Search:

Type: Posts; User: chadtech

Page 1 of 9 1 2 3 4

Search: Search took 0.02 seconds.

  1. Replies
    6
    Views
    321

    Must be a "controls problem"

    Must be a "controls problem"
  2. Replies
    0
    Views
    95

    Dorsett's Inc controllers

    Anyone have experience with this controls manufacturer?

    http://dorsett-tech.com/

    I've got a building with MS3 and MS4 controllers, will these communicate bacnet ms/tp?
  3. Thread: Ax Switcher

    by chadtech
    Replies
    5
    Views
    606

    Could I also get a link, please? Thanks

    Could I also get a link, please?

    Thanks
  4. Replies
    3
    Views
    275

    Possible duplicate node numbers on the network.

    Possible duplicate node numbers on the network.
  5. Replies
    1
    Views
    303

    Trane BMTB comm3/4 communication bridge

    Curious if anyone is using the Tracer communication bridge BMTB001AAA00 to get comm3/4 equipment to BACnet/IP into a niagara system? I have many customers with old BCUs and comm3 UCMs, looks like...
  6. If my memory serves me correctly, the unit will...

    If my memory serves me correctly, the unit will do supply fan fault if the fan command is off and the switch doesn't open. Therefore your jumper may be making things worse. Replace the fan switch.
  7. Replies
    2
    Views
    392

    Good question....I've never figured it out either.

    Good question....I've never figured it out either.
  8. Replies
    5
    Views
    982

    Thanks for the feedback!

    Thanks for the feedback!
  9. Replies
    5
    Views
    982

    AAM new CBT CBM controllers

    We have an opportunity to possibly become an AAM dealer. I'm curious if anybody is currently using their new CB controllers, which I believe they have gotten from the Cylon side. How are they?
  10. A station backup contains the station.

    A station backup contains the station.
  11. Replies
    6
    Views
    1,605

    Email sent. New construction. Thanks for your...

    Email sent.

    New construction. Thanks for your help!
  12. Replies
    6
    Views
    1,605

    manual J & D help

    Anybody willing to help me out with a manual j and d on my new house I'm building. Its been many years since I've done a calc by hand, I've looked at buying software, but, ouch $400 and I'm only...
  13. Replies
    13
    Views
    1,887

    I'd like to have those also. If you would please...

    I'd like to have those also. If you would please send them to me.
  14. Replies
    1
    Views
    488

    Niagara Energy Star Portfolio manager

    I am searching for an AX driver that can automatically push meter data to Energy Star Portfolio manager. Anybody seen or heard of such?

    Thanks!
  15. Replies
    11
    Views
    1,673

    Infocon sold the driver division to Maxline...

    Infocon sold the driver division to Maxline Solutions. There have been many updates to the comm4 driver. What version driver are you using. I used it on several jobs in the past few months with...
  16. Replies
    4
    Views
    841

    http://csicubed.com/portfolios/csv-driver/ ...

    http://csicubed.com/portfolios/csv-driver/

    I've used this driver before. Works pretty well. Not sure if this is what your looking for.
  17. Replies
    15
    Views
    2,168

    Be careful about how often you writing to CCN...

    Be careful about how often you writing to CCN points also. I had a job once where we were writing to the chilled water setpoint too often (reset) and it caused the Carrier controls on the chiller to...
  18. Replies
    10
    Views
    1,536

    Download the Trane Tracer BACnet Setup tool. From...

    Download the Trane Tracer BACnet Setup tool. From here:

    http://www.tranecds.com/COMMERCIAL/DesignAnalysis/DownloadCenter.aspx?i=909&p=18

    Plug into the white Trane BACnet UC400 using USB cable...
  19. Replies
    9
    Views
    1,900

    Sorry to bring this old thread up but I wanted to...

    Sorry to bring this old thread up but I wanted to clarify. I have a SiteLink 12 without a 2MB label. Its currently communicating modbus out of port B.

    Is it possible for this Sitelink to be...
  20. Replies
    4
    Views
    596

    I have the same legitimate complaint about the...

    I have the same legitimate complaint about the Niagara nav file. I have built my own HTML tree similar to the one in the demo station, although it has its limitations too. Let us know if you find a...
  21. Thread: Trucks

    by chadtech
    Replies
    23
    Views
    3,130

    I knew it was just a matter of time. I thought...

    I knew it was just a matter of time. I thought it was funny hence the reason I didn't correct it.:cheers:
  22. Thread: Trucks

    by chadtech
    Replies
    23
    Views
    3,130

    I think mechmike is referring to the nv200. ...

    I think mechmike is referring to the nv200. Those things are ugly as the north end of a southbound donkey! I drive a Ford Transit Connect and it works well, had to modify the dividing partition in...
  23. Replies
    7
    Views
    1,442

    If the OSS is in the jace, how do you get it up...

    If the OSS is in the jace, how do you get it up to the supervisor to put on a px?
  24. Replies
    14
    Views
    1,933

    :beat: PM me if you need local support.

