  1. The only answer I have is to contact you local...

    The only answer I have is to contact you local JCI branch and have them, via the SIS team, create you a new VCT file. I work for JCI and thats what I would have to do if it was me.
  2. Exactly the way Ive always done it, but Im sure...

    Exactly the way Ive always done it, but Im sure someone can edit it IF they had the proper software, Ive just never found it.
  3. Simux, was there actually anything there that...

    Simux, was there actually anything there that told how to edit a .VCT? I have been with JCI almost 10 years and havent ever done it, I have always been told I have to have a table created for me, but...
  4. Replies
    9
    Views
    363

    Also, what kind of controller is this setpoint...

    Also, what kind of controller is this setpoint for? Bacnet or N2? Is it a calculated point under local control? (Some DAT-SP are calculated in many UNT configurations so it has to be asked) Is it an...
  5. Replies
    16
    Views
    1,747

    But if you have no other version of SCT, it will...

    But if you have no other version of SCT, it will at least give you a backup in case you have to replace the NAE. I am assuming that the NAE may be a -0, if so, then you cannot nut it to anything...
  6. Replies
    16
    Views
    1,747

    You can, but you cannot download it back to that...

    You can, but you cannot download it back to that NAE without nutting it to the upgraded version
  7. Replies
    12
    Views
    541

    If you have a NAE55xx-1, or a NAE45 or 35, you...

    If you have a NAE55xx-1, or a NAE45 or 35, you can upgrade to 4.1 without having to purchase the software, if your capable of performing the upgrade yourself, but you will have to be able to back up...
  8. Replies
    12
    Views
    541

    Well, like I said, between 4.0 and 4.1 there was...

    Well, like I said, between 4.0 and 4.1 there was a big difference, which is actually out of the ordinary, usually the big differences occur at the major revisions, but not this time. they actually...
  9. Replies
    12
    Views
    541

    Hey Berg, I don't think that was his issue, he...

    Hey Berg, I don't think that was his issue, he couldn't send commands to multiple points. Igotworms, I noticed something today, although you probably already went and did all the points individually,...
  10. Replies
    16
    Views
    1,747

    The site name and NAE name has to be IDENTICAL,...

    The site name and NAE name has to be IDENTICAL, also, when you get the error, if you highlight the entry, then I believe the details at the bottom becomes available, you can see more info on the...
  11. Replies
    15
    Views
    1,238

    First Osiyo, sorry for your lose, hang in there,...

    First Osiyo, sorry for your lose, hang in there, sounds like you still have people that love you, so you will be alright. Second, your advice is perfect, both for controls or AC work, or car...
  12. Replies
    12
    Views
    541

    I had no problem with the "highlight, right...

    I had no problem with the "highlight, right click" method on a 5.2 site, but the issue may be the version. Try Phantoms idea, I will try to access an older site tomorrow to see if I have any...
  13. Replies
    12
    Views
    541

    Hmm actually the units don't even need to match,...

    Hmm actually the units don't even need to match, I was wrong, so maybe you have an old version?
  14. Replies
    12
    Views
    541

    You have to make sure all the setpoint types are...

    You have to make sure all the setpoint types are the same (deg vs inches etc) Also what version MEA do you have? I have to double check, but I believe some of the older versions might have had an...
  15. Replies
    10
    Views
    955

    Set up as "AN" OWS not "THE" OWS though. The NIE...

    Set up as "AN" OWS not "THE" OWS though. The NIE cant be the archive. Use WNCsetup or NCsetup to go into the NCMs and see where the archive is set for, usually the port or IP of the computer with the...
  16. Replies
    10
    Views
    955

    Not quite, the NIE cannot be the archive, you...

    Not quite, the NIE cannot be the archive, you need to have an OWS for that because you have to compile the DDL and translate the GPL, then point the NCMs to the OWS with NCSETUP or WNCSETUP so they...
  17. Replies
    10
    Views
    955

    If you have an NIE with NCMs you should still...

    If you have an NIE with NCMs you should still have an active PMI workstation on site. Otherwise you would have database maintanance issues since the NIE cant download an NCM. And some of the NCM/IP...
  18. Replies
    26
    Views
    3,191

    And of course we all know FUBAR....

    And of course we all know FUBAR....
  19. Replies
    17
    Views
    2,036

    Hi all, I want to revisit this subject for some...

    Hi all, I want to revisit this subject for some clarity and maybe an update. While looking for an N2/ethernet solution, I have seen whereeveryone says it is viable for NAEs, and I was wondering if...
  20. Replies
    3
    Views
    4,024

    Thanks, that is def a way to go. I had read that...

    Thanks, that is def a way to go. I had read that same thing, but the thing that threw me on the "address" is that one of the boards on one of the existing units (that seems to have a custom cfg) has...
  21. Replies
    15
    Views
    4,149

    and check to be sure there arent any LCT or...

    and check to be sure there arent any LCT or interlock processes controlling the heat, cuz then the vma prog is useless
  22. Replies
    15
    Views
    4,149

    Are you able to upload the vma and provide the...

    Are you able to upload the vma and provide the files? Also, the heating min cfm has to be met for box heat to work, not sure if that would effect the baseboard heat tho, the files would be the most...
  23. Replies
    3
    Views
    4,024

    Carrier Premier Link downloadeer

    Good day,
    I have a site that I am replacing a Premier link board. I have "inherited" a "service tool V" interface and CD. I was able to find how to connect, upload, and re-address via software. I...
  24. Replies
    14
    Views
    3,380

    The Trane site downloads are service pack...

    The Trane site downloads are service pack upgrades, like, you cant get xp for free, but you can get sp3 free. These are not full software packages
  25. Replies
    9
    Views
    1,452

    Your over on your object count, if you do have...

    Your over on your object count, if you do have low COVs between the 2 it could be a factor. I agree also to check for unbound refs as well