Search:

Type: Posts; User: DaveCR

Page 1 of 13 1 2 3 4

Search: Search took 0.03 seconds.

  1. Thread: Rmcc

    by DaveCR
    Replies
    4
    Views
    277

    From this document, it looks like a software...

    From this document, it looks like a software package called UltraSite is used to program REFLECS controllers.
    http://www.emersonclimate.com/Documents/Retail%20Solutions/026-1102Rev4.pdf
  2. Replies
    55
    Views
    3,980

    Worst programmable controller ever

    What is the worst controller / system you have ever seen? (since we aren't supposed to bash, let's keep this to obsolete stuff)

    My vote is for the Johnson Controls DSC-3500.

    It was born in the...
  3. I forgot there were two versions of the LCP; I...

    I forgot there were two versions of the LCP; I never used one of the 100s. http://www.vikingcontrols.com/_documents/Product/635067.PDF
    The LCP did allow for passive analog inputs making it an easier...
  4. My first use of the 9100 series, in 1990, was...

    My first use of the 9100 series, in 1990, was with some imported DC-9100s. I don't recall the point count, but do remember that the AI hardware supported only 0-10 Vdc. They were programmed with a...
  5. I have used the Simply VAV product and found it...

    I have used the Simply VAV product and found it is pretty easy to set up, and worked as advertised.
  6. Replies
    2
    Views
    346

    The attached brochure explains how this, and most...

    The attached brochure explains how this, and most other single phase, condenser fan controller works.

    This controller will proportionally control between Min and Max and has the option to hold at...
  7. Replies
    11
    Views
    914

    Search the web a bit. I tried that indeed site...

    Search the web a bit. I tried that indeed site with St. Louis and the average salaries seemed somewhat in line; it would be more helpful if they gave a range of salaries.
    ...
  8. The OP has a voyager...

    The OP has a voyager...
  9. Replies
    11
    Views
    841

    The company I work for uses Tech Tool by IFS. I...

    The company I work for uses Tech Tool by IFS. I absolutely despise the product. Why? It takes about four times longer to fill out than a paper ticket. The field interface is clumsy and data entry is...
  10. Replies
    9
    Views
    577

    Trane+Modbus+gateway=BACnet=gateway+CCN+Carrier. ...

    Trane+Modbus+gateway=BACnet=gateway+CCN+Carrier. Makes a BACnet guy wish for LON.
  11. Replies
    2
    Views
    292

    While most modern controllers have decent...

    While most modern controllers have decent electrical isolation odd things still happen.

    I am not a fan of TattleTails as they don't catch quick, small current changes. While expensive, 1/128 A...
  12. Thread: Parker VVT

    by DaveCR
    Replies
    4
    Views
    808

    Since seve77 hasn't been here since 2011 I doubt...

    Since seve77 hasn't been here since 2011 I doubt you get a response. (click on the user id and select View Profile)
  13. Replies
    18
    Views
    1,380

    3500's or 8500's? There is a line in a Stooge's...

    3500's or 8500's? There is a line in a Stooge's short where Curly says "A hot steak is better than a cold chop" Which is like deciding between Power Perfect and Cal1.
  14. Replies
    18
    Views
    1,380

    Wow, the second person I know of that used one of...

    Wow, the second person I know of that used one of those things. My right thumb has permanent nerve damage :grin2:
  15. OP, basically what they said but, some of the...

    OP, basically what they said but, some of the newer thermostats are quite a bit more sophisticated. White Rodgers and Honeywell are two of the bigger names in the market. Download a couple of owner's...
  16. Replies
    1
    Views
    228

    If the person that programmed the FX07 set up the...

    If the person that programmed the FX07 set up the AI point(s) offset slot, then yes. Otherwise no.

    Best practice is to calibrate or replace the humidity transmitter.
  17. Replies
    3
    Views
    484

    Try using the Jci N2 Import Manager.

    Try using the Jci N2 Import Manager.
  18. Thread: Fx30 access

    by DaveCR
    Replies
    4
    Views
    315

    If you are using IE try adding the FX30 to the...

    If you are using IE try adding the FX30 to the Compatibility View list. While you are at it open the Java console, cancel automatic updates and add the FX to the Exception List. These steps usually...
  19. Replies
    18
    Views
    1,380

    Direct control of the DOs from a supervisory...

    Direct control of the DOs from a supervisory controller works fine. The quirk is the DX will not always display (locally) the point as being overridden. Since I've never had an issue with a JCI...
  20. Johnson has MAP Gateway for their controllers. I...

    Johnson has MAP Gateway for their controllers. I haven't used the product.
    Maybe a BACnet to Modbus gateway with some HMI freeware could be made to work.
  21. Replies
    11
    Views
    741

    Thanks. Happy New Year!

    Thanks.
    Happy New Year!
  22. Replies
    9
    Views
    788

    I think the fitting is a cord strain relief like...

    I think the fitting is a cord strain relief like an SR-50-250; the assembly was probably field built. The element is anyone's guess.
  23. Replies
    11
    Views
    741

    Finally go back to that place. New addresses for...

    Finally go back to that place. New addresses for devices at 1, 2 and 3 did the trick.
  24. Replies
    2
    Views
    319

    See page 120....

    See page 120....
  25. Replies
    11
    Views
    741

    I figured out a way to get this device online....

    I figured out a way to get this device online. Disable comm to 1,2 and 3. Add the device manually. Enable comm to 1,2 and 3.
    The 1611 is still not discoverable by the FX60, but is now communicating...
  26. Replies
    11
    Views
    741

    Thank you for the replies. I've thought about...