    :beat:


    PM me if you need local support.
  25. Replies
    3
    Views
    794

    Trane COMM3 CSC

    Attention Trane guys. Interested in what is Trane's solution to older (1997) CSC units with the blue LED display that will only communicate Trane COMM3, am I correct that the new BCUs will no longer...
  26. This should be an easy panel to setup and wire. ...

    This should be an easy panel to setup and wire. I find it hard to believe that you can't easily find a contractor capable of getting this simple system working. Was the zone panel working before...
  27. Please share. Email in my profile.

    Please share. Email in my profile.
  28. Replies
    10
    Views
    1,506

    Keith, could I get a copy of the .bog also. I've...

    Keith, could I get a copy of the .bog also. I've always struggled to understand how to totalize data and put it into a report.

    Thanks!
  29. Replies
    8
    Views
    1,262

    Is it on a communication network? If so the...

    Is it on a communication network? If so the password is viewable and editable via the network. Otherwise I don't know of a way to reset the password.
  30. Replies
    11
    Views
    1,429

    My opinion.....Required-no, Recommended yes. I...

    My opinion.....Required-no, Recommended yes. I always at the end of a installation project go to the Lon device manager and highlight all devices, (even the local Lon device) and commission them,...
  31. Replies
    19
    Views
    2,753

    Oops forgot the attachment......438061

    Oops forgot the attachment......438061
  32. Replies
    19
    Views
    2,753

    MatrixTransform, I have been doing some digging...

    MatrixTransform, I have been doing some digging on this today and I have been able to get the hyperlink working but still can't figure out how to display the history chart on the relativized px. See...
  33. Honeywell Spyder Calculating suction gas superheat

    The question is whats the best way you can think to get the saturated suction temperature for the superheat calc.
  34. Replies
    5
    Views
    1,183

    Went to the job site today and reconnected the...

    Went to the job site today and reconnected the jace 485 and tried to duplicate the scenario and of course was unsuccessful. The chiller has been running fine for almost 2 weeks without the jace...
  35. I think you should get your facts straight before...

    I think you should get your facts straight before throwing rocks. Honeywell doesn't charge ANY extra for a Webs open license. And the spyder ILC are needed only when using the SpyderTool on a JACE...
  36. Replies
    5
    Views
    1,183

    When the display goes blank it shows only the...

    When the display goes blank it shows only the Carrier emblem (the one that circles the problem)! I think that is the screen it shows on boot up. I haven't been onsite to troubleshot yet, other...
  37. Replies
    5
    Views
    1,183

    No one has successfully used the CCN driver?

    No one has successfully used the CCN driver?
  38. Replies
    37
    Views
    4,142

    Osiyo, sorry to hear of your lose. You, your...

    Osiyo, sorry to hear of your lose. You, your family, and close friends are in my thoughts.
  39. Replies
    19
    Views
    2,753

    Thanks for the respnse. Can it be used to...

    Thanks for the respnse.

    Can it be used to display the supervisor history chart on the vav PX?
  40. Replies
    19
    Views
    2,753

    AX history chart on px

    I am having a brain fart or this isn't possible....been sitting here stumped for an hour!

    I have jaces with histories setup in them, sending the histories to the supervisor daily. All control...
  41. Replies
    5
    Views
    1,183

    Tridium AX CCN driver

    We have recently installed a Jace 6 with a CCN driver connected to just 1 19XRV chiller. Job went very well , learned all desired points. After about a week of normal operation, one morning the...
  42. Replies
    2
    Views
    555

    KitControl interval trigger and a select? Theres...

    KitControl interval trigger and a select? Theres many other way.......
  43. Also do you have the network terminated at each...

    Also do you have the network terminated at each end with terminating resistors?
  44. Is the meter/converter address unique? Do you...

    Is the meter/converter address unique? Do you have the baud rate, and parity setup correctly in the meter/converter?
  45. Replies
    11
    Views
    1,542

    Are these fully programmables or application...

    Are these fully programmables or application specific? If fully programmable then you will certainly need that additional tool. If asc then you should be able to perform replace, download and...
  46. Replies
    0
    Views
    558

    Single zone mini split BACnet

    I am looking for a single zone mini split heat pump that will easily communicate BACnet or a mini-split that I can put a programmable DDC controller on to control it. Specifically it needs to be a...
  47. Replies
    4
    Views
    963

    They are all serving the same space, the VAVs are...

    They are all serving the same space, the VAVs are slightly modified venom apps.

    There are no local sensor overrides.

    When should I start the RTU for recovery, unoccupied cooling etc.
    ...
  48. Replies
    4
    Views
    963

    Spyder VENOM VAVs RTU scheduling

    RTU with 15-20 vavs. I would like to use the recovery in the vav spyders, what would be the most effective way to start/stop the RTU?
  49. Replies
    10
    Views
    2,108

    Tuning policies max write time.

    Tuning policies max write time.
  50. Replies
    2
    Views
    938

    Yes. It was displaying properly with less VAVs,...

    Yes. It was displaying properly with less VAVs, but once I had added all 37 no bueno.