Page 1 of 2 1 2

Search: Search took 0.00 seconds.

  1. Replies
    20
    Views
    1,275

    I only bought the blue electrostatic filter...

    I only bought the blue electrostatic filter because of the black stronger frame work.

    I've been through (3) of the flimsy cardboard pleated filters already. Each one collapsed but the force of...
  2. Replies
    20
    Views
    1,275

    What type filters should be used then ? I'm...

    What type filters should be used then ?

    I'm trying to talk the "Boss" into letting my cut a bigger hole in her dining room floor for the intake return. Not going over too well ! LOL!

    BTW,...
  3. Replies
    20
    Views
    1,275

    https://www.dropbox.com/s/qfyq7u48e1qkpkx/2013-12-...

    https://www.dropbox.com/s/qfyq7u48e1qkpkx/2013-12-11%2011.22.48.jpg

    https://www.dropbox.com/s/9l6a4lxbf4x8ivg/2013-12-11%2011.22.40.jpg
    ...
  4. Replies
    20
    Views
    1,275

    I assume this would cause the filter to collapse...

    I assume this would cause the filter to collapse as well ?

    I'm going to down for a look right now. I'll report back soon what I find out.
  5. Replies
    20
    Views
    1,275

    The filter was only a couple months old and still...

    The filter was only a couple months old and still pretty clean.

    I know our intake vent is way too small (under-sized) and needs to be enlarged. We've been in the house (18) years without any...
  6. Replies
    20
    Views
    1,275

    Why would you say something like that ? The...

    Why would you say something like that ?

    The Contractor installed it when I had the furnace installed last January. If you go back and look at the picture, their company's name is on the...
  7. Replies
    20
    Views
    1,275

    Not sure yet. The furnace is located under the...

    Not sure yet. The furnace is located under the house and not quick access. I have to shovel snow off the entrance door to access under the house.

    I have had (in the past) issues with the filter...
  8. Replies
    20
    Views
    1,275

    What would cause an overheat limit to be reached...

    What would cause an overheat limit to be reached ?

    The filter is only a few weeks old.
  9. Replies
    20
    Views
    1,275

    No, it shuts down, the exhaust fan comes right...

    No, it shuts down, the exhaust fan comes right back on and the furnace fires right back up.
  10. Replies
    20
    Views
    1,275

    Furnace Double Cycles......WHY ?

    I have a newer Rheem RGPS along with a new electronic thermostat.

    The system works well overall, but recently started an odd behavior.

    The furnace will double cycle before it finally turns...
  11. Correct. Nothing is insulated from what I can...

    Correct. Nothing is insulated from what I can tell. Just all the original duct work from the 1950s!

    Definately going to put that mil floor liner down ASAP!
  12. I was worried about over-working and burning out...

    I was worried about over-working and burning out the pump.
  13. Good stuff! Thank you. Given we were dumping...

    Good stuff! Thank you.

    Given we were dumping 5-10 gal/day last year, if I install a dehumidifier and drain it into the same pump as the furnace, do you think that pump can handle the xtra load ?...
  14. I suspect there is condensate in the furnace and...

    I suspect there is condensate in the furnace and ducts as well.

    The condensate line is clear and flowing. The pump is pumping as it should.

    Would it be wise to open up (and a vent) to the...
  15. Very good info folks! There are NO vents in...

    Very good info folks!

    There are NO vents in the foundation. It is stone all the way around. I do have it sealed (expandable foam) where possible.

    I like the idea of the heavy plastic for a...
  16. Very Heavy Condensation in Crawl Space (pics).... NEED ADVICE !

    Our house is just over 100 years old and has the furnace/AC coil located down underneath in an uninsulated crawl space. The actually area where the furnace is located is about 15' x 15' x 6' 6" in...
  17. It was they manner in which he expressed his...

    It was they manner in which he expressed his displeasure. VERY unprofessional. Had I been present when he said that to my wife in that manner, he would he left without a few teeth......but I guess he...
  18. The house does have updated (3 wire) wiring....

    The house does have updated (3 wire) wiring. Also, the furnace line is a dedicated run straight off the circuit panel box.

    I agree that a weak (no ground) connection will cause nuisance lockouts....
  19. The plug is a (3) pronged type. Will that suffice...

    The plug is a (3) pronged type. Will that suffice ?
  20. Well, I found the culprit that was causing the...

    Well, I found the culprit that was causing the furnace to NOT come ON fully. It was turning ON the inducer fan, burners firing and when the blower would go to START up the whole furnace would shut...
  21. Thank you all for your very helpful input. I...

    Thank you all for your very helpful input. I really do appreciate.

    It was a low bid job....$. The next lowest was double that!

    One thing I would like to do is move the connection point of the...
  22. Ok, I got ya now. Actually, those runs have very...

    Ok, I got ya now. Actually, those runs have very decent air flow, the only complaint is the long one (35' or so) puts out luke warm air by the time it gets to the register.

    The run we really have...
  23. I don't know about the filter door.... ?? The...

    I don't know about the filter door.... ??

    The AC coil was actually very clean when they pulled it out.

    They are coming back when the weather warms up (they said above 50 degrees) to recharge...
  24. No. It was installed vertically, but it was at...

