Search:
Type: Posts; User: chrisc
Search: Search took 0.01 seconds.
-
02-20-2013, 08:10 AM
Thread: LP-FXVMA11-1C Point Mapping to NAE45
by chrisc- Replies
- 6
- Views
- 186
Berg, Thanks for the reply. N30's removed, NAE45...
Berg,
Thanks for the reply. N30's removed, NAE45 installed with N2 network. I have 5-FX VMA's left out there that were installed by another contractor last year before we arrived on site. We install... -
02-19-2013, 11:03 AM
Thread: LP-FXVMA11-1C Point Mapping to NAE45
by chrisc- Replies
- 6
- Views
- 186
LP-FXVMA11-1C Point Mapping to NAE45
I'm looking for the point tables for the LP-FXVMA11-1C controller, this controller resides on the N2 bus and is mapped in as an N2 open device, typical to a TEC controller. I've upgraded the site and...
-
02-18-2011, 10:46 AM
Thread: WARNING about HVAC trade schools
by chrisc- Replies
- 112
- Views
- 21,821
Wolf, It seems as though you've had some tough...
Wolf,
It seems as though you've had some tough luck in the HVAC field. I've been in for 25 years and have seen more good than bad times. I notice your 39 yrs old, how long have you been in the... -
11-23-2009, 08:32 PM
Thread: JCI O/A hotwater reset schedule
by chrisc- Replies
- 7
- Views
- 1,022
You have to pick the AI to AO sideloop option...
You have to pick the AI to AO sideloop option with reset/span. Your OA-T will be resetting your hot water setpoint. Once you get some numbers in there you can download your UNT and play with the...
-
08-03-2009, 07:10 PM
Thread: JCI giving advise?
by chrisc- Replies
- 8
- Views
- 636
That's pretty funny, I remember working for the...
That's pretty funny, I remember working for the branch when the stock was splitting and they still told us that two percent was all they could afford. I have alot to say, but it's better I keep it to...
-
02-27-2009, 06:03 PM
Thread: Central Control System Advice needed!
by chrisc- Replies
- 10
- Views
- 568
My company is located in Central NJ, if you'd...
My company is located in Central NJ, if you'd like to contact me via my email address in my profile, we could set up a visit to your site.
Take Care, Chris -
01-25-2009, 12:09 PM
Thread: ADS\NAE and Alarms
by chrisc- Replies
- 6
- Views
- 343
Check the IP of the ADS repository in each NAE....
Check the IP of the ADS repository in each NAE. Match the IP of the computer you want the alarm(s) to report to.
-
01-23-2009, 05:34 PM
Thread: Facilitator
by chrisc- Replies
- 2
- Views
- 263
If the occupied point is defined in the...
If the occupied point is defined in the Facilitator database and not attached to a schedule it will default to on and run 24/7. Just verify in your H-Pro prn file that the OCC point their using is...
-
12-19-2008, 03:20 PM
Thread: NEED HELP ON DX 9100 CALBRATION
by chrisc- Replies
- 10
- Views
- 400
I think that reply is quite harsh especially...
I think that reply is quite harsh especially coming from a controls committee member. I've seen more ridiculous posts that you've been glad to reply too. I don't think DIYers are exposed to DX's...
-
12-13-2008, 04:16 PM
Thread: Was there another round at JCI?
by chrisc- Replies
- 44
- Views
- 1,784
I had heard from a good source that office...
I had heard from a good source that office personnel from the Phila. area were asked to accept a layoff at 9am one morning and then reapply at 1pm for the same jobs at a lower salary, what happens...
-
12-11-2008, 05:01 PM
Thread: Pls help me on DX 9100 AO problem
by chrisc- Replies
- 10
- Views
- 541
First of all where is Mandamarri? Secondly,...
First of all where is Mandamarri? Secondly, upload your calibration values and check the HI value for your AO, it sounds like someone reduced the number and your HI = 3VDC. If that's the case correct...
-
12-04-2008, 05:34 PM
Thread: metasys Global set point
by chrisc- Replies
- 4
- Views
- 475
Do you have an N30,NCM or an NAE?
