  1. Replies
    30
    Views
    4,253

    Windows 7/SCT

    Better a late answer than none. Tried loading SCT on a 7 machine today. Looks like SCT requires IIS 5.1, and it doesn't look like 7 can get there (easily). I do hear 5.0 supports 7 (or vice versa).
  2. Replies
    13
    Views
    1,098

    Thanks, for all your input guys. I'm calling this...

    Thanks, for all your input guys. I'm calling this a laptop issue. I had to load Lonmaker on another laptop as I was having issues with Lonmaker after trying that as well. With Lonmaker on the new...
  3. Replies
    13
    Views
    1,098

    The red is blinking once a second. I am using the...

    The red is blinking once a second. I am using the PC card at this time. I do have the USB converter somewhere though. I was attached to the network at the 520. I can try right at the board after...
  4. Replies
    13
    Views
    1,098

    summit-dude Wasn't intending to Trane bash. I...

    summit-dude
    Wasn't intending to Trane bash. I like there product in certain small applications such as area control, and they can certainly do a good job in a straight forward chiller plant that is...
  5. Replies
    13
    Views
    1,098

    I did give that a shot, but it said something...

    I did give that a shot, but it said something about no configuration details available, so I didn't spend much time with it. I did show the 520 plug in as registered. I may do more tomorrow. My LON...
  6. Replies
    13
    Views
    1,098

    Rover 6 Config trouble

    I finally need to use our Rover because a 520 mysteriously went unconfigured. It (Rover) gives an error:
    Run-Time error '-2147221231 (80040111)'
    Automation error
    ClassFactory cannot supply...
  7. Replies
    2
    Views
    364

    Thanks for the quick response. Is this only valid...

    Thanks for the quick response. Is this only valid for an actual physical C-Bus, for example, only the controllers on a particular BNA? I do know I also have issues with Excel Online remote, and that...
  8. Replies
    2
    Views
    364

    HW Care Global points

    I cannot figure out how to utilize global points in Care. I need to pull a couple of status points (hard-wired DI's) to a couple of other controllers, as well as a pseudo point. Can't get it to work....
  9. simsd How'd you make out with your Carrier...

    simsd

    How'd you make out with your Carrier BACnet interface? Mines good to go. It was a little quirky trying to ensure the point tables and data migrated from the target device, but that's...
  10. Taking a quick look at my config, I believe the...

    Taking a quick look at my config, I believe the protocol address and device instance need to be the same, and you may want to change Max Master to the highest address actually in use on the bus...
  11. This one is of interest to me, because as soon as...

    This one is of interest to me, because as soon as the bus gets run to mine, that's what I'm hooking to. I had that issue with another vendor via fieldserver when passed as AVs, and it was deeper on...
  12. Replies
    6
    Views
    1,447

    Just did a 30HX chiller today. 1st crack at this...

    Just did a 30HX chiller today. 1st crack at this interface and at using NST.The translator comes defaulted to element 200. if you are doing more than 1 on a CCN, you will have to get into config of...
  13. Replies
    6
    Views
    2,160

    Once you know the BACnet device ID of any device...

    Once you know the BACnet device ID of any device on the network, you can create a non-Trane BACnet device. All you need to do is go to site configuration, devices tab, create a non-Trane BACnet...
  14. Replies
    3
    Views
    528

    We are in the middle of updating to Macroserver....

    We are in the middle of updating to Macroserver. We have around 380 devices and should end up with over 4,000 points to an NAE55.

    We were getting NO updates, not infrequent ones, and all that took...
  15. Thread: HW Live Care

    by kingtuna
    Replies
    5
    Views
    584

    Thanks for the info. Who's trying 1st, you or...

    Thanks for the info. Who's trying 1st, you or I?:)

    I actually have other machines and this one is more or less devoted to Care right now, so I may give it a whirl.

    What concerns me, is how...
  16. Replies
    3
    Views
    528

    Gateway or Macroserver? New install? New problem?...

    Gateway or Macroserver? New install? New problem? I can try and remember what we did to correct this, but the last time was on the Macroserver. Can't remember for the gateway, but can dig up some...
  17. Thread: HW Live Care

    by kingtuna
    Replies
    5
    Views
    584

    HW Live Care

    I can't get Live Care to come up anymore, Care disappears but remains in the background. I have to reboot (after a couple error messages) to get back to Care, because if I try to reopen it, it says...
  18. Replies
    36
    Views
    2,008

    I believe this is the most important thread ever...

    I believe this is the most important thread ever encountered here. I never heard the term VE until I came to my present facility. We have in house engineers, use outside engineers, and educate...
  19. Replies
    36
    Views
    2,008

    1) Did you wash your hands after you went to the...

    1) Did you wash your hands after you went to the bathroom?

    2) Did you brush your teeth before bed?

    3) Get your hand out of the cookie jar!

    4) Good night, we'll take care of everything and...
  20. Replies
    8
    Views
    815

    Oops, just looked at a template. That's kind of...

    Oops, just looked at a template. That's kind of an autopilot thing for me, the extensions are filled in. As an end user and with some good branch people still left (A couple of vets around on their...
  21. Replies
    8
    Views
    815

    As long as you know where it's saving...

    As long as you know where it's saving (directory), it saves as a .dmo file I believe. It will be viewable in notepad. There is a tool out there to convert to ddl that is helpful for mapping in the...
  22. Replies
    6
    Views
    651

    Thanks Foyler, it is the Pseudo Point asterisk...

    Thanks Foyler, it is the Pseudo Point asterisk thing. Unfortunately, because of HW rules I couldn't get the software until I had the training, then didn't get involved in the project in this new...
  23. Replies
    6
    Views
    651

    HW Care Switching Logic Tables

    What am I doing wrong if I can printout and see the switching logic tables in Care, but can't get to them in the editor? I just need to change a couple of 0's to 2 or 3 or so for hysteresis (Pumps...
  24. Replies
    9
    Views
    1,188

    Sorry, was doing something else and missed the...

    Sorry, was doing something else and missed the bit about the switch and gauges at the pump. If the gauges are correct, it's really hard telling what's up from afar. If there is a switch there, it is...
  25. Replies
    9
    Views
    1,188

    While the VFD can be set up to do its own PID...

    While the VFD can be set up to do its own PID control, it is more likely that the controller that has the VFD Speed output on it also has the DP input on it, and references the setpoint written in...