02-18-2013, 06:00 PM
Thread: Niagara AX to Trane comm3 and comm4 advise
by dlhvac- Replies
- 27
- Views
- 2,770
Yes it could be a big deal as long as it is comm3...
Yes it could be a big deal as long as it is comm3 isolate ie not polarity sensitive already have driver for the comm3 non isolated ie polArity sensitive
-
02-18-2013, 04:40 PM
Thread: Niagara AX to Trane comm3 and comm4 advise
by dlhvac- Replies
- 27
- Views
- 2,770
The interface is a torroid transformer the...
The interface is a torroid transformer the protocol is audio just as modem audio that is the data highway
-
12-04-2012, 06:18 PM
Thread: Trane Com4 to AX integration problem......
by dlhvac- Replies
- 28
- Views
- 1,543
i tried to email you the answer but your email...
i tried to email you the answer but your email bounced email me at dlhvac@ptd.net
-
12-04-2012, 03:13 PM
Thread: Trane Com4 to AX integration problem......
by dlhvac- Replies
- 28
- Views
- 1,543
i use an infocon easyio 30p or a spyder micro
i use an infocon easyio 30p or a spyder micro
-
12-04-2012, 03:12 PM
Thread: Trane Com4 to AX integration problem......
by dlhvac- Replies
- 28
- Views
- 1,543
the sensor has the output rating right on it i...
the sensor has the output rating right on it i cannot recall offhand but the bypass damper cannot be controlled by the jace you must replace this controller with another the ccp panel previously...
-
12-04-2012, 03:09 PM
Thread: Trane Com4 to AX integration problem......
by dlhvac- Replies
- 28
- Views
- 1,543
yes but usually the supply house you purchase the...
yes but usually the supply house you purchase the driver from is the first contact i use broudy supply in philadelphia, also cochrane supply in mich has the driver
-
12-03-2012, 06:13 PM
Thread: Trane Com4 to AX integration problem......
by dlhvac- Replies
- 28
- Views
- 1,543
worked well have done a bunch since then 12 or 13
worked well have done a bunch since then 12 or 13
-
12-03-2012, 01:16 PM
Thread: Trane Com4 to AX integration problem......
by dlhvac- Replies
- 28
- Views
- 1,543
9600 8 none 1
9600 8 none 1
-
12-03-2012, 01:10 PM
Thread: Infocon Trane Comm 4 Driver.
by dlhvac- Replies
- 3
- Views
- 546
broudy supply in phila has the drivers
broudy supply in phila has the drivers
-
12-03-2012, 01:00 PM
Thread: Infocon Trane Comm 4 Driver.
by dlhvac- Replies
- 3
- Views
- 546
yes it is available thru maxline drivers with...
yes it is available thru maxline drivers with infocon support for 10 years
-
12-03-2012, 12:56 PM
Thread: Trane Com4 to AX integration problem......
by dlhvac- Replies
- 28
- Views
- 1,543
Does the install have trane purple wire if not...
Does the install have trane purple wire if not your on your own
-
11-30-2012, 05:59 PM
Thread: Trane Com4 to AX integration problem......
by dlhvac- Replies
- 28
- Views
- 1,543
Approx 80 or more points per rtu all the...
Approx 80 or more points per rtu all the diagnostic alarms and you can also reset diagnostic faults
-
11-30-2012, 05:57 PM
Thread: Trane Com4 to AX integration problem......
by dlhvac- Replies
- 28
- Views
- 1,543
You can see more of the voyager and reliatel...
You can see more of the voyager and reliatel points than with tranes software
-
11-30-2012, 05:55 PM
Thread: Trane Com4 to AX integration problem......
by dlhvac- Replies
- 28
- Views
- 1,543
The zoning and rtu overides are done in the jace
The zoning and rtu overides are done in the jace
-
11-30-2012, 05:54 PM
Thread: Trane Com4 to AX integration problem......
by dlhvac- Replies
- 28
- Views
- 1,543
I would use a six if you are putting graphics on...
I would use a six if you are putting graphics on it if noy jace 2 should work watch your java heap and busy time on the jace comm four is a reource hog
-
11-30-2012, 01:32 PM
Thread: Trane Com4 to AX integration problem......
by dlhvac- Replies
- 28
- Views
- 1,543
Sorry but i dont give away stations that ive done...
Sorry but i dont give away stations that ive done but it is doable to integrate all that you stated
-
11-30-2012, 01:31 PM
Thread: Trane Com4 to AX integration problem......
by dlhvac- Replies
- 28
- Views
- 1,543
Maxline drivers owms the comm4 driver infocon...
Maxline drivers owms the comm4 driver infocon sold the driver division go them but has a contract for 10 years to provide support
-
11-29-2012, 08:14 PM
Thread: Trane Com4 to AX integration problem......
by dlhvac- Replies
- 28
- Views
- 1,543
worked very well have done 12 to date
worked very well have done 12 to date
-
10-23-2012, 01:36 PM
Thread: Niagara AX to Trane comm3 and comm4 advise
by dlhvac- Replies
- 27
- Views
- 2,770
you have to put the unit in tracer control and...
you have to put the unit in tracer control and command the input mode
-
09-28-2012, 07:26 PM
Thread: Sedona controller
by dlhvac- Replies
- 119
- Views
- 11,216
the ashrae show sent you an email
the ashrae show sent you an email
-
09-28-2012, 07:21 PM
Thread: Sedona controller
by dlhvac- Replies
- 119
- Views
- 11,216
the ashrae show
the ashrae show
-
09-26-2012, 08:05 PM
Thread: Sedona controller
by dlhvac- Replies
- 119
- Views
- 11,216
THE CONTROLLERS WILL BE OUT AT THE SHOW IN DALLAS...
THE CONTROLLERS WILL BE OUT AT THE SHOW IN DALLAS IM BETA TESTING A PROTOTYPE
-
09-15-2012, 03:12 PM
Thread: Sedona controller
by dlhvac- Replies
- 119
- Views
- 11,216
Have over 50 installed at different sites all...
Have over 50 installed at different sites all work flawlessly and yes they talk sedona modbus and bacnet all at the same time the new ones due out will have its own html5 graphics engine and it own...
-
08-16-2012, 09:49 AM
Thread: Niagara AX to Trane comm3 and comm4 advise
by dlhvac- Replies
- 27
- Views
- 2,770
Forgot using lon requires the firmware in chiller...
Forgot using lon requires the firmware in chiller to be the latest Trane will have to upgrade recommend using comm4
-
08-16-2012, 09:48 AM
Thread: Niagara AX to Trane comm3 and comm4 advise
by dlhvac- Replies
- 27
- Views
- 2,770
There are some issues with the commissioning of...
There are some issues with the commissioning of the lci-c chiller lon cards you have to set the response to the jace at no response to commission because some of the cards do not send this response
Results 1 to 25 of 46