Do you have an N30,NCM or an NAE?
-
12-04-2008, 05:30 PM
Thread: Fried CVT Pro!!!!!(metasys)
by chrisc- Replies
- 19
- Views
- 1,558
Actually an N2 connection has more capabilities...
Actually an N2 connection has more capabilities than a zone bus connection, you can access all controllers on the N2 bus. I like the idea with the field made cable.
-
12-02-2008, 08:38 PM
Thread: Fried CVT Pro!!!!!(metasys)
by chrisc- Replies
- 19
- Views
- 1,558
I fried 2 cvt-300's in two days, plugged into...
I fried 2 cvt-300's in two days, plugged into zone bus on unt-1126/44/series controller, something in the unt took it out. My stupidity was tough to explain to our parts guy,I've been dealing solely...
-
11-26-2008, 07:43 PM
Thread: JC Experts
by chrisc- Replies
- 5
- Views
- 545
Remove the control from it's base and on the back...
Remove the control from it's base and on the back of the DX you'll see the factory calibration tables, write down the numbers you currently have and then return the AI to it's default numbers.
Good... -
11-26-2008, 07:38 PM
Thread: dx9100 problem
by chrisc- Replies
- 5
- Views
- 466
Is this a new install? If not it sounds as though...
Is this a new install? If not it sounds as though the AI's on the DX are bad, can you read resistance thru the sensors with a meter?
-
11-08-2008, 11:48 PM
Thread: DX9100 AO not sourcing.
by chrisc- Replies
- 8
- Views
- 474
Delete PIDs and reAdd, make sure Aos are set for...
Delete PIDs and reAdd, make sure Aos are set for proper out put, this should correct problem.
-
10-24-2008, 11:50 PM
Thread: Controls training
by chrisc- Replies
- 8
- Views
- 590
Apply to JCI and take advantage of their training...
Apply to JCI and take advantage of their training institute, I've never been disappointed by any of their classes, they've always been top notch.
-
10-18-2008, 08:37 AM
Thread: Terminating Shielded Cable
by chrisc- Replies
- 16
- Views
- 1,395
Typically, when we run any cables near MCC's or...
Typically, when we run any cables near MCC's or high voltage, we'll run all our cables in conduit, as well. I have seen companies actually ty-rap to the high voltage conduits, causing their cables to...
-
10-17-2008, 06:05 PM
Thread: Zoom Modem connection to metasys N30 issue
by chrisc- Replies
- 2
- Views
- 432
Make sure that when you exit your dial up...
Make sure that when you exit your dial up connection that you disconnect from the program and don't simply do a file exit, this will not properly hang up the modem, causing the modem issue....
-
10-17-2008, 05:55 PM
Thread: Terminating Shielded Cable
by chrisc- Replies
- 16
- Views
- 1,395
What does Acutherm recommend?, it should be...
What does Acutherm recommend?, it should be spelled out in their installation specs. Every manufacturer has this type of tech data, if they don't recommend shielded cable then I wouldn't provide it.
-
09-13-2008, 09:27 PM
- Replies
- 13
- Views
- 1,108
Orion, I spit my beer all over the monitor after...
Orion,
I spit my beer all over the monitor after reading your comment, that's hilarious.
Chris -
09-03-2008, 04:31 PM
Thread: Slowing down a PID output on DX9100
by chrisc- Replies
- 22
- Views
- 1,076
Not for nothing, but, what are the current...
Not for nothing, but, what are the current numbers your running in your PID and are you filtering your AI? It sounds as though it's a straight PID and not a Dual PID, am I correct? And what are the...
-
08-13-2008, 03:13 PM
Thread: NAE and combine graphics
by chrisc- Replies
- 4
- Views
- 626
We have typically built ours from scratch but...
We have typically built ours from scratch but have developed our own library to pull from for our current jobs. If you can use alias drawings to prevent yourself from having to use an ADS, if your...
-
02-29-2008, 11:53 AM
Thread: Boyd Coddington
by chrisc- Replies
- 32
- Views
- 1,323
Heard that Roy passed away, also.
Heard that Roy passed away, also.
Results 1 to 25 of 147