. Replies
    7
    Views
    851

    When you exit DX commissioning overides on...

    When you exit DX commissioning overides on outputs won't hold but overrides made to setpoints will. Even tho it says override you're actually just adjusting them. As for not being able to see all of...
  32. Thread: NAE upgrade

    by pare
    Replies
    3
    Views
    1,112

    Thanks

    Thanks
  33. Thread: NAE upgrade

    by pare
    Replies
    3
    Views
    1,112

    NAE upgrade

    I've read a few threads about not being able to update older NAEs to rev 4.1 because of a lack of b@lls. I remember seeing a list of all NAE part numbers that are not compatible with 4.1. I could...
  34. http://cgproducts.johnsoncontrols.com//MET_PDF/120...

    http://cgproducts.johnsoncontrols.com//MET_PDF/12011242.PDF
  35. Replies
    11
    Views
    4,030

    Yes. You can control, add and edit any point that...

    Yes. You can control, add and edit any point that resides in a panel from any panel provided that they are on the same BLN.
  36. Thread: NCM Upload

    by pare
    Replies
    10
    Views
    1,098

    O.K. I returned to the site today. Performed a...

    O.K. I returned to the site today. Performed a unddlf fms, unddl had no errors. Compared the ddl files to what was online, all seemed the same. Temporarily deleted the globrev.dbf, rebooted the...
  37. Thread: NCM Upload

    by pare
    Replies
    10
    Views
    1,098

    Already done.

    Already done.
  38. Thread: NCM Upload

    by pare
    Replies
    10
    Views
    1,098

    Are you sure there is no virus software running...

    Are you sure there is no virus software running
    or if the folder where the database resides has
    been changed to read only.

    I am sure there is no software virus software running however I am not...
  39. Replies
    4
    Views
    1,422

    It's been a while since I worked on Siemens but i...

    It's been a while since I worked on Siemens but i do beleive that the newer TECs have 4 digit application numbers. Application 25 is actually 2025. You must also make the application change on...
  40. Thread: NCM Upload

    by pare
    Replies
    10
    Views
    1,098

    O.K. I am not at the site but I do have the...

    O.K. I am not at the site but I do have the recent copy of the data folder. I found a Globrev.dbf file in the "network name".dob folder and in the "network name" folder. I did not find any .tmp...
  41. Thread: NCM Upload

    by pare
    Replies
    10
    Views
    1,098

    NCM Upload

    Good day fellows,

    I have an NCM that will not upload global data or perform an NC Upload. After forcing an upload twice I get the message "Selected device is not an NC". PMI Revision 9.01c, NCM...
  42. Replies
    1
    Views
    460

    Replacing an OWS computer for an NCM

    What is the correct procedure to follow when replacing the OWS computer on a network that has 1 NCM, direct connect? Can I install the PMI software, ddl the net file and models file, log onto the...
  43. Thanks guys

    Thanks guys
  44. Metasys Control system/Software Model discrepancies

    Hi,

    I tried to add a point to a CS object by modifying the associated Software Model. The software model saves the changes, however, the control system does not show the new point. How do I...
  45. Replies
    7
    Views
    2,702

    Yeah that's a dead end, I'm not a member. I did...

    Yeah that's a dead end, I'm not a member. I did however manage to get the patch through a local controls distributor. It's been working great thus far, I've only had to reboot the laptop once. ...
  46. Replies
    7
    Views
    2,702

    OK, I upgraded to 8.08. Now I need the patch....

    OK,

    I upgraded to 8.08. Now I need the patch. That link isn't working for me. Could you double check it?

    Thanks
  47. Replies
    7
    Views
    2,702

    Yeah I'm running XP Pro. I'm trying to...

    Yeah I'm running XP Pro.

    I'm trying to download the patch but the link that you provided me doesn't seem to work.
  48. Replies
    7
    Views
    2,702

    Connecting to the zone bus via HVAC Pro

    Hi,

    I have HVAC Pro release 8.06 installed on my laptop (windows XP). I use the edgeport serial/USB adapter and Cable Pro 3. I can upload and download ASCs when connected to the N2 bus with HVAC...