    No. It was installed vertically, but it was at such an angle it was touching the outer metal cabinet. The Tech bent it back a bit so it is vertically straight up and down.

    That is the ONLY thing...
  25. I should mention also we have (3) CO2 detectors...

    I should mention also we have (3) CO2 detectors running. One in the crawl space (not far from the furnace), 1st and 2nd floors. None have ever gone off.

    Here's some old scary pics of the old...
  26. Yea, I was thinking that myself! LMAO!

    Yea, I was thinking that myself! LMAO!
  27. Are you refering to this pic ? 351341 ...

    Are you refering to this pic ?

    351341

    They didn't do that. I taped that about (10) years ago. I saw a gap between the (2) pipes and went to town with the duct tape.

    The outer (bigger...
  28. The crawl space I would guess to be around 5-600...

    The crawl space I would guess to be around 5-600 sq ft. ??

    The house is rather well insulated. Not drafty at all. It is however, very dry. We keep several small humidifers running most of the...
  29. You mean in the red box area ? BELOW This...

    You mean in the red box area ? BELOW

    This was original duct work from who knows how long ago. ?

    351351

    It's a pretty bizarre setup. That particular run goes into a very large diameter...
  30. RG PN 07 I believe.... I need to find the papers...

    RG PN 07 I believe.... I need to find the papers to verify that.
  31. I'm not clear on what you're asking. ??

    I'm not clear on what you're asking. ??
  32. What would a negative pressure in the house do ?...

    What would a negative pressure in the house do ?

    I was thinking a negative pressure may have built up under the house that may have restricted the flow out the flu pipe. Therefore causing the...
  33. BTW, the furnace has gone thru several cycles...

    BTW, the furnace has gone thru several cycles since this AM and appears to be doing much better. No more short cycling or shutting down during startups.

    Like I stated before, the ONLY thing the...
  34. I'm not quite sure which one your referring to....

    I'm not quite sure which one your referring to. ?? The flexible hose and the plenum (before the filter) are all new. The 2 - 12" ducts are from the old setup.

    What would installing a supply run...
  35. How much should this should this configuration...

    How much should this should this configuration have ?

    How can I add more capacity ?
  36. And here some still pics of the setup. ...

    And here some still pics of the setup.

    http://katmanduonline.net/albums/NewFurnace/
  37. No, it's in a crawl space under the house. The...

    No, it's in a crawl space under the house. The house is 101 years old.

    Here's a video I just took.

    http://www.youtube.com/watch?v=baxBdQCbyeQ&feature=youtu.be

    I believe the model is a...
  38. I don't think so. Yes, same Rheem furnace. ...

    I don't think so.

    Yes, same Rheem furnace.

    The Moderator merged these threads. I'm not sure why, the issues aren't related.... it is the same furnace though. ??
  39. 2- (12") flexible duct work.

    2- (12") flexible duct work.
  40. ok.... I'll post pics of the furnace/install a...

    ok.... I'll post pics of the furnace/install a bit later today.

    The chimney is clear for sure (cleaned it out last year) so I now that is not the issue. The vent pipe off the furnace is the same...
  41. Ok, Service Tech came out this AM, said it sounds...

    Ok, Service Tech came out this AM, said it sounds like the flu pressure switch is tripping. There wasn't any codes stored since we were instructed to reset the furnace by turning the circuit breaker...
  42. ok....Only thing is the original posting "short...

    ok....Only thing is the original posting "short cycling" has been fixed and this new issue is not related that.
  43. Yup. I know. They did come back and finish...

    Yup. I know.

    They did come back and finish hooking up the intake vent pipes as they said they would.

    There is a separate issue now where we had to call them today. He came out and said he had...
  44. Had to Reboot/Reset a New Rheen RGPS..... WHY was this necessary ?

    We just had a brand new Rheem RGPS installed a few weeks ago. Overall it's been working good. That was until a few days ago.

    The inducer fan would come on, burners fire and then everything would...
  45. I found a document On-line that shows the Temp...

    I found a document On-line that shows the Temp Rise --- 40 - 70 F for this unit.

    Going down to 23 degrees (where is the degree sign on the keyboard ??) by tomorrow AM so the Contractor best be...
  46. Very good info! The return air ducts are not...

    Very good info!

    The return air ducts are not yet connected to the "inside - 1st floor" return vent work. BTW, they are a pair of (12") ducts that run up there. The furnace is in a crawl space...
  47. Close I believe. The old one was 80,000...

    Close I believe. The old one was 80,000 btu.......the new one is 75,000 btu 80%. The Tech said the old one was about 35 years old and was about 50% efficient.

    I know he "should have" set the...
  48. The anticipator is set at .1 right now. I just...

    The anticipator is set at .1 right now. I just turned it up to .4 and see how it responds.

    Well, the furnace blower came on and blew cold air for about (5) minutes and then it turned OFF. NO HEAT...
  49. Thanks for the quick replies. This the...

    Thanks for the quick replies.

    This the type/style thermostat that is currently hooked up.

    345711
  50. Thanks for the quick replies. This the...

    Thanks for the quick replies.

    This the type/style thermostat that is currently hooked up.

    345711
Results 1 to 50 of 51