Search:

Type: Posts; User: *TEEKAY*

Page 1 of 2 1 2

Search: Search took 0.00 seconds.

  1. Replies
    5
    Views
    714

    Yep. Been there. Change that and presto, button...

    Yep. Been there. Change that and presto, button won't be grayed out.
  2. Replies
    4
    Views
    988

    Be careful to compare the dwell time of the pulse...

    Be careful to compare the dwell time of the pulse time of the meter to the controller you'll be connecting it to. Some pulse outputs are ultra fast and controller misses pulses. Learned that the...
  3. Replies
    7
    Views
    1,065

    What type of equipment?

    What type of equipment?
  4. Replies
    18
    Views
    1,085

    Try Control Panel Java Advanced Tab Expand...

    Try
    Control Panel
    Java
    Advanced Tab
    Expand Java Plug in
    Uncheck Unable next generation Java Plug In

    Worked for me last time I had this issue.
    Might be worth a try
  5. Replies
    37
    Views
    2,632

    I hear you John! :)

    I hear you John! :)
  6. Replies
    37
    Views
    2,632

    Companies run credit checks on potential...

    Companies run credit checks on potential employees... just the way it is. If you want to look at your potential employer's credit report, ask. If they decline, you don't have to take a position...
  7. Replies
    7
    Views
    4,643

    IMO, if you are new to the trade and just...

    IMO, if you are new to the trade and just starting out, your employer won't expect you to be a pro-tech and will probably have you ride along with a journeyman in a
    'helper/apprentice" role. You...
  8. Thread: Controls ????

    by *TEEKAY*
    Replies
    4
    Views
    1,076

    Please email specs to me also. I've been...

    Please email specs to me also. I've been estimating controls jobs for years and am curious.
  9. Replies
    23
    Views
    1,757

    I agree with Norriski, apparently some people...

    I agree with Norriski, apparently some people have nothing better to do than try to split hairs. It must be because at the end of the day, they have to look in the mirror and they must not like what...
  10. Replies
    8
    Views
    635

    Maybe a fire damper closed? Or VAV boxes closing...

    Maybe a fire damper closed? Or VAV boxes closing at same time for some reason (global calibration) Or VFD in hand?
  11. Thread: GCL+

    by *TEEKAY*
    Replies
    14
    Views
    2,683

    DeltaFrank, could you send it to me too? email is...

    DeltaFrank, could you send it to me too? email is is profile.
    Please and Thanks
  12. Replies
    21
    Views
    1,830

    Yep, W and C, I misunderstood the intent of the...

    Yep, W and C, I misunderstood the intent of the damper
  13. Replies
    21
    Views
    1,830

    (2) relays, (1) actuator- preferably powered from...

    (2) relays, (1) actuator- preferably powered from a seperate power source than the furnaces. Relay coils enegized from G to C on each furnace, parallel n.o. contacts to actuator. Done
  14. What is controlling the exhaust dampers? Is...

    What is controlling the exhaust dampers? Is there a return fan in the AHU?
  15. Replies
    8
    Views
    735

    Could be completely unrelated to your problem...

    Could be completely unrelated to your problem but....
    I ran into this exact issue on a tridium based system/ Intellipak, and turns out mechanical contractor had replaced a VAV box on the job and...
  16. Replies
    13
    Views
    718

    Just saw your other posts. Regardless of the lon...

    Just saw your other posts. Regardless of the lon vendor or equipment manufacturer for that matter, nci's are not meant to be written to by any "dynamic" function. The only nci points I've ever had...
  17. Replies
    13
    Views
    718

    Yes, nci points, as a rule, are designed to allow...

    Yes, nci points, as a rule, are designed to allow integrators to make some configuration changes to equipment without needing vendor specific software. nvi points, are to designed to allow...
  18. Replies
    13
    Views
    718

    Bet they are writing to nciDAClSP instead of...

    Bet they are writing to nciDAClSP instead of nviDAClSP. (Discharge air cooling Setpoint) Lon 101- nci are network Configurable points and nvi are network variable points. Some guys just don't...
  19. Replies
    8
    Views
    1,227

    Sorry, I misunderstood as well.

    Sorry, I misunderstood as well.
  20. Replies
    8
    Views
    1,227

    KitControl/Energy/SlidingWindowDemandCalc Works...

    KitControl/Energy/SlidingWindowDemandCalc Works great for what you are trying to do.
  21. Been in the same situation, and I have had people...

    Been in the same situation, and I have had people tell me to set the Occheat and OccCool setpoint the same and the EffStpt will equal nviSetpoint. I have done this but didn't feel warm and fuzzy...
  22. Typically this is done by interlocking Boiler(s)...

    Typically this is done by interlocking Boiler(s) with MAU(s). This can be done via series circuit (end-switch on MAU unit damper, current relay on MAU blower, and Boiler Enable relay. Depending on...
  23. Replies
    8
    Views
    1,101

    Maxtaf, if I understand this correctly the...

    Maxtaf, if I understand this correctly the scenario would be...Occupant sets wall sensor to 73. She leaves for the night, at midnight, setpoint automatically changes to 75. She arrives the next...
  24. Replies
    6
    Views
    1,046

    I guess time would depend on how many points you...

    I guess time would depend on how many points you need modified, number of controllers and a number of other factors including distance to the jobsite etc. If the Trane tech is qualified, he should...
  25. Replies
    6
    Views
    1,046

    With Rover software it isn't difficult. I am...

    With Rover software it isn't difficult. I am assuming you have a non trane front end you're trying to use to change some setpoints etc. i.e. Tridium or similar
Results 1 to 25 of 28
Page 1 of 2 1 2
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine
Comfortech365 Virtual Event