Search:

Type: Posts; User: dlhvac

Page 1 of 2 1 2

Search: Search took 0.03 seconds.

  1. Replies
    27
    Views
    2,770

    Yes it could be a big deal as long as it is comm3...

    Yes it could be a big deal as long as it is comm3 isolate ie not polarity sensitive already have driver for the comm3 non isolated ie polArity sensitive
  2. Replies
    27
    Views
    2,770

    The interface is a torroid transformer the...

    The interface is a torroid transformer the protocol is audio just as modem audio that is the data highway
  3. Replies
    28
    Views
    1,543

    i tried to email you the answer but your email...

    i tried to email you the answer but your email bounced email me at dlhvac@ptd.net
  4. Replies
    28
    Views
    1,543

    i use an infocon easyio 30p or a spyder micro

    i use an infocon easyio 30p or a spyder micro
  5. Replies
    28
    Views
    1,543

    the sensor has the output rating right on it i...

    the sensor has the output rating right on it i cannot recall offhand but the bypass damper cannot be controlled by the jace you must replace this controller with another the ccp panel previously...
  6. Replies
    28
    Views
    1,543

    yes but usually the supply house you purchase the...

    yes but usually the supply house you purchase the driver from is the first contact i use broudy supply in philadelphia, also cochrane supply in mich has the driver
  7. Replies
    28
    Views
    1,543

    worked well have done a bunch since then 12 or 13

    worked well have done a bunch since then 12 or 13
  8. Replies
    28
    Views
    1,543

    9600 8 none 1

    9600 8 none 1
  9. Replies
    3
    Views
    546

    broudy supply in phila has the drivers

    broudy supply in phila has the drivers
  10. Replies
    3
    Views
    546

    yes it is available thru maxline drivers with...

    yes it is available thru maxline drivers with infocon support for 10 years
  11. Replies
    28
    Views
    1,543

    Does the install have trane purple wire if not...

    Does the install have trane purple wire if not your on your own
  12. Replies
    28
    Views
    1,543

    Approx 80 or more points per rtu all the...

    Approx 80 or more points per rtu all the diagnostic alarms and you can also reset diagnostic faults
  13. Replies
    28
    Views
    1,543

    You can see more of the voyager and reliatel...

    You can see more of the voyager and reliatel points than with tranes software
  14. Replies
    28
    Views
    1,543

    The zoning and rtu overides are done in the jace

    The zoning and rtu overides are done in the jace
  15. Replies
    28
    Views
    1,543

    I would use a six if you are putting graphics on...

    I would use a six if you are putting graphics on it if noy jace 2 should work watch your java heap and busy time on the jace comm four is a reource hog
  16. Replies
    28
    Views
    1,543

    Sorry but i dont give away stations that ive done...

    Sorry but i dont give away stations that ive done but it is doable to integrate all that you stated
  17. Replies
    28
    Views
    1,543

    Maxline drivers owms the comm4 driver infocon...

    Maxline drivers owms the comm4 driver infocon sold the driver division go them but has a contract for 10 years to provide support
  18. Replies
    28
    Views
    1,543

    worked very well have done 12 to date

    worked very well have done 12 to date
  19. Replies
    27
    Views
    2,770

    you have to put the unit in tracer control and...

    you have to put the unit in tracer control and command the input mode
  20. Replies
    119
    Views
    11,216

    the ashrae show sent you an email

    the ashrae show sent you an email
  21. Replies
    119
    Views
    11,216

    the ashrae show

    the ashrae show
  22. Replies
    119
    Views
    11,216

    THE CONTROLLERS WILL BE OUT AT THE SHOW IN DALLAS...

    THE CONTROLLERS WILL BE OUT AT THE SHOW IN DALLAS IM BETA TESTING A PROTOTYPE
  23. Replies
    119
    Views
    11,216

    Have over 50 installed at different sites all...

    Have over 50 installed at different sites all work flawlessly and yes they talk sedona modbus and bacnet all at the same time the new ones due out will have its own html5 graphics engine and it own...
  24. Replies
    27
    Views
    2,770

    Forgot using lon requires the firmware in chiller...

    Forgot using lon requires the firmware in chiller to be the latest Trane will have to upgrade recommend using comm4
  25. Replies
    27
    Views
    2,770

    There are some issues with the commissioning of...

    There are some issues with the commissioning of the lci-c chiller lon cards you have to set the response to the jace at no response to commission because some of the cards do not send this response
Results 1 to 25 of 46