    Thank you for the replies.
    I've thought about the reserved addresses, but the other two PCx controllers work fine. However, this is probably the first thing I try. Maybe swapping addresses between...
  27. Replies
    11
    Views
    741

    PCT via Bluetooth works fine if the controller is...

    PCT via Bluetooth works fine if the controller is disconnected from the network. PCT via bacnet router works fine if the controller is connected to the network.
  28. Replies
    11
    Views
    741

    Eleven. There are FX controllers at addresses 1,2...

    Eleven. There are FX controllers at addresses 1,2 and 3. I have thought about changing these (and may still do so), but the other two PCx controllers don't seem to mind.
  29. Replies
    11
    Views
    741

    FX60 not discovering PCG16xx

    FX60 with 11 field devices. Eight controllers are older FX bacnet and three are PCx. The recently added PCG1611 is not discovered by the FX60 and if manually added will not come online. What I have...
  30. Replies
    11
    Views
    1,229

    If CommPro and Builder are recent maybe the...

    If CommPro and Builder are recent maybe the Recycle Bin contains the APD files.
  31. Replies
    5
    Views
    720

    Mammoth has an active web site....

    Mammoth has an active web site. http://www.mammoth-inc.com/
  32. JSLLC4Life - Thanks for the offer, but my need...

    JSLLC4Life - Thanks for the offer, but my need for the software is past. Long, nine month horror story regarding JCI support...
  33. Distech is apparently going proprietary. They...

    Distech is apparently going proprietary. They have removed the programming tools from their public site. I filled out their software request form, including the name of the distributer we buy from,...
  34. Replies
    10
    Views
    1,248

    If those points are in a Metasys N30 "program"...

    If those points are in a Metasys N30 "program" then, yes. If those points are in an NCM or NAE then, no.
  35. Replies
    30
    Views
    3,018

    If the UPC Open was factory installed the point...

    If the UPC Open was factory installed the point mapping should be configured properly. There are several good trouble shooting threads in this forum; search "carrier upc" (with quotes).

    If the UPC...
  36. Replies
    10
    Views
    1,248

    With M-Tools you will be able to program and...

    With M-Tools you will be able to program and commission: VAV, VMA, DX, TC, AHU and UNT controllers. With the exception of the DX, you will need some form of RS-485 adapter (USB, RS232, N30 pass...
  37. Replies
    7
    Views
    760

    Johnson ABCS distributors will sell just about...

    Johnson ABCS distributors will sell just about everything across the counter. You can become a non-direct ABCS contractor through the distributor; that will give you access to the Tridium Jace...
  38. Replies
    3
    Views
    585

    To my knowledge, the simulator will not work with...

    To my knowledge, the simulator will not work with XM modules nor slave N2 controllers. The former crashes the software, while the latter ignores the slave devices.
    One workaround is to make a copy...
  39. Facility Explorer - 5 year update --FX...

    Facility Explorer - 5 year update

    --FX Controllers--
    History (almost)

    --LX Controllers--
    I have had one nightmare experience with these. Seven months and counting without a resolution.
    ...
  40. Thread: Carel Repair

    by DaveCR
    Replies
    5
    Views
    1,057

    plccenter.com lists some PCO3 models as stock...

    plccenter.com lists some PCO3 models as stock items and also state they repair them. Having never used their services I can offer no recommendation in that regard.
  41. Replies
    17
    Views
    3,504

    The discontinuation notice states the DX and ASCs...

    The discontinuation notice states the DX and ASCs will be discontinued this month and when the current stock is gone that is it. However, the notice also states those products will not be...
  42. Replies
    14
    Views
    2,298

    Cool. It's good to see someone else likes to...

    Cool.

    It's good to see someone else likes to have some fun with controls.
  43. Replies
    2
    Views
    703

    Some ten years ago I was told by our local rep....

    Some ten years ago I was told by our local rep. that it is a proprietary protocol.
    I know we aren't supposed to bash equipment vendors, but around here they are known as Rabid Air.
  44. Replies
    2
    Views
    700

    I don't know of a 10C1 alarm, but OC1 is valid...

    I don't know of a 10C1 alarm, but OC1 is valid (over current when accelerating)
    Here's the manual.

    538311
  45. Replies
    5
    Views
    1,036

    My observations are for the 5.7" model. Pros It...

    My observations are for the 5.7" model.
    Pros
    It has a bright screen and is nicely finished.
    Many communications options.
    Configuration software is solid.
    Cons
    Touch screen response to taps and...
  46. Lowering the baud rate will be of some help. If...

    Lowering the baud rate will be of some help.
    If there aren't any competing wireless networks, lock the WBTs to a single channel.
    I would guess there are some tuning policies that could be adjusted.
  47. Replies
    2
    Views
    740

    Link a BooleanWritable to StatusBooleanToBoolean...

    Link a BooleanWritable to StatusBooleanToBoolean to EmailService / Enable. You may need to execute a clearQueue action on the OutgoingAccount before email is re-enabled.
  48. The FEC line has no provisions (software or...

    The FEC line has no provisions (software or hardware) to operate the stepper motor on that valve.
  49. Replies
    4
    Views
    2,303

    The Trane document in this thread may be of help....

    The Trane document in this thread may be of help.
    http://hvac-talk.com/vbb/showthread.php?792662-BCI-R
  50. Replies
    9
    Views
    1,508

    Option 1 - if you have access to the PID tuning...

    Option 1 - if you have access to the PID tuning parameters and integration can be set to zero (the latter makes some Carriers a no go) try this. On both AHUs: Set the VFD acceleration to five minutes...
Results 1 to 50 of 641
Page 1 of 13 1 2 3 4