Search:

Type: Posts; User: Fridge Repairer

Page 1 of 5 1 2 3 4

Search: Search took 0.00 seconds.

  1. Don't miss quote me. That's your quote not mine. ...

    Don't miss quote me. That's your quote not mine.

    I said "Best to set it when you do start up. if its summer out and system is running it will be tough to set the A8. Bypass all your fans on and...
  2. Because your a moderator, I take great offense to...

    Because your a moderator, I take great offense to your statement calling me out as LAZY for not checking an A8 valve in a high ambient condition. When was the last time you tried to set a low ambient...
  3. Nope...but maybe others will like to know.

    Nope...but maybe others will like to know.
  4. Bottom line is don't mess with the A8 A9 valve...

    Bottom line is don't mess with the A8 A9 valve unless you have fans cycling on and off on your condenser because your just waisting your customers time. Make sure you have a good receiver level and...
  5. Touchee! Your right about me. I'm not going to...

    Touchee! Your right about me. I'm not going to waist the customers time trying to set a valve in conditions that are not favorable to set it. As long as I have a strong receiver level, the amount to...
  6. http://www.youtube.com/watch?v=PFb6NU1giRA ...

    http://www.youtube.com/watch?v=PFb6NU1giRA

    It's your job to train your techs that your in charge of, right? Sounds like your not doing a good job of training your techs if you constantly are going...
  7. To be honest, I can tell I'm not nearly as smart...

    To be honest, I can tell I'm not nearly as smart as you BUT, your the one that is to dimwitted that your the one un-able to think outside the box just by the nature of your response. Let's be honest...
  8. Best to set it when you do start up. if its...

    Best to set it when you do start up. if its summer out and system is running it will be tough to set the A8. Bypass all your fans on and turn off a bunch of system circuits. See if you can creat a...
  9. Thanks zartangreen. I'd certainly entertain the...

    Thanks zartangreen. I'd certainly entertain the idea of sharing a booth if it's allowed. I don't need much space to do my demonstations.
    I'll be starting to braze the piping tomorrow. I'm starting...
  10. 354131354141354151 The warehousing evaporators...

    354131354141354151
    The warehousing evaporators are hung and the "Gas Coolers" are on the roof. Midwest helicopters put them up there for us. The condenders are called gas coolers because on the hot...
  11. 354091354101354111 Racks are in place. We have 4...

    354091354101354111
    Racks are in place. We have 4 systems. Now that I had the training class, I'm a lot clearer on how these things will function. I am honored and privilaged to have this opportunity...
  12. Rusty Walker from Hill Phoenix just did our...

    Rusty Walker from Hill Phoenix just did our training class last week. Rusty did a great job as I know pretty much know whats going on now. Now that I know more about how it works I am beginning the...
  13. It's amazing how much of an investment has been...

    It's amazing how much of an investment has been made to get the Valve Core Gripper off the ground. Im not in the green yet but I am climbing out of the hole. All the profit I make I reinvest back...
  14. Replies
    43
    Views
    5,849

    An oversized liquid line solenoid is a bad...

    An oversized liquid line solenoid is a bad thing...it may not always close all the way. Be sure your LLS is properly sized.
  15. Replies
    53
    Views
    6,560

    Jump right in head first and fake it till you...

    Jump right in head first and fake it till you make it! Goodluck
  16. Assuming you have a full system charge on sounds...

    Assuming you have a full system charge on sounds like to me you have a bad TXV. another thing you want to check is make sure you have the proper nozzle in your distributor. Check the distributor...
  17. Replies
    30
    Views
    3,626

    Job security!

    Job security!
  18. No matter what your going to log Freon in the...

    No matter what your going to log Freon in the condenser. The hard part is settiong your A8 and A9 valve. Its best and easiest to set when outdoor ambient is about 40 Degrees F. I always set the A8...
  19. What you can do next chance you work on it is...

    What you can do next chance you work on it is take a meg ohm reading. Supco makes a nice meter that works very well for this purpose. I had a customer years ago that had an extremely noisy little...
  20. Tomorrow I have a 10,000# Lull coming in so we...

    Tomorrow I have a 10,000# Lull coming in so we can lift the heaviest rack into the room. The first one they sent could not lift rack DT3. Walkin freezers and coolers are being built. Underground...
  21. This is the first Trans-Critical CO2 store going...

    This is the first Trans-Critical CO2 store going in within the United States. CO2 means extremely high pressure. Yesterday I met with the engineers from Hill Phoenix. We unwrapped one of the 4 rack...
  22. Replies
    24
    Views
    3,286

    I agree with dangpgt... I have had great luck...

    I agree with dangpgt... I have had great luck with the battery operated tif ZX1 and also love my H10 plug in ...hate the plug in though. As far as using your h10 I was taught to put it on the small...
  23. Replies
    14
    Views
    2,949

    The proper solenoid valve does not neccessarily...

    The proper solenoid valve does not neccessarily match the pipe size.
  24. Replies
    14
    Views
    2,949

    I had the same problem once... the problem was...

    I had the same problem once... the problem was that the solenoid valve was over sized and it would not always close .
  25. Replies
    23
    Views
    2,641

    Be sure you pump down the system when your done...

    Be sure you pump down the system when your done adding freon to make sure your reciever is capable of holding the charge. Not doing this could cause you an unneccessary callback