  1. Replies
    45
    Views
    3,130

    Yes already!!

    Yes already!!
  2. Replies
    11
    Views
    1,808

    The worst thing is trying to get info from...

    The worst thing is trying to get info from turbocor or smardt or mcquay or even multistack if you have a control question. I think all of them are still going through growing pains with this new...
  3. Thread: 19xr

    by steward
    Replies
    6
    Views
    538

    The DP switches most always get plugged up on the...

    The DP switches most always get plugged up on the condenser side. There is a SB detailing get rid of them and just letting the machine use its other sensors to shut off on low flow conditions.
  4. Replies
    9
    Views
    611

    I just purchased a pump from Grainger today. I'm...

    I just purchased a pump from Grainger today. I'm going to use it tomorrow to circulate acid thru a condenser bundle. Cost 150. I'll let you know how it did tomorrow.
  5. Replies
    6
    Views
    598

    I've also used it.

    I've also used it.
  6. Replies
    88
    Views
    4,692

    Think of it like this, An Ahu with inlet guide...

    Think of it like this, An Ahu with inlet guide vanes, as the vanes close amperage goes down since you are moving less air. Basically the vanes are adding a restriction. JMO
  7. Replies
    11
    Views
    1,025

    Little slow here. Most years I'll have at least...

    Little slow here. Most years I'll have at least two overhauls maybe four right after the first of the year. This year none. Guess I'll be doing a lot of oil changes this year.
  8. Thread: Carrier NST V

    by steward
    Replies
    5
    Views
    664

    I work for a mech. cont. We purchased NSTV about...

    I work for a mech. cont. We purchased NSTV about a year ago thru our local carrier parts house.
  9. Replies
    5
    Views
    663

    We had several guys working at our shop on travel...

    We had several guys working at our shop on travel cards for over a year. Our local was low on work, so they did not transfer them till work picked up. They were doing refer work, which none of the...
  10. Replies
    5
    Views
    1,337

    We have installed several. So far no big...

    We have installed several. So far no big problems. Smardt seems to be going through "growing pains". The IOM's they send with their units may be outdated by the time your ready to do startup. All...
  11. Replies
    11
    Views
    2,591

    We also had one that was bad. Pulled it out and...

    We also had one that was bad. Pulled it out and also did the ch530 works well.
  12. It does sound like a 23xl. I take care of a few...

    It does sound like a 23xl. I take care of a few and have had to rebuild several slide valves due to seals leaking.
  13. Replies
    4
    Views
    824

    If you or someone at your co. has been "Factory...

    If you or someone at your co. has been "Factory Trained" then the software is on the T-core website. Must have the proper login and password to get to it
  14. Thread: RTHA255

    by steward
    Replies
    4
    Views
    680

    RTHA255

    Can the load and unload solenoid valves be replaced with out pulling the gas? Thanks
  15. Replies
    2
    Views
    792

    Balibe, Thanks for the reply. What I should have...

    Balibe, Thanks for the reply. What I should have said was that I don't know if the battery was bad and we lost power there by losing the software, or if that was assumed and something else is...
  16. Replies
    2
    Views
    792

    Carrier PSIO 39T II

    Hello all, This PSIO is used on an AHU. It has lost its software. Red LED blinks about two times per second. I am not sure if the battery was bad or not, got replaced before I arrived. Is there...
  17. Replies
    7
    Views
    740

    I won't be at this one, but two others from...

    I won't be at this one, but two others from company will be there. Should be a nice one to spend a few extra days playing at the sites. Have fun
  18. Replies
    12
    Views
    1,423

    Check out the Lennox Himiditrol system. Seems to...

    Check out the Lennox Himiditrol system. Seems to work ok, but it will cost you some doe. Not only to buy but also to run. Good Luck
  19. Replies
    2
    Views
    447

    I have never had one stick, but yes they can be...

    I have never had one stick, but yes they can be pulled apart and inspected. I think you could order parts if needed. I would think you would see low discharge superheat if stuck open.
  20. Thread: Roll on scale

    by steward
    Replies
    1
    Views
    457

    Grainger has one in their catalog. A little...

    Grainger has one in their catalog. A little pricey. I also rented one from a local company several times before.
  21. Replies
    6
    Views
    861

    As a temp repair I have used the 2 part epoxy...

    As a temp repair I have used the 2 part epoxy tubes you can buy from the hardware store for Marine use. Only tried this on small leaks but works till the tower can be drained and repaired with...
  22. Thread: 19 DM Starters

    by steward
    Replies
    14
    Views
    1,202

    I would suggest looking into a Benshaw SSS. ...

    I would suggest looking into a Benshaw SSS. Seems to be a good product.
  23. Replies
    4
    Views
    529

    What OS are you trying to load it onto?

    What OS are you trying to load it onto?
  24. Replies
    14
    Views
    1,472

    Vari-prime systems seem to work well. Two -way...

    Vari-prime systems seem to work well. Two -way valves at all Ahu's etc. Control Chw pump Vfd to system diff press stpt. Maintain min flow at chiller with a bypass valve. Chiller selection is...
  25. Replies
    10
    Views
    765

    Lots of equipment. Air cooled, water cooled, dx,...

    Lots of equipment. Air cooled, water cooled, dx, and some absorbers too.