  1. If he is using RC-Studio 1.1 then they were...

    If he is using RC-Studio 1.1 then they were probably setup using Reliable's proprietary RCP protocol. To switch it to Bacnet you need RC-Toolkit and run the MSet program and configure each...
  2. Replies
    12
    Views
    1,740

    If it is a .mpb file then you have N30s and can...

    If it is a .mpb file then you have N30s and can open it using Project Builder. If it is an NCM you need to unddl the database and use Notepad like controlgeek said.
  3. Replies
    8
    Views
    607

    The MAC address identifies the device uniquely on...

    The MAC address identifies the device uniquely on that particular network segment or MSTP trunk. The Device instance identifies it uniquely across the entire Bacnet network which can include...
  4. Replies
    23
    Views
    1,569

    Reliable has the Mach Stat and Smart Space...

    Reliable has the Mach Stat and Smart Space Controller. Both Bacnet thermostat looking devices that are freely programmable with different I/O configurations. The SSC is the best bang for your buck...
  5. Propmanage, My company does alot of work both...

    Propmanage,
    My company does alot of work both install and service with JCI product. My email is in my profile if you are interested. We are located in Woburn.
  6. Replies
    9
    Views
    1,912

    Are you in edit mode? In RC-Studio I've noticed...

    Are you in edit mode? In RC-Studio I've noticed that it won't generally start polling info until you save the System Group.
  7. Replies
    5
    Views
    2,357

    Is therewith any issue with increased demand on...

    Is therewith any issue with increased demand on the controller you have cover subscriptions to? I.e. does a controller that is respond
    ing to cover point subscriptions work harderw than one that is...
  8. Replies
    5
    Views
    2,357

    Bacnet COV vs. Polling

    Does anybody have a preference between using COV subscriptions vs. polling for points using Bacnet protocol. I was always had the understanding that if a controller supported COV subscriptions then...
  9. Replies
    4
    Views
    685

    the device instance is set in the CCT program as...

    the device instance is set in the CCT program as part of the Define Hardware section.
  10. Replies
    12
    Views
    1,443

    tapatalk works with all v-bulletin based forums

    tapatalk works with all v-bulletin based forums
  11. Replies
    5
    Views
    1,288

    Th limit for the license is actually four so if...

    Th limit for the license is actually four so if you want five I suggest using a MSTP to IP router like the onefrom Contemporary Controls to bring that fifth port in using Bacnet/IP.
  12. Replies
    4
    Views
    970

    in CCT you can set the priority for the program...

    in CCT you can set the priority for the program to write to. It defaults to 16 (lowest) but I generally change it to 14 so that this doesn't happen. Then you can bring them in as writable and still...
  13. Replies
    29
    Views
    1,960

    They're defensive because we're all sick and...

    They're defensive because we're all sick and tired of how easy our job is - sitting on our a$$ staring at a computer screen all day. A new tech to a new site, anyone worth their salt would spend a...
  14. Replies
    27
    Views
    2,890

    That's like saying put a V8 in a Pinto and it...

    That's like saying put a V8 in a Pinto and it will drive like a Corvette.
  15. Replies
    27
    Views
    2,890

    Can someone elaborate on the details of this- I...

    Can someone elaborate on the details of this- I must have missed the beginning
  16. Thread: FX70

    by justjohnson
    Replies
    10
    Views
    1,939

    Any idea on release date and will this...

    Any idea on release date and will this incorporate JCI's jump to 3.5 and allow CCT passthrough?
  17. Replies
    1
    Views
    2,584

    APDU length max accepted

    Can someone better explain the APDU length max accepted parameter in Bacnet MSTP? I've got a mix of controllers on a trunk with some mitsubishi VFD drives and I'm having trouble with the drives...
  18. Replies
    37
    Views
    4,048

    make sure you don't do an autodiscover of the...

    make sure you don't do an autodiscover of the microtech IIs. They try and respond but it overloads them with all their points and then they just crap out and require the manual reset.
  19. Replies
    62
    Views
    9,229

    It might happen but I don't see JCI breaking the...

    It might happen but I don't see JCI breaking the deal with Distech completely. Without the LN/LX products they don't have a viable LON line. What are they going to go forward with the NexSys ESUSA...
  20. Replies
    9
    Views
    743

    did you use N2B points instead of N2Open points?

    did you use N2B points instead of N2Open points?
  21. Replies
    4
    Views
    835

    JCI is at it again

    http://www.duluthnewstribune.com/event/article/id/164839/

    Thought this was funny.
  22. Replies
    36
    Views
    6,237

    Generally B is positive and A is negative.

    Generally B is positive and A is negative.
  23. Replies
    40
    Views
    8,338

    yes

    yes
  24. Replies
    40
    Views
    8,338

    The add uses soap calls and web services to...

    The add uses soap calls and web services to communicate to the nae it does not use bacnet ip
  25. Replies
    40
    Views
    8,338

    Export the points via bacnet/IP into the nae. ...

    Export the points via bacnet/IP into the nae. Not that it's a good solution as the fx is far superior to the nae
  26. Replies
    18
    Views
    2,294

    JCI has a market cap of $22 billion and Honeywell...

    JCI has a market cap of $22 billion and Honeywell has a market cap of $34.31 billion. I wonder who is at the pleasure of who in that relationship?
  27. Replies
    16
    Views
    1,674

    see here...

    see here

    Besides these horror stories I have heard others of AOs locking up for no reason, refusing to respond to programs. As well as other communication issues and high failure rates. They...
  28. Replies
    16
    Views
    1,674

    What's that supposed to mean?

    What's that supposed to mean?
  29. Replies
    16
    Views
    1,674

    Now that 3.5 has been released... Any update from...

    Now that 3.5 has been released... Any update from those in the know if this is a possibility for JCI and CCT?
  30. Replies
    8
    Views
    1,369

    The other reason I don't like the idea is that n2...

    The other reason I don't like the idea is that n2 is not peer to peer so it requires the supervisory controller to pass the values through. That's fine for sharing oa temp and scheduling but...
  31. Replies
    109
    Views
    10,484

    how do you handle a failure of one of the points...

    how do you handle a failure of one of the points though? It seems to me like it makes a system that much more complicated for marginal savings and could be a big problem if you have a bunch of boxes...
  32. Replies
    8
    Views
    1,369

    The ABB ACH550 actually does N2, Modbus, Bacnet...

    The ABB ACH550 actually does N2, Modbus, Bacnet MSTP, and FLN all out of the box depending on your preference so yes there are integration options other than N2 if you want. I've done both N2 and...
  33. Replies
    8
    Views
    1,369

    First off you will need an FX20 or FX60 as those...

    First off you will need an FX20 or FX60 as those are the only jaces with N2 driver. Next, the book on the ACH550 should have a point mapping table in the communication section detailing the points...
  34. Replies
    6
    Views
    1,004

    Honeywell Gray Manual - for reference on generic...

    Honeywell Gray Manual - for reference on generic HVAC controls operations. For controller specific info I would go straight to the manufacturer and get their manuals for their controllers. But the...
  35. Replies
    13
    Views
    2,022

    The XPC communicates to the BMSII using Modbus. ...

    The XPC communicates to the BMSII using Modbus. The BMSII needs the Net Header Setpoint re-written to it within the timeout period regardless if it has changed, (I think it defaults to 2 minutes) or...
  36. Replies
    15
    Views
    3,504

    No one is really sure yet. We will find out when...

    No one is really sure yet. We will find out when it is officially released in March.
  37. Replies
    15
    Views
    3,504

    Controllers are robust - bacnet based only so if...

    Controllers are robust - bacnet based only so if you like LON try something else.

    Programming is easy - it is line based coding using CONTROL-BASIC - kind of like BASIC but with a Reliable flavor....
  38. Replies
    11
    Views
    1,021

    In your PC. I've not used Windows 7 but you...

    In your PC. I've not used Windows 7 but you probably have to configure an exception to Windows Firewall. I've had that issue in XP before. To confirm that's what it is, shut off Windows Firewall...
  39. Replies
    3
    Views
    597

    It's in the alarm class under AlarmServices. ...

    It's in the alarm class under AlarmServices. Under "Ack Required" uncheck the "toNormal" box. Then you won't need to acknowledge a "Return to Normal" state.
  40. If the customer is willing to pay for it, why...

    If the customer is willing to pay for it, why don't you just take the class? You already saved him $9K - the class is already paid for?
  41. Replies
    24
    Views
    2,581

    I just got a Moto Droid. The browser is top...

    I just got a Moto Droid. The browser is top notch and most of the apps work well. Still need a good tethering app. I got EasyTether Beta and it works well but doesn't seem to work with VPN...
  42. Replies
    5
    Views
    596

    Now that's some funny @#$%

    Now that's some funny @#$%
  43. how is a bad programming job = faulty hardware? ...

    how is a bad programming job = faulty hardware? I agree with Freddy, from what you have said is on it, I would guess a problem with the programming and application of device. You will probably find...
  44. Replies
    3
    Views
    544

    Barber Coleman (and consequently the Siebe and...

    Barber Coleman (and consequently the Siebe and TAC I/A controllers ) support thermistors only with an 11K shunt across it. This is to bring the actual resistance measured by the controller down...
  45. Replies
    27
    Views
    5,306

    you need to go to Tridium for their AX...

    you need to go to Tridium for their AX certification training class or attend an AX cert class hosted by a Tridium partner like MOV Training. www.movtraining.com
  46. Replies
    6
    Views
    579

    what version of NAE do you have? I don't think...

    what version of NAE do you have? I don't think they supported MSTP routing until version 4.0
  47. Replies
    5
    Views
    697

    I believe a zoom functionality is one of the...

    I believe a zoom functionality is one of the features Tridium is adding in Niagara 3.5
  48. Replies
    5
    Views
    2,262

    save it as svg and use a different drawing...

    save it as svg and use a different drawing package to modify it. I like Adobe Illustrator.
  49. Replies
    2
    Views
    547

    thanks mackinaw, that's what I thought. Still...

    thanks mackinaw, that's what I thought. Still getting used to the naming conventions in CCT...
  50. Replies
    2
    Views
    547

    FEC hybrid activity

    in a hybrid activity logic sheet. when a particular mode is not active does that mean that any logic blocks in the mode are not executed at all? i.e. a hybrid activity has states of off/on. if the...
Results 1 to 50 of 255
Page 1 of 6 1 2 3 4
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine
Comfortech365 Virtual Event