  1. Thread: BQL Search

    by checkvalve
    Replies
    5
    Views
    376

    bql select * from control:NumericPoint where name...

    bql select * from control:NumericPoint where name like 'Zn*Tmp' and not(like '*FlrTmp')

    Should handle any number of characters in the zone number and also exclude any of the points with FlrTmp in...
  2. Replies
    7
    Views
    393

    I don't know of a single component that would...

    I don't know of a single component that would test for both conditions. You would need to use multiple logic components linked together, unless you wanted to write the logic in a program object or...
  3. Replies
    9
    Views
    477

    Did the images ever load in the browser? In most...

    Did the images ever load in the browser? In most cases people forget to transfer the modules to the JACE which has the images used in the px views. When you use Workbench it has a copy of those...
  4. Replies
    5
    Views
    564

    Are you making an RDP connection to the Soft...

    Are you making an RDP connection to the Soft JACE? I think that there is an issue if you make the RDP connection using the /admin switch that can cause that behavior.
  5. Did you assign a valid object ID to the local...

    Did you assign a valid object ID to the local bacnet device? It defaults to -1 which is not valid.
  6. Replies
    3
    Views
    386

    You cannot use the batch editor to add proxy...

    You cannot use the batch editor to add proxy points. You can do it using the robot editor, but it requires writing some Java code.
  7. Replies
    12
    Views
    721

    I use a KVM switch when in the office with my...

    I use a KVM switch when in the office with my laptop, which requires pressing scroll lock key twice to toggle between machines. I have noticed that when using hyperterminal (haven't tested the same...
  8. Replies
    3
    Views
    312

    There is a McQuay driver from Tridium. In the...

    There is a McQuay driver from Tridium. In the Workbench help look at the docMcquay for the specifics. local:|module://docMcQuay/doc/index.html
  9. Replies
    1
    Views
    470

    I don't think the SMS driver will route SMS over...

    I don't think the SMS driver will route SMS over the IP connection. In other words it just sees the Cradlepoint as a router and doesn't really know about the USB device being used for the broadband...
  10. Replies
    6
    Views
    1,061

    To access from the internet you would need to...

    To access from the internet you would need to open the following ports for station access.

    Browser/HTTP port 80
    Browser/HTTPS port 443
    Browser using a WB profile/Fox port 1911 (or whatever port...
  11. Replies
    6
    Views
    1,061

    You need to have the crypto feature in the...

    You need to have the crypto feature in the license for the JACE. You also need to install the crypto.jar to the JACE and copy the crytpo service from the crypto palette to the services container in...
  12. Have you tried checking for an updated license...

    Have you tried checking for an updated license from the license server?

    Your license should have a feature such as this, which is from my JACE 6 demo license.

    <feature name="ibmj9j2me"...
  13. It sounds like you might be using 3.6 and not...

    It sounds like you might be using 3.6 and not 3.5. Starting in 3.6 the fx60 uses the Sun Hotspot JVM instead of the IBM J9 VM. For a fx60 which is licensed for 3.6 it should have a feature in the...
  14. Replies
    2
    Views
    476

    I think you just need an updated module. ...

    I think you just need an updated module.

    https://www.niagara-central.com/ord?portal:/discussion/DiscussionThread/10059
  15. Replies
    10
    Views
    1,064

    Nothing really, as the client doesn't need to...

    Nothing really, as the client doesn't need to authenticate. It is just an added step in the station engineering to allow BACnet client devices to write to the exposed BACnet objects.

    In Workbench...
  16. Replies
    10
    Views
    1,064

    The station automatically creates a user named...

    The station automatically creates a user named BACnet. You need to assign the BACnet user operator write permissions to the BACnet export components.
  17. Replies
    17
    Views
    1,352

    It doesn't sound like too much, but it is...

    It doesn't sound like too much, but it is difficult to say simply by device counts or history counts alone. Based on your free heap mentioned in the thread, I wouldn't say that it was overloaded.
    ...
  18. Replies
    17
    Views
    1,352

    Are you using the NDIO network in the JACE? I...

    Are you using the NDIO network in the JACE?

    I would suggest looking at the console backup text file located in the root of the station file system. Assuming that your aren't seeing some sort of...
  19. Replies
    14
    Views
    1,041

    In the past I have added a stringWritable to the...

    In the past I have added a stringWritable to the station. On the facets for the stringWritable I added a facet named multiLine of type boolean and set it to true. That is one of the default facets...
  20. Replies
    15
    Views
    1,401

    Auto save versions to keep affects flash drive...

    Auto save versions to keep affects flash drive usage and not ram disk.
  21. Replies
    15
    Views
    1,401

    BTW, when you initially setup the histories they...

    BTW, when you initially setup the histories they only take a portion of the RAM disk space. As the histories accumulate records up to their configured capacity they will take more memory. It is...
  22. Replies
    15
    Views
    1,401

    Gregf, what do you not agree with? I agree...

    Gregf, what do you not agree with?

    I agree that before arbitrarily increasing the RAM disk size that you should check the flash drive free space to make sure that you have sufficient room to save...
  23. Replies
    15
    Views
    1,401

    GregF, those statements you made about the RAM...

    GregF, those statements you made about the RAM disk are not really correct. The QNX operating system doesn't use the RAM disk, nor do the jars, programming or graphics. The station uses the heap...
  24. Well default alarm database (500 records),...

    Well default alarm database (500 records), default audit history (500 records), default log history (500 records), and 500 numeric histories with 500 records each should only account for ~8-9 MB....
  25. Look at the property sheet of the alarm service...

    Look at the property sheet of the alarm service and verify what the capacity is set to.

    Double click on the history node in the tree. Then hit ctrl + L and paste this, |bql:select